MACX MCR-EX-T-UI-UP
-
Temperature measuring transducer
2865654
Freely programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer in 2-, 3-, or 4-conductor technology, thermocouples, electrical isolation, wide-range power supply, screw connection, SIL, PL.
Free download available.
Downloads
Product details
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product type | Temperature transmitter |
Product family | MACX Analog |
Type | Ex i signal conditioners with SIL and PL Functional Safety |
Configuration | DIP switches |
Software | |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Functionality | |
Configuration | DIP switches |
Software |
Electrical isolation | 4-way isolation |
Step response (0–99%) | ≤ 1.75 s (SIL on) |
1.3 s (SIL off) | |
Maximum temperature coefficient | 0.01 %/K |
Maximum transmission error | 0.1 % (E.g., at Pt 100, 300 K min. span) |
Electrical isolation Input/output/power supply | |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Electrical isolation Input/output IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VP |
Electrical isolation Input/power supply IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VP |
Electrical isolation Input/switching output IEC/EN 60079-11 | |
Standards/regulations | IEC/EN 60079-11 |
Rated insulation voltage | 375 VP |
Electrical isolation Output/supply IEC/EN 61010-1 | |
Standards/regulations | IEC/EN 61010-1 |
Rated insulation voltage | 300 Vrms |
Insulation | Safe isolation |
Supply | |
Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
Typical current consumption | < 50 mA (24 V DC) |
Power consumption | < 1.5 W |
Signal | |
Number of inputs | 1 |
Input signal | Temperature |
Resistor | |
Voltage | |
Measurement | |
Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
Linear resistance measuring range | 0 Ω ... 50 kΩ |
Potentiometer resistance range | 0 Ω ... 50 kΩ |
Linear mV signal range | -1000 mV ... 1000 mV |
Switching: Relay | |
Configurable/programmable | Yes |
Contact switching type | 1 changeover contact |
Contact material | AgSnO2, hard gold-plated |
Maximum switching voltage | 30 V AC/DC |
Max. switching current | 0.5 A (30 V AC) |
1 A (30 V DC) | |
Signal: Voltage/current | |
Number of outputs | 1 |
Configurable/programmable | Yes |
Max. voltage output signal | ± 11 V |
Current output signal | 0 mA ... 20 mA (SIL off) |
4 mA ... 20 mA (SIL on) | |
Max. current output signal | 22 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/output load current output | ≤ 600 Ω (20 mA) |
Behavior in the event of a sensor error | freely programmable |
Connection method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket | |
Max. diameter | 2 mm |
Ex installation (EPL) | Gc |
Div. 2 | |
Ex i circuits (EPL) | Ga |
Da | |
Ma | |
Div. 1 | |
Safety data | |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | 44 nF |
Max. output voltage Uo | 6 V DC |
Max. output current Io | 7 mA (RTD in 2-conductor technology) |
13 mA (RTD in 3-conductor technology) | |
16 mA (RTD in 4-conductor technology) | |
13 mA (TC with internal cold junction compensation) | |
10 mA (TC with external cold junction compensation) | |
5 mA (mV) | |
13 mA (Potentiometer) | |
Max. output power Po | 11 mW (RTD in 2-conductor technology) |
20 mW (RTD in 3-conductor technology) | |
24 mW (RTD in 4-conductor technology) | |
20 mW (TC with internal cold junction compensation) | |
15 mW (TC with external cold junction compensation) | |
7.5 mW (mV) | |
20 mW (Potentiometer) | |
IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 150 µF |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 100 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 10 µF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 600 nF, 10 mH / 600 nF, 1 mH / 600 nF |
I/IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1 µF, 10 mH / 1 µF, 1 mH / 1 µF |
Status display | LED supply voltage, PWR (green) |
Red LED, flashing (line, sensor error, ERR) | |
Red LED (module error, ERR) | |
Yellow LED (switching output) |
Dimensional drawing |
|
Width | 17.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 (not assessed by UL) |
Ambient temperature (operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) |
Shock (operation) | 15g (IEC 60068-2-27) |
Vibration (operation) | 5g (IEC 60068-2-6) |
Altitude range (≤ 2000 m) | |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient temperature (operation) | -20 °C ... 65 °C |
Safety-related maximum voltage Um | 253 V AC/DC (Terminals 1.1, 1.2) |
250 V AC (Terminals 3.1, 3.2, 3.3) | |
120 V DC (Terminals 3.1, 3.2, 3.3) | |
30 V (Installation in zone 2) | |
Altitude range (≤ 3000 m) | |
Height range | > 2000 m ... 3000 m |
