The PLCnext Control AXC F 1252 for the Axioline I/O system is fast, robust, and easy to use. This means it is consistently designed for maximum performance, easy handling, and use in harsh industrial environments.
AXC F 1252
-
Controller
1646469
Controller (SPS), PLCnext Control; Programming: High-level language and IEC 61131-3; Operating system: Yocto/Linux® (real-time); Programming tool: PLCnext Engineer, Eclipse®, Visual Studio®, MATLAB®/ Simulink®; IoT connection: PROFICLOUD and every cloud via cloud connectors; Development process certified in accordance with IEC 62443-4-1; Processor: Arm® Cortex®-A55, 2x 1.7 GHz.
Free download available.
Downloads
Product details
| Product type | Controller |
| Product family | PLCnext Control |
| Type | modular |
| Special properties | Development process certified in accordance with IEC 62443-4-1 |
| Insulation characteristics | |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Trusted Platform Module | TPM 2.0 |
| Flash memory | 1.1 GByte (internal flash memory) |
| Retentive data storage | 16 kByte |
| RAM | 1024 Mbyte |
| IoT capability: PROFICLOUDIoT capability: PROFICLOUD | |
| IoT platform | PROFICLOUD |
| Supports cloud computing | yes |
| IoT capability: PROFICLOUDIoT capability: PROFICLOUD | |
| IoT platform | PROFICLOUD |
| Supports cloud computing | yes |
| IEC 61131 runtime system | |
| Program memory | 8 Mbyte |
| Data storage system | 12 Mbyte |
| Axioline | |
| Amount of process data | max. 1482 Byte (per station (total input and output data)) |
| max. 1024 Byte (Axioline F local bus (input)) | |
| max. 1024 Byte (Axioline F local bus (output)) | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) |
| INTERBUS-Master | |
| Amount of process data (Axioline input/output data max.) | max. 1482 Byte (per station (total input and output data)) |
| Amount of process data (Axioline input data max.) | max. 1024 Byte (Axioline F local bus (input)) |
| Amount of process data (Axioline output data max.) | max. 1024 Byte (Axioline F local bus (output)) |
| PROFINET | |
| Device function | PROFINET controller, PROFINET device |
| Update rate | min. 8 ms (4 devices) |
| min. 32 ms (16 devices) | |
| Process data width | 2 Byte ... 512 Byte (PROFINET device) |
| Conformance Class | B |
| Device ID | 0193hex |
| Vendor ID | 00B0hex |
| Function | |
| Industrial cybersecurity | yes |
| Programming data | |
| Register length (master) | 1482 Byte |
| Functionality | |
| Programming languages supported | Symbolic flowchart (SFC) |
| Ladder diagram (LD) | |
| Function block diagram (FBD) | |
| Structured text (ST) | |
| C++ | |
| C# | |
| Java | |
| Python® | |
| Simulink® | |
| System requirements | |
| Application interface | OPC UA® |
| Maximum power dissipation for nominal condition | 3.2 W (3.2 W = 13.2 W - 10.0 W) |
| Real-time clock | |
| Realtime clock | yes (not buffered) |
| Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple (± 5 %)) |
| Current draw | max. 640 mA (with 2 A at UBus for the I/Os and UL = 19.2 V) |
| Current consumption | typ. 63 mA (without I/Os and UL = 24 V) |
| Power consumption | max. 13.2 W (with 2 A at UBus for the I/Os and UL = 24 V) |
| Protective circuit | Reverse polarity protection; electronic |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Power supply unit | 2 A |
| Supply of the logic voltage UL | |
| Connection method | Push-in connection |
| Conductor cross-section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section AWG | 24 ... 16 |
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 1.5 mm² |
| Conductor cross-section, flexible, with ferrule, without plastic sleeve | 0.2 mm² ... 1.5 mm² |
| 0.2 mm² ... 1.5 mm² | |
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 1.5 mm² |
| Stripping length | 10 mm |
| Supported protocols | HTTP (only for access to the recovery system) |
| HTTPS | |
| PROFINET | |
| INTERBUS (via the extension module AXC F IL ADAPT) | |
| Modbus/TCP | |
