Spark gap-based non-pluggable lightning current arrester / surge protective device free of leakage current for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for use in the unmetered area, for lightning protection levels III and IV, with remote signaling.
IEC test classification | T1 + T2 + T3 |
I + II + III | |
T1 + T2 + T3 | |
EN type | T1 + T2 + T3 |
Product type | Combination type |
Number of positions | 4 |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics | |
Overvoltage category | IV (between the main and auxiliary circuit) |
II (Auxiliary circuit) | |
Pollution degree | 2 |
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling | |
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating voltage | 12 V AC ... 250 V AC |
125 V DC (200 mA DC) | |
Operating current | 10 mA AC ... 0.5 A AC |
0.5 A DC (30 V DC) |
Connection method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm (2,5 mm² ... 16 mm²) |
4.5 Nm (25 mm² ... 35 mm²) | |
Stripping length | 18 mm |
Conductor cross section flexible | 2.5 mm² ... 25 mm² |
Conductor cross section solid | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 13 ... 2 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 2.5 mm² ... 25 mm² |
Remote fault indicator contact | |
Connection method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensional drawing |
|
Width | 72 mm |
Height | 99.7 mm |
Depth | 76.6 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 4 Div. |
Color | light grey RAL 7035 |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PBT |
Material group | I |
Housing material | PBT |
Mechanical data | |
Open side panel | No |
Mode of protection | L-N |
L-PE | |
N-PE | |
Nominal voltage UN | 240/415 V AC (TN-S) |
240/415 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 264 V AC |
Rated load current IL | 80 A (< 55 °C) |
Residual current IPE | ≤ 0.01 mA |
Nominal discharge current In (8/20) µs (L-N) | 12.5 kA |
Nominal discharge current In (8/20) µs (L-PE) | 12.5 kA |
Nominal discharge current In (8/20) µs (N-PE) | 50 kA |
Combination wave UOC | 6 kV |
Impulse discharge current (10/350) µs (L-N), charge | 6.25 As |
Impulse discharge current (10/350) µs (L-N), specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 12.5 kA |
Impulse discharge current (10/350) µs (L-PE), charge | 6.25 As |
Impulse discharge current (10/350) µs (L-PE), specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 12.5 kA |
Impulse discharge current (10/350) µs (N-PE), charge | 25 As |
Impulse discharge current (10/350) µs (N-PE), specific energy | 625 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 50 kA |
Total discharge current Itotal (10/350) µs | 50 kA |
Follow current quenching capacity Ifi (L-N) | 25 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up (L-N) | ≤ 1.5 kV |
Voltage protection level Up (L-PE) | ≤ 2.5 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Residual voltage Ures (L-N) | ≤ 1.5 kV (at In) |
Residual voltage Ures (L-PE) | ≤ 2.5 kV (at In) |
Residual voltage Ures (N-PE) | ≤ 1.5 kV (at In) |
TOV behavior at UT (L-N) | 457 V AC (5 s / withstand mode) |
457 V AC (120 min / withstand mode) | |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 80 A (gG) |
Max. backup fuse with branch wiring | 160 A (gG) |
Ambient conditions | |
Degree of protection | IP20 (Installed) |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (operating voltage remote contact ≤ 250 V) |
≤ 5000 m (operating voltage remote contact ≤ 150 V) | |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 2g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 0,5g (9 … 200 Hz / 2.5 h / X, Y, Z) |
Standards/specifications | IEC 61643-11 |
Standards/specifications | EN 61643-11 |
Mounting type | DIN rail: 35 mm |
Item number | 1380667 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales Key | ***** |
Product Key | CL11D1 |
GTIN | 4063151751586 |
Weight per Piece (including packing) | 222.222 g |
Weight per Piece (excluding packing) | 222.222 g |
ECLASS-9.0 | 27130805 |
ECLASS-10.0.1 | 27130805 |
ECLASS-11.0 | 27130805 |
ETIM 8.0 | EC000941 |
UNSPSC 21.0 | 39121600 |