MACX MCR-EX-SL-RPSSI-I-UP-SP
   - 
  Repeater power supply
    
      2924029
      
      
    
  
      Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. SIL 2 (1oo1) / SIL 3 (1oo2), wide-range supply.
Product details
| Product type | Repeater power supply | 
| Product family | MACX Analog | 
| Application | Analog IN | 
| No. of channels | 1 | 
| Configuration | DIP switches | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Step response (10-90%) | < 600 µs (for 4 mA ... 20 mA step) | 
| Maximum temperature coefficient | < 0.01 %/K | 
| Maximum transmission error | < 0.1 % (of final value) | 
| Transmission error, typical | < 0.05 % (of final value) | 
| Electrical isolation | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 300 Vrms | 
| Insulation | Safe isolation | 
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 265 Vrms | 
| Electrical isolation Input/power supply IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 265 Vrms | 
| Electrical isolation Output/supply IEC/EN 60079-7 | |
| Standards/regulations | IEC/EN 60079-7 | 
| Rated insulation voltage | 265 Vrms | 
| Supply | |
| Designation | Repeater power supply operation | 
| Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) | 
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) | 
| Max. current consumption | < 80 mA (24 V DC / 20 mA) | 
| Power dissipation | < 1.6 W (24 V DC / 20 mA) | 
| Power consumption | < 2.2 W | 
| Supply | |
| Designation | Signal conditioner operation | 
| Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) | 
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) | 
| Max. current consumption | < 45 mA (24 V DC / 20 mA) | 
| Power dissipation | < 1.1 W (24 V DC / 20 mA) | 
| Signal: Repeater power supply operation | |
| Description of the input | Active current input, intrinsically safe | 
| Number of inputs | 1 | 
| Current input signal | 4 mA ... 20 mA | 
| Transmitter supply voltage | > 16 V (20 mA) | 
| > 15.3 V (22.5 mA) | |
| Signal: Signal conditioner operation | |
| Description of the input | Passive current input, intrinsically safe | 
| Current input signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Voltage drop | < 3.5 V (in input isolating amplifier operation) | 
| Signal: Repeater power supply operation | |
| Output description | Current output (active and passive) | 
| Number of outputs | 1 | 
| Voltage output signal | 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) | 
| Configurable via DIP switches | |
| Current output signal | 4 mA ... 20 mA (active) | 
| 4 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| Load/output load current output | < 600 Ω (20 mA) | 
| < 525 Ω (22.5 mA) | |
| Output ripple | < 20 mVrms | 
| Output behavior in the event of an error | 0 mA (Cable break in the input) | 
| ≥ 22.5 mA (Cable short-circuit in the input) | |
| Signal: Signal conditioner operation | |
| Output description | Current output (active and passive) | 
| Voltage output signal | 0 V ... 5 V (internal resistance, 250 Ω, 0.1%) | 
| 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) | |
| Current output signal | 0 mA ... 20 mA (active) | 
| 4 mA ... 20 mA (active) | |
| 0 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| 4 mA ... 20 mA (14 ... 26 V ext. source voltage) | |
| Load/output load current output | < 600 Ω (20 mA) | 
| < 525 Ω (22.5 mA) | |
| Output ripple | < 20 mVrms | 
| Output behavior in the event of an error | 0 mA (Cable break in the input) | 
| 0 mA (Cable short-circuit in the input) | |
| Connection method | Push-in connection | 
| Stripping length | 10 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) | 
| 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) | |
| Conductor cross-section AWG | 24 ... 14 | 
| 24 ... 22 (TWIN ferrule without plastic sleeve) | |
| 20 ... 16 (TWIN ferrule with plastic sleeve) | 
| Ex installation (EPL) | Gc | 
| Div. 2 | |
| Ex i circuits (EPL) | Ga | 
| Da | |
| Ma | |
| Div. 1 | |
| Safety data: Repeater power supply operation | |
| Max. output voltage Uo | 25.2 V | 
| Max. output current Io | 93 mA | 
| Max. output power Po | 587 mW | 
| Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) | 
| 253 V AC (Output terminals) | |
| 125 V DC (Output terminals) | |
| I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 40 mH / 4.8 µF | 
| IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 2.9 µF | 
| IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 14 mH / 820 nF | 
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 3 mH / 107 nF | 
| IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF | 
| IIB/III (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF | 
| IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF | 
| I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF | 