Ambient temperature (operation) | -20 °C ... 55 °C |
Safety-related maximum voltage Um | 190 V AC (Terminals 1.1, 1.2) |
110 V DC (Terminals 1.1, 1.2) | |
190 V AC (Terminals 3.1, 3.2, 3.3) | |
110 V DC (Terminals 3.1, 3.2, 3.3) | |
30 V (Installation in zone 2) | |
Altitude range (≤ 4000 m) | |
Height range | > 3000 m ... 4000 m |
Ambient temperature (operation) | -20 °C ... 50 °C |
Safety-related maximum voltage Um | 60 V AC/DC (Terminals 1.1, 1.2) |
60 V AC/DC (Terminals 3.1, 3.2, 3.3) | |
30 V (Installation in zone 2) | |
Altitude range (≤ 5000 m) | |
Height range | > 4000 m ... 5000 m |
Ambient temperature (operation) | -20 °C ... 45 °C |
Safety-related maximum voltage Um | 60 V AC/DC (Terminals 1.1, 1.2) |
60 V AC/DC (Terminals 3.1, 3.2, 3.3) | |
30 V (Installation in zone 2) |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II (1) G [Ex ia Ga] IIC |
II (1) D [Ex ia Da] IIIC | |
II 3 G Ex ec ic nC [ia Ga] IIC T4 Gc | |
I (M1) [Ex ia Ma] I | |
Certificate | IBExU 10 ATEX 1044 X |
IECEx | |
Identification | [Ex ia Ga] IIC |
[Ex ia Da] IIIC | |
Ex ec ic nC [ia Ga] IIC T4 Gc | |
[Ex ia Ma] I | |
Certificate | IECEx IBE 10.0004 X |
INMETRO | |
Identification | [Ex ia Ga] IIC |
[Ex ia Da] IIIC | |
Ex ec ic nC [ia Ga] IIC T4 Gc | |
[Ex ia Ma] I | |
Certificate | DNV 18.0143 X |
UL, USA/Canada | |
Identification | UL 508 Listed |
Certificate | , C.D.-No 83104549 |
KC-s | |
Identification | [Ex ia] IIC |
Certificate | 17-KA4BO-0411X |
Shipbuilding approval | |
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
Certificate | SEBS-A.150520/17, V2.0 |
Systematic Capability | |
Identification | 2 |
Performance Level (ISO 13849) | |
Identification | d |
Shipbuilding data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | |
Standards/regulations | EN 61000-6-4 |
Electromagnetic HF field | |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 2 % |
Fast transients (burst) | |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 2 % |
Conducted interference | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 2 % |
Electrical isolation | 4-way isolation |
Mounting type | DIN rail mounting |
Item number | 2865654 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DK1215 |
Product key | DK1215 |
Catalog page | Page 150 (C-5-2019) |
GTIN | 4046356296670 |
Weight per piece (including packing) | 272,6 g |
Weight per piece (excluding packing) | 264,1 g |
Customs tariff number | 85437090 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27210129 |
ETIM
ETIM 9.0 | EC002919 |
UNSPSC
UNSPSC 21.0 | 41112100 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 38abe268-e596-4328-9202-4f127a6029b6 |
Compatible products
-
EA-MSTB 2,5/ 5 - Accessories 1831016
-
MCR-DP - Separating plate 1430594
-
IFS-USB-PROG-ADAPTER - Programming adapter 2811271
-
MACX MCR-EX-I20 - Plug 2905679
-
MACX MCR-EX-CJC - Plug 2925002
-
IFS-BT-PROG-ADAPTER - Adapter 2905872
-
MPS-IH WH - Insulating sleeve 0201663
-
MPS-IH RD - Insulating sleeve 0201676
-
MPS-IH BU - Insulating sleeve 0201689
-
MPS-IH YE - Insulating sleeve 0201692
-
MPS-IH GN - Insulating sleeve 0201702
-
MPS-IH GY - Insulating sleeve 0201728
-
MPS-IH BK - Insulating sleeve 0201731
-
MPS-MT - Test plug 0201744
-
UC-EMLP (11X9) - Plastic label 0819291
-
UC-EMLP (11X9) YE - Plastic label 0822602
-
UC-EMLP (11X9) CUS - Plastic label 0824547
-
UC-EMLP (11X9) YE CUS - Plastic label 0824548
-
UC-EMLP (11X9) SR - Plastic label 0828094
-
UC-EMLP (11X9) SR CUS - Plastic label 0828098
-
US-EMLP (11X9) - Plastic label 0828789
-
US-EMLP (11X9) YE - Plastic label 0828871
-
US-EMLP (11X9) SR - Plastic label 0828872
-
LS-EMLP (11X9) WH - Device marker 0831678
-
LS-EMLP (11X9) SR - Device marker 0831705
-
LS-EMLP (11X9) YE - Device marker 0831732
-
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
-
SZS 0,6X3,5 - Screwdriver 1205053
Your advantages
Input for resistance thermometers, thermocouples, resistance-type sensors, potentiometers, and mV sources, [Ex ia] IIC
Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Cold junction compensation with separate plug
Configuration via software (FDT/DTM) or IFS-OP-UNIT operator interface and display unit
Installation in zone 2, protection type "n" (EN 60079-15) permitted
Up to SIL 2 in accordance with EN 61508
Status indicator for supply voltage, cable, sensor, and module errors
Plug-in screw or spring-cage connection technology (Push-in technology)
Wide-range power supply of 19.2 ... 253 V AC/DC
Measure differential temperatures
Inverse output signal ranges as an option
Relay switching output
Freely programmable input and output
PHOENIX CONTACT B.V.
Hengelder 56, 6902 PA Zevenaar, Postbus 246, 6900 AE Zevenaar