MINI MCR-SL-I-U-4-SP
   - 
  Signal conditioner
    
      2813567
      
      
    
  
      MCR 3-way signal conditioner, for electrical isolation of analog signals, with spring-cage connection, input signal: 4 mA...20 mA, output signal: 0 V...10 V. Replacement part: 2902003 MINI MCR-2-I4-U-PT.
Product details
| Product type | Signal conditioner | 
| Product family | MINI Analog | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Rated insulation voltage | 30 V AC | 
| 50 V DC | |
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Electrical isolation between input and output | yes | 
| Limit frequency (3 dB) | approx. 100 Hz | 
| Maximum power dissipation for nominal condition | 434 mW | 
| Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) | 
| Step response (10-90%) |  3.5 ms | 
| Maximum temperature coefficient | < 0.01 %/K | 
| Temperature coefficient, typical | < 0.002 %/K | 
| Maximum transmission error | ≤ 0.1 % (of final value) | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) | 
| Max. current consumption | < 9 mA | 
| Power consumption | < 200 mW | 
| Signal | |
| Number of inputs | 1 | 
| Configurable/programmable | no | 
| Current input signal | 4 mA ... 20 mA | 
| Max. current input signal | 50 mA | 
| Input resistance current input | approx. 50 Ω | 
| Signal | |
| Number of outputs | 1 | 
| Configurable/programmable | no | 
| Voltage output signal | 0 V ... 10 V | 
| Max. voltage output signal | 12.5 V | 
| Short-circuit current | approx. 2 mA | 
| Load/output load voltage output | ≥ 10 kΩ | 
| Ripple | < 20 mVPP (at 10 kΩ) | 
| Connection method | Spring-cage connection | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Dimensional drawing |  | 
| Width | 6.2 mm | 
| Height | 93.1 mm | 
| Depth | 102.5 mm | 
| Color | green (RAL 6021) | 
| Housing material | PBT | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 65 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| ATEX | |
| Identification |  II 3 G Ex nA IIC T4 Gc X | 
| UL, USA/Canada | |
| Identification | UL 508 Recognized | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| GL | |
| Identification | GL EMC 2 D | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 5 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 5 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 5 % | 
| Electrical isolation | Basic insulation in accordance with EN 61010 | 
| Mounting type | DIN rail mounting | 
| Assembly note | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. | 
| Mounting position | any | 
| Item number | 2813567 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DK1131 | 
| GTIN | 4046356101929 | 
| Weight per piece (including packing) | 81,4 g | 
| Weight per piece (excluding packing) | 60 g | 
| Country of origin | DE | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
Your advantages
Power supply possible via the foot element (TBUS)
        Entry-level alternative to configurable signal conditioners
        Low power consumption
        3-way isolation
        Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
        Fixed signal combinations
        PHOENIX CONTACT B.V.
        
        Hengelder 56, 6902 PA Zevenaar, Postbus 246, 6900 AE Zevenaar