PSR-SPP- 24DC/SDC4/2X1/B
-
Safety relays
2981499
Safety relay for emergency stop, safety door, and magnetic switches, as well as light grids, up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, 2 N/O contacts, TBUS interface, automatic or manual activation, pluggable Push-in terminal block
Free download available.
Downloads
Product details
Note on application | |
Note on application | Only for industrial use |
Product type | Safety relays |
Product family | PSRclassic |
Application | Emergency stop |
Safety door | |
Light grid | |
Magnetic switch | |
Control | 1 and 2 channel |
Mechanical service life | approx. 107 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Insulation characteristics | |
Overvoltage category | III |
Degree of pollution | 2 |
Maximum power dissipation for nominal condition | 1.68 W |
Nominal operating mode | 100% operating factor |
Rated insulation voltage | 250 V |
Rated surge voltage/insulation | 4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV between input circuit and enabling current paths.) |
General | |
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 70 mA |
Voltage at input/start and feedback circuit | approx. 24 V DC |
Typical response time | 20 ms (manual start) |
150 ms (automatic start) | |
Typical release time | 10 ms |
Recovery time | 1 s |
Max. permissible overall conductor resistance | 50 Ω (Input and start circuits at US) |
Contact switching type | 2 enabling current paths |
1 semiconductor signaling output | |
Contact material | AgSnO2 |
Maximum switching voltage | 250 V AC/DC (Enabling current paths) |
24 V (Signal output) | |
Minimum switching voltage | 15 V AC/DC (Enabling current paths) |
Limiting continuous current | 6 A (Enabling current paths) |
100 mA (Signal output) | |
Maximum inrush current | 6 A |
Inrush current, minimum | 25 mA (Enabling current paths) |
Sq. Total current | 72 A2 (ITH2 = I12 + I22) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
288 W (48 V DC, τ = 0 ms) | |
77 W (110 V DC, τ = 0 ms) | |
88 W (220 V DC, τ = 0 ms) | |
1500 VA (250 V AC, τ = 0 ms) | |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
40 W (48 V DC, τ = 40 ms) | |
35 W (110 V DC, τ = 40 ms) | |
33 W (220 V DC, τ = 40 ms) | |
Switching capacity | min. 0.4 W (Enabling current paths) |
Switching capacity (360/h cycles) | 6 A (24 V DC) |
5 A (230 V (AC15)) | |
Switching capacity (3600/h cycles) | 3 A (24 V (DC13)) |
3 A (230 V (AC15)) | |
Output fuse | 10 A gL/gG NEOZED (Enabling current paths) |
Miniature circuit breaker C6 (24 V / 20 A power supply unit) |
Connection technology | |
pluggable | yes |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross-section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross-section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross-section AWG | 24 ... 16 |
Stripping length | 8 mm |
Width | 22.5 mm |
Height | 112 mm |
Depth | 114.5 mm |
Color (Housing) | yellow (RAL 1018) |
Housing material | PA |
Safety data | |
Stop category | 0 |
Safety data: EN ISO 13849 | |
Category | 4 (Undelayed contacts) |
Performance level (PL) | e |
Safety data: IEC 61508 - High demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand | |
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061 | |
Safety Integrity Level (SIL) | 3 |
Ambient conditions | |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient temperature (operation) | -20 °C ... 55 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Mounting type | DIN rail mounting |
Mounting position | any |
Item number | 2981499 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DNA211 |
Product key | DNA211 |
GTIN | 4046356051699 |
Weight per piece (including packing) | 228 g |
Weight per piece (excluding packing) | 197,9 g |
Customs tariff number | 85371098 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27371819 |
ECLASS-15.0 | 27371819 |
ECLASS-15.0 ASSET | 27250101 |
ETIM
ETIM 9.0 | EC001449 |
UNSPSC
UNSPSC 21.0 | 39122200 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 3ffe7659-7c07-4479-bf6c-1b797cdb1c40 |
EF3.0 Climate Change | |
CO2e kg | 6,132 kg CO2e |
Compatible products
Your advantages
Up to Cat. 4/PL e in accordance with ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Modular system with TBUS extension
For emergency stop and safety door monitoring, plus evaluation of light grids
2 enabling current paths, 1 signaling current path
1- and 2-channel control
PHOENIX CONTACT B.V.
Hengelder 56, 6902 PA Zevenaar, Postbus 246, 6900 AE Zevenaar