| Safety data: Signal conditioner operation | |
| Input voltage Ui | ≤ 30 V | 
| Input current Ii | ≤ 150 mA | 
| Max. internal inductance Li | negligible | 
| Max. internal capacitance Ci | negligible | 
| Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) | 
| 253 V AC (Output terminals) | |
| 125 V DC (Output terminals) | |
| Data communication (bypass) | |
| HART function | Yes | 
| Protocols supported | HART-transparent | 
| Status display | Green LED (supply voltage) | 
| Dimensional drawing |  | 
| Width | 17.5 mm | 
| Height | 107.9 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) | 
| Ambient temperature (operation) | -40 °C ... 60 °C (Any mounting position) | 
| -40 °C ... 70 °C (Derating) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) | 
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) | 
| Ambient temperature (operation) | -40 °C ... 60 °C | 
| -40 °C ... 70 °C (Derating) | |
| Rated insulation voltage | 375 VPP (Power supply, input / output) | 
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m ... 3000 m | 
| Ambient temperature (operation) | -40 °C ... 54 °C | 
| -40 °C ... 63 °C (Derating) | |
| Rated insulation voltage | 190 V AC (Power supply, input / output) | 
| 110 V DC (Power supply, input / output) | |
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m ... 4000 m | 
| Ambient temperature (operation) | -40 °C ... 48 °C | 
| -40 °C ... 56 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) | 
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m ... 5000 m | 
| Ambient temperature (operation) | -40 °C ... 42 °C | 
| -40 °C ... 49 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) | 
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  II (1) G [Ex ia Ga] IIC | 
|  II (1) D [Ex ia Da] IIIC | |
|  II 3(1) G Ex ec [ia Ga] IIC T4 Gc | |
|  I (M1) [Ex ia Ma] I | |
| Certificate | BVS 08 ATEX E 094 X | 
| IECEx | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Certificate | IECEx BVS 08.0035X | 
| CCC / China-Ex | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| Certificate | 2022122316115974 | 
| UL, USA/Canada | |
| Identification | Class I Div 2; IS for Class I, II, III Div 1 | 
| Certificate | , C.D.-No 83104549 | 
| Safety Integrity Level (SIL / SILCL, IEC 61508) | |
| Identification | 2 | 
| Certificate | ZP/C031/20 | 
| Systematic Capability (SC / SILCL) | |
| Identification | 3 | 
| INMETRO | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] IIC T4 Gc | |
| Certificate | DNV 18.0138 X | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 1 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 1 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 1 % | 
| Electrical isolation | 3-way isolation | 
| GB Standard | |
| Standards/regulations | GB/T 3836.1 | 
| GB/T 3836.3 | |
| GB/T 3836.4 | |
| GB/T 16935.1 | |
| Mounting type | DIN rail mounting | 
| Item number | 2924029 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK1211 | 
| Product key | DK1211 | 
| GTIN | 4046356338172 | 
| Weight per piece (including packing) | 189,2 g | 
| Weight per piece (excluding packing) | 147,1 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210120 | 
| ECLASS-15.0 | 27210120 | 
ETIM
| ETIM 9.0 | EC002653 | 
UNSPSC
| UNSPSC 21.0 | 39121000 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c), 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | 367c4dc0-fbc8-4db5-b70d-89c229ca3ff9 | 
Compatible products
- 
    
      GW HART USB MODEM - Cable adapter 1003824
- 
    
      MCR-DP - Separating plate 1430594
- 
    
      MPS-IH WH - Insulating sleeve 0201663
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-MT - Test plug 0201744
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      MACX MCR-PTB - Power and error message module 2865625
- 
    
      MACX MCR-PTB-SP - Power and error message module 2924184
- 
    
      QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
- 
    
      SZS 0,6X3,5 - Screwdriver 1205053
- 
    
      MACX EX-SET-TVFKC 3-POLE - Connector set 1584393
Your advantages
250 Ω resistor that can be activated via DIP switches to increase HART impedance for low-resistance systems
        Up to SIL 2 in accordance with EN 61508
        Installation in zone 2, protection type "n" (EN 60079-15) permitted
        Wide-range power supply of 19.2 ... 253 V AC/DC
        3-way electrical isolation
        Plug-in screw or spring-cage connection technology (Push-in technology), with integrated sockets for HART communicators
        0/4 ... 20 mA input, [Ex ia] IIC (powered or not powered)
        Bidirectional transmission of digital HART communication signals
        0/4 ... 20 mA output (active or passive), 0/1 ... 5 V, can be selected via DIP switches