C-UB/E
-
Surge protection device
2763701
Attachment plug with surge protection, for coaxial signal interfaces with floating shield. Connection: BNC socket/plug
Product details
General | |
Note | To meet the discharge conditions for DC voltages, please note the following information: "The surge protective device should be used together with a transmitter unit, which shuts down in the event of a short-circuit." |
Product type | Surge protection for transceiver systems |
IEC test classification | C2 |
C3 | |
D1 | |
Type | Intermediate plug |
Surge protection fault message | none |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Connection method | BNC 50 Ω |
Dimensional drawing |
|
Width | 25.4 mm |
Height | 25.4 mm |
Depth | 80 mm |
Color | black (RAL 9005) |
Housing material | Aluminum |
Mechanical data | |
Open side panel | No |
Direction of action | Line-Shield/Earth Ground |
Maximum continuous voltage UC | 180 V DC |
130 V AC | |
Rated current | 3.5 A (25 °C) |
Operating effective current IC at UC | ≤ 1 µA |
Protective conductor current IPE | ≤ 2 µA |
Nominal discharge current In (8/20) µs (line-ground) | 5 kA |
Nominal discharge current In (8/20) µs (line-shield) | 5 kA |
Nominal discharge current In (8/20) µs (shield-ground) | 5 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 2.5 kA |
Pulse discharge current Iimp (10/350) µs (line-shield) | 2.5 kA |
Total discharge current ITotal (8/20) µs | 10 kA |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 470 V |
Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 590 V |
Output voltage limitation at 1 kV/µs (shield-ground) spike | ≤ 470 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 33 V |
Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 33 V |
Output voltage limitation at 1 kV/µs(shield-ground) static | ≤ 33 V |
Residual voltage at In (conductor-ground) | ≤ 160 V (1.5 m cable) |
Residual voltage at In (conductor-shield) | ≤ 55 V |
Residual voltage at In (shield-ground) | ≤ 160 V (1.5 m cable) |
Voltage protection level Up (line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-shield) | ≤ 700 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (shield-ground) | ≤ 500 V (C2 - 10 kV / 5 kA) |
Response time tA | ≤ 100 ns |
Input attenuation aE, asym. | typ. 0.1 dB (≤ 100 MHz/50 Ω) |
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ω system | typ. 1 GHz |
Voltage standing wave ratio VSWR in a 50 Ω system | typ. 1.30 (≤ 150 MHz) |
Permissible HF power Pmax at VSWR = xx (50 ohm system) | 300 W (VSWR = 1.1) |
80 W (VSWR = ∞) | |
Capacity asymmetrical (shield) | typ. 6 pF |
Surge protection fault message | none |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
C3 - 100 A | |
D1 - 2.5 kA | |
Impulse durability (line-shield) | C2 - 10 kV/5 kA |
C3 - 100 A | |
D1 - 2.5 kA |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Standards/specifications | IEC 61643-21 |
Note | 2012 |
Standards/specifications | EN 61643-21 |
Note | 2013 |
Mounting type | Connection-specific intermediate plugging |
Item number | 2763701 |
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Note | Made to order (non-returnable) |
Sales key | CL |
Product key | CL3316 |
Catalog page | Page 201 (C-4-2019) |
GTIN | 4017918065638 |
Weight per piece (including packing) | 102.4 g |
Weight per piece (excluding packing) | 102.4 g |
Customs tariff number | 85363010 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27171504 |
ETIM
ETIM 9.0 | EC000943 |
UNSPSC
UNSPSC 21.0 | 39121600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |