MACX MCR-RTD-I
   - 
  Temperature measuring transducer
    
      1050192
      
      
    
  
      Temperature transducer, converts signals from resistance temperature detectors and resistors into analog 0/4 - 20 mA signals. Freely programmable, screw connection, SIL, 3-way electrical isolation, standard configuration.
      Free download available.
      Downloads
    
  Product details
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | 
| Product type | Temperature transmitter | 
| Product family | MACX Analog | 
| Application | Temperature | 
| No. of channels | 1 | 
| Configuration | Software | 
| Functionality | |
| Configuration | Software | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Step response (0–99%) | ≤ 1.7 s | 
| Temperature coefficient, typical | 0.01 %/K | 
| Transmission error, typical | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) | 
| Electrical isolation | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 300 Vrms | 
| Insulation | Safe isolation | 
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Electrical isolation Input/power supply IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Supply | |
| Nominal supply voltage | 24 V DC -20 % ... +25 % | 
| Supply voltage range | 19.2 V DC ... 30 V DC | 
| Power dissipation | ≤ 0.76 W | 
| Power consumption | ≤ 1 W | 
| Signal | |
| Number of inputs | 1 | 
| Measurement | |
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire | 
| Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) | 
| Linear resistance measuring range | 0 Ω ... 50 kΩ | 
| Potentiometer resistance range | 0 Ω ... 50 kΩ | 
| Max. permissible overall conductor resistance | 50 Ω (Per cable) | 
| Sensor input current | 10 µA ... 210 µA (Up to 2x 210 µA with 3-conductor technology) | 
| Temperature measuring range | ≥ 50 K | 
| Signal: Current | |
| Number of outputs | 1 | 
| Configurable/programmable | Yes | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA (SIL) | |
| Max. current output signal | ≥ 21 mA | 
| Load/output load current output | ≤ 600 Ω | 
| Output ripple (current) | < 15 µAPP | 
| < 10 µArms | |
| Behavior in the event of a sensor error | Freely definable | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 14 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Test socket | |
| Max. diameter | 2 mm | 
| Ex installation (EPL) | Gc | 
| Div. 2 | 
| Status display | Green LED (supply voltage) | 
| Red LED, flashing 2.8 Hz (cable error, sensor error on input or output, ERR) | |
| Red LED, flashing 1.2 Hz (simulation mode, ERR) | |
| Red LED, permanently on (module error, ERR) | 
| Dimensional drawing | 
                 | 
            
| Width | 12.5 mm | 
| Height | 112.5 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C ... 70 °C (Any mounting position) | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) | 
| Ambient temperature (operation) | -40 °C ... 70 °C | 
| Test voltage | 2.5 kV | 
| Rated insulation voltage | 300 Vrms | 
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m ... 3000 m | 
| Ambient temperature (operation) | -40 °C ... 63 °C | 
| Test voltage | 2.25 kV | 
| Rated insulation voltage | 150 Vrms | 
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m ... 4000 m | 
| Ambient temperature (operation) | -40 °C ... 56 °C | 
| Test voltage | 2 kV | 
| Rated insulation voltage | 150 Vrms | 
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m ... 5000 m | 
| Ambient temperature (operation) | -40 °C ... 49 °C | 
| Test voltage | 1.75 kV | 
| Rated insulation voltage | 150 Vrms | 
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  II 3 G Ex ec ic IIC T4 Gc | 
| Certificate | IBExU19ATEX1006 X | 
| IECEx | |
| Identification | Ex ec ic IIC T4 Gc | 
| Certificate | IECEx IBE 19.0001 X | 
| UL, USA/Canada | |
| Identification | UL 61010 Listed | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC T4 | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA00000AG | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Certificate | SEBS-A.150520/17, V2.0 | 
| Systematic Capability | |
| Identification | 2 | 
| INMETRO | |
| Identification | Ex ec ic IIC T4 Gc | 
| Certificate | DNV 21.0064 X | 
| EAC Ex | |
| Identification |  2Ex ec ic IIC T4 Gc | 
| Certificate | BY/112 02.01 TP012 103.01 00082 | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | A | 
| EMC | B | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 1 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 1 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 1 % | 
| Electrical isolation | 3-way isolation | 
| Mounting type | DIN rail mounting | 
| Item number | 1050192 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK1115 | 
| Product key | DK1115 | 
| GTIN | 4055626666105 | 
| Weight per piece (including packing) | 174,4 g | 
| Weight per piece (excluding packing) | 150 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210129 | 
| ECLASS-15.0 | 27210129 | 
ETIM
| ETIM 9.0 | EC002919 | 
UNSPSC
| UNSPSC 21.0 | 41112100 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-50
               An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | 8c831623-5052-477f-a344-2f0a0afc3ac3 | 
Compatible products
- 
    
