MINI MCR-SL-SHUNT-UI-SP-NC
   - 
  Signal conditioner
    
      2810793
      
      
    
  
      MCR 3-way signal conditioner, with configurable input/output, for electrical isolation and conversion of analog signals in the mV range, both・unipolar・and・bipolar with spring-cage connection, not preconfigured. Replacement part: 2902021 MINI MCR-2-U-UI-PT.
      Free download available.
      Downloads
    
  Product details
| Product type | Signal conditioner | 
| Product family | MINI Analog | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Rated insulation voltage | 30 V AC | 
| 50 V DC | |
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Electrical isolation between input and output | yes | 
| Limit frequency (3 dB) | 100 Hz / 30 Hz switchable | 
| Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) | 
| Step response (10-90%) | 3.5 ms (100 Hz) | 
| Maximum temperature coefficient | < 0.01 %/K | 
| Temperature coefficient, typical | < 0.002 %/K | 
| Maximum transmission error | ≤ 0.2 % | 
| < 0.4 % (Without adjustment) | |
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 30 V AC | 
| 50 V DC | |
| Test voltage | 1.5 kV AC (50 Hz, 60 s) | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) | 
| Max. current consumption | < 25 mA | 
| Power consumption | < 450 mW (Current output) | 
| Signal: Voltage | |
| Number of inputs | 1 | 
| Configurable/programmable | Yes, unconfigured | 
| Voltage input signal | -50 mV ... 50 mV | 
| -60 mV ... 60 mV | |
| -75 mV ... 75 mV | |
| -80 mV ... 80 mV | |
| -100 mV ... 100 mV | |
| -120 mV ... 120 mV | |
| -150 mV ... 150 mV | |
| -200 mV ... 200 mV | |
| -240 mV ... 240 mV | |
| -300 mV ... 300 mV | |
| -500 mV ... 500 mV | |
| -600 mV ... 600 mV | |
| -750 mV ... 750 mV | |
| -800 mV ... 800 mV | |
| -1 V ... 1 V | |
| -1.2 V ... 1.2 V | |
| -1.5 V ... 1.5 V | |
| -2 V ... 2 V | |
| -2.4 V ... 2.4 V | |
| -3 V ... 3 V | |
| 0 mV ... 50 mV (additional areas can be configured, see table) | |
| 0 mV ... 60 mV | |
| 0 mV ... 75 mV | |
| 0 mV ... 80 mV | |
| 0 mV ... 100 mV | |
| 0 mV ... 120 mV | |
| 0 mV ... 150 mV | |
| 0 mV ... 200 mV | |
| 0 mV ... 240 mV | |
| 0 mV ... 300 mV | |
| 0 mV ... 500 mV | |
| 0 mV ... 600 mV | |
| 0 mV ... 750 mV | |
| 0 mV ... 800 mV | |
| 0 V ... 1 V | |
| 0 V ... 1.2 V | |
| 0 V ... 1.5 V | |
| 0 V ... 2 V | |
| 0 V ... 2.4 V | |
| 0 V ... 3 V | |
| Max. voltage input signal | approx. 3 V DC | 
| Input resistance of voltage input | approx. 10 kΩ | 
| Signal: Voltage/current | |
| Number of outputs | 1 | 
| Configurable/programmable | Yes, unconfigured | 
| Voltage output signal | 0 V ... 10 V | 
| 2 V ... 10 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| -10 V ... 10 V (The bi-polar output can be used only for bi-polar input signals.) | |
| -5 V ... 5 V (The bi-polar output can be used only for bi-polar input signals.) | |
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Load/output load voltage output | ≥ 10 kΩ | 
| Load/output load current output | < 500 Ω (at 20 mA) | 
| Ripple | < 20 mVPP (at 500 Ω) | 
| < 20 mVPP (at 10 kΩ) | |
| Connection method | Spring-cage connection | 
| Connection technology | 2-conductor | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Dimensional drawing |  | 
| Width | 6.2 mm | 
| Height | 93.1 mm | 
| Depth | 102.5 mm | 
| Color | green (RAL 6021) | 
| Housing material | PBT | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 65 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| UKCA | |
| Certificate | UKCA-compliant | 
| UL, USA/Canada | |
| Identification | UL 508 Recognized | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA000020N | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | B | 
| EMC | A | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 6 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 6 % | 
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge current load (surge) | |
| Comments | Criterion B | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 6 % | 
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Mounting type | DIN rail mounting | 
| Assembly note | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. | 
| Mounting position | any | 
| Item number | 2810793 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DK1131 | 
| GTIN | 4046356305358 | 
| Weight per piece (including packing) | 109,6 g | 
| Weight per piece (excluding packing) | 109,6 g | 
| Country of origin | DE | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
Your advantages
Power supply possible via the foot element (TBUS)
        Low power consumption
        Ideal for converting signals for shunt measurements
        Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of mV signals to create standard analog signals
        Up to 280 signal combinations can be configured using DIP switches
        3-way isolation
        PHOENIX CONTACT B.V.
        
        Hengelder 56, 6902 PA Zevenaar, Postbus 246, 6900 AE Zevenaar