PROFIBUS or other RS-485 networks can be actively terminated at the end of the bus using the PSI-TERMINATOR-PB. This ensures safe communication even if the bus device is connected/disconnected during operation. In addition, the connectable termination enables the device to be operated as a service interface at any point in the bus system. For the operation of active programming and diagnostic devices, the required power supply is provided at the alternative D-SUB connection.
PSI-TERMINATOR-PB
-
Termination resistor
2313944
Active termination resistor for PROFIBUS and RS-485 bus systems. Compact design, electrical isolation between supply and data interface, bus termination can be activated, integrated programming interface.
Product details
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Utilization restriction | |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Product type | Terminal resistor |
MTTF | 3550 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
1818 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
849 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | |
MTBF | 2383 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
559 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical isolation | RS-485 // VCC |
Maximum power dissipation for nominal condition | 1.08 W |
Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) |
Supply | |
Supply voltage range | 19.2 V DC ... 28.8 V DC (via pluggable COMBICON screw terminal block) |
Nominal supply voltage | 24 V DC (via pluggable COMBICON screw terminal block) |
Typical current consumption | 45 mA (24 V DC) |
Function | |
Status and diagnostic indicators | LEDs: UL (communications power), data activity (not marked) |
Supply | |
Tightening torque | 0.56 Nm ... 0.79 Nm |
Signal | Modbus |
PROFIBUS | |
Data: PROFIBUS acc. to IEC 61158, RS-485 2-conductor | |
Serial transmission speed | ≤ 12 Mbps |
Connection method | D-SUB-9, COMBICON |
Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) |
Termination resistor | 390 Ω |
220 Ω | |
390 Ω (Can be connected) | |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section, rigid max. | 1.5 mm² |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section AWG max. | 16 |
Conductor cross section AWG min. | 24 |
Output nominal voltage | 5 V DC |
Dimensional drawing |
|
Width | 22.5 mm |
Height | 99 mm |
Depth | 56 mm |
Color (Housing) | green (RAL 6021) |
Material (Housing) | PA 6.6-FR |
Free fall in accordance with IEC 60068-2-32 | : 1 m |
Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | Vibration (operation): 5g, 10...150 Hz, 2.5 h, in XYZ direction |
Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | Shock (operation): 25g, 11 ms period, half-sine shock pulse |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
Permissible humidity (operation) | 30 % ... 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
UL, USA/Canada | |
Identification | 508 Listed |
Class I, Div. 2, Groups A, B, C, D | |
UL, USA | |
Identification | Class I, Zone 2, AEx nA IIC T5 |
UL, Canada | |
Identification | Class I, Zone 2, Ex nA IIC T5 Gc X |
Corrosive gas test | |
Identification | ISA-S71.04-1985 G3 Harsh Group A |
ATEX | |
Identification | II 3 G Ex nA IIC T4 Gc X |
Note | Please follow the special installation instructions in the documentation! |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | ± 6 kV (Test Level 3) |
Discharge in air | ± 8 kV (Test Level 3) |
Comments | Criterion B |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 3 GHz (Test Level 3) |
Field intensity | 10 V/m |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | ± 2.2 kV (Test Level 3) |
Signal | ± 2.2 kV (Test Level 3) |
Comments | Criterion B |
Surge current load (surge) | |
Standards/regulations | EN 61000-4-5 |
Surge current load (surge) | |
Input | ± 0.5 kV (DC supply) |
Signal | ± 1 kV (Data line, asymmetrical) |
Comments | Criterion B |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V |
Emitted interference | |
Standards/regulations | EN 61000-6-4 |
Radio interference voltage in acc. with EN 55011 | EN 55011 class A industrial area of application |
Emitted radio interference in acc. with EN 55011 | EN 55011 class A industrial area of application |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting type | DIN rail mounting |
Item number | 2313944 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to order (non-returnable) |
Sales key | CN |
Product key | DNC141 |
Catalog page | Page 335 (C-8-2015) |
GTIN | 4046356579445 |
Weight per piece (including packing) | 136 g |
Weight per piece (excluding packing) | 124.2 g |
Customs tariff number | 85389091 |
Country of origin | DE |
UNSPSC
UNSPSC 21.0 | 32121617 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 6(c), 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
Compatible products
-
-
SUBCON-PLUS-PROFIB/90/PG/IDC - D-SUB bus connector 2313685
-
SUBCON-PLUS-PROFIB/90/SC - D-SUB bus connector 2313698
-
SUBCON-PLUS-PROFIB/90/PG/SC - D-SUB bus connector 2313708
-
SUBCON-PLUS-PROFIB/35/M12 - D-SUB bus connector 2902320
-
SUBCON-PLUS-PROFIB/90/M12 - D-SUB bus connector 2902318
-
SUBCON-PLUS-PROFIB/90X/M12 - D-SUB bus connector 2902729
-
PSM-CABLE-PROFIB/FC - Bus system cable 2744652
-
SZF 0-0,4X2,5 - Screwdriver 1204504
-
PSM-STRIP-FC/PROFIB - Stripping tool 2744623
-
QUICK WIREFOX 6 - Stripping pliers 1204384
-
SUBCON-PLUS-PROFIB/SC2 - D-SUB bus connector 2708232
-
SUBCON-PLUS-PROFIB/PG/SC2 - D-SUB bus connector 2708245
-
SUBCON-PLUS-PROFIB/AX/SC - D-SUB bus connector 2744380
-
PSI-REP-PROFIBUS/12MB - Repeater 2708863
-
PSI-REP-RS485W2 - Repeater 2313096
-
PSM-ME-RS485/RS485-P - Repeater 2744429
-
PSM-ME-RS232/RS485-P - Interface converter 2744416
Your advantages
Extended temperature range of -20°C ... +65°C
DIN rail mounting
Termination can be connected externally
Fixed programming interface in the network
Electrical isolation of power supply and data interface
Interference-free bus communication thanks to active termination
Diagnostic LEDs for voltage and data activity
Compact housing design
PHOENIX CONTACT (Ireland) Ltd
C6 The Exchange, Calmount Park, Ballymount, Dublin 12, D12 XE18, Ireland