      
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connector 2695439
 - 
    
      
ME 6,2 TBUS-PR-ADAPTER - DIN rail bus connector 1136500
 - 
    
      
MCR-DP - Separating plate 1430594
 - 
    
      
EA-MSTB 2,5/ 5 - Accessories 1831016
 - 
    
      
TC-D37SUB-AIO16-EX-PS-UNI - Module carrier 2902932
 - 
    
      
TC-D37SUB-ADIO16-EX-P-UNI - Module carrier 2924854
 - 
    
      
IFS-USB-PROG-ADAPTER - Programming adapter 2811271
 - 
    
      
IFS-BT-PROG-ADAPTER - Adapter 2905872
 - 
    
      
MPS-IH WH - Insulating sleeve 0201663
 - 
    
      
MPS-IH RD - Insulating sleeve 0201676
 - 
    
      
MPS-IH BU - Insulating sleeve 0201689
 - 
    
      
MPS-IH YE - Insulating sleeve 0201692
 - 
    
      
MPS-IH GN - Insulating sleeve 0201702
 - 
    
      
MPS-IH GY - Insulating sleeve 0201728
 - 
    
      
MPS-IH BK - Insulating sleeve 0201731
 - 
    
      
MPS-MT - Test plug 0201744
 - 
    
      
UC-EMLP (11X9) - Plastic label 0819291
 - 
    
      
UC-EMLP (11X9) YE - Plastic label 0822602
 - 
    
      
UC-EMLP (11X9) CUS - Plastic label 0824547
 - 
    
      
UC-EMLP (11X9) YE CUS - Plastic label 0824548
 - 
    
      
UC-EMLP (11X9) SR - Plastic label 0828094
 - 
    
      
UC-EMLP (11X9) SR CUS - Plastic label 0828098
 - 
    
      
US-EMLP (11X9) - Plastic label 0828789
 - 
    
      
US-EMLP (11X9) YE - Plastic label 0828871
 - 
    
      
US-EMLP (11X9) SR - Plastic label 0828872
 - 
    
      
LS-EMLP (11X9) WH - Device marker 0831678
 - 
    
      
LS-EMLP (11X9) SR - Device marker 0831705
 - 
    
      
LS-EMLP (11X9) YE - Device marker 0831732
 - 
    
      
MACX MCR-PTB - Power and error message module 2865625
 - 
    
      
MACX MCR-PTB-SP - Power and error message module 2924184
 - 
    
      
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
 - 
    
      
SZS 0,6X3,5 - Screwdriver 1205053
 
Your advantages
Power supply possible via DIN rail connector
        Programming possible during operation, when measuring circuit is connected, and also when power is switched off using the IFS-USB-PROG-ADAPTER programming adapter
        Installation in zone 2, protection type "ec" (EN 60079-7) permitted
        3-way electrical isolation
        Status indicator for supply voltage, cable, sensor, and module errors
        Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
        Output: 0 mA ... 20 mA or 4 mA ... 20 mA
        PHOENIX CONTACT B.V.
        
        Hengelder 56, 6902 PA Zevenaar, Postbus 246, 6900 AE Zevenaar