| Modbus/RTU (via corresponding library) | |
| CANopen® (via corresponding library) | |
| DALI (via corresponding library) | |
| DALI-2 (via corresponding app) | |
| HART (via corresponding library) | |
| IO-Link® (via corresponding library) | |
| MQTT (via corresponding app) | |
| OPC UA® Server | |
| OPC UA® Client (License required) | |
| DHCP (via corresponding library) | |
| SFTP | |
| SMTP (via corresponding library) | |
| SNTP (via corresponding library) | |
| SNMP (via corresponding library) | |
| DNS (via corresponding library) | |
| DNP3 (via corresponding library) | |
| IEC 60870-5-1 (via corresponding library) | |
| IEC 60870-5-104 (via corresponding library) | |
| IPsec | |
| syslog | |
| Web server | yes |
| Axioline F local bus | |
| Number of interfaces | 1 |
| Connection method | integrated bus socket |
| Transmission speed | 100 Mbps |
| Ethernet | |
| Bus system | RJ45 |
| Number of interfaces | 1 |
| Connection method | RJ45 jack |
| Note on the connection method | Auto negotiation and autocrossing |
| Transmission speed | 10/100 Mbps (full duplex) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Transmission length | max. 100 m |
| Dimensional drawing |
|
| Width | 45 mm |
| Height | 122 mm |
| Depth | 75 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Color (Housing) | gray (RAL 7042) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 60 °C up to 2000 m above mean sea level |
| Operating altitude > 2000 m above mean sea level: Observe temperature derating | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (according to DIN EN 61131-2) |
| Shock (operation) | 30g (IEC 60068-2-27) |
| Vibration (operation) | 5g (IEC 60068-2-6) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
| UL, USA/Canada | |
| Identification | cULus |
| Certificate | E238705 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Electrostatic discharge (ESD)IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge |
| Immunity test in accordance with EN IEC 61000-6-2 Electromagnetic fieldsIEC 61000-4-3 Criterion A, Field intensity: 10 V/m | |
| Immunity test in accordance with EN IEC 61000-6-2 Fast transients (burst)IEC 61000-4-4 Criterion B, ±2 kV | |
| Immunity test in accordance with EN IEC 61000-6-2 Transient overvoltage (surge)IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1.0 kV | |
| Immunity test in accordance with EN IEC 61000-6-2 Conducted interferenceIEC 61000-4-6 Criterion A, Test voltage 10 V | |
| Noise emission test in accordance with EN IEC 61000-6-3 Class B |
| Mounting type | DIN rail mounting |
| Item number | 1646469 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | DRA |
| Product key | DRADAI |
| GTIN | 4067923176423 |
| Weight per piece (including packing) | 170.2 g |
| Weight per piece (excluding packing) | 137 g |
| Customs tariff number | 85371091 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27242207 |
| ECLASS-15.0 | 27242207 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 6(c), 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Diboron trioxide (CAS: 1303-86-2) |
| Lead (CAS: 7439-92-1) | |
Compatible products
Your advantages
Real-time-capable Linux operating system for deterministic and reliable execution of time-critical processes
Supports numerous protocols such as: HTTP, HTTPS, FTP, OPC UA, SNTP, SNMP, SMTP, SQL, MySQL, DCP, etc. – for smooth communication with IT systems
Direct connection to the Proficloud, the PLCnext Store and any cloud platforms – for seamless IoT integration of your applications
Support for numerous fieldbus protocols (PROFINET, Modbus TCP/RTU, Ethernet/IP, etc.) for easy integration into existing automation technology systems and installations
Maximum design freedom thanks to the combination of classic PLC programming with modern high-level languages such as C++, C#, or Python
Meets the highest security requirements of industrial automation – for the protection of your applications and data
PHOENIX CONTACT Trading LLC