Thermocouple measuring transducer - MINI MCR-TC-UI-NC
2902851

Configurable temperature transducer for the connection of thermocouples. Can be configured via DIP switches or, with extended functionality, using the software. Screw connection, standard configuration.

Downloads

Product Details


The configurable temperature transducer with 3-way isolation is suitable for the connection of thermocouples.
The measured values are converted into a linear current or voltage signal.
You can configure the device using one of the free software solutions. Default settings can also be made directly on the device by simply using the DIP switches (see configuration table). The measuring transducer supports fault monitoring.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Temperature transmitter
Configuration DIP switches
Software
Insulation characteristics
Overvoltage category II
Pollution degree 2

Electrical isolation 3-way isolation
Typical cold point errors < 2 K
Cold point error, max. < 3 K
Protective circuit Transient protection
Step response (0–99%) 400 ms (Highspeed Mode: typ. 150 ms)
Maximum temperature coefficient ≤ 0.01 %/K
Transmission error thermocouples 0.1 % * 600 K / set measuring range; 0.1 % > 600 K (E, J, K, N, T, L, U, M Gost, L Gost)
0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3)
0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode
0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode
Electrical isolation Input/output/power supply
Rated insulation voltage 50 V AC/DC
Test voltage 1.5 kV AC (50 Hz, 60 s)
Insulation Basic insulation in accordance with IEC/EN 61010
Supply
Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Item No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption < 27 mA (at 24 V DC)
Max. current consumption 72 mA
Power consumption ≤ 700 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)

Signal
Number of inputs 1
Measurement
Number of inputs 1
Configurable/programmable Yes
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
Temperature measuring range -250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches)
Temperature measuring range min. 50 K

Signal: Voltage/current
Output name Voltage output / current output
Number of outputs 1
Configurable/programmable Yes
Voltage output signal 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal approx. 12.3 V
Non-load voltage < 17.5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal 24.6 mA
Short-circuit current < 31.5 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP
< 20 mVPP (at 500 Ω)

Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

Data: IFS interface
Connection method S-PORT

Status display LED red

Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Designation CE
Certificate CE-compliant
CE
Designation UKCA
Certificate UKCA-compliant
CE
Designation UL, USA / Canada
Identification UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
CE
Designation Shipbuilding approval
Certificate DNV GL TAA00002R0
DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 0.15 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 0.05 %
Surge current load (surge)
Standards/regulations EN 61000-4-5
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 0.02 %

Electrical isolation 3-way isolation

Mounting type DIN rail mounting
Mounting position any

Item number 2902851
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CK
Product Key CK1221
Catalog Page Page 107 (C-7-2015)
GTIN 4046356689229
Weight per Piece (including packing) 118.4 g
Weight per Piece (excluding packing) 118.4 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210129
ECLASS-10.0.1 27210129
ECLASS-11.0 27210129

ETIM

ETIM 8.0 EC002919

UNSPSC

UNSPSC 21.0 41112100

DNV GL

Approval ID: TAA00002R0

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”