Signal conditioner - MINI MCR-SL-U-UI-NC
2865007

MCR 3-way isolation amplifier, with configurable input/output, for electrical isolation and conversion of analog signals up to 30 V, with screw connection, standard configuration

Free Download available. Downloads

Product Details


The 6.2 mm wide configurable 3-way isolating amplifier MINI MCR-SL-U-UI-... is used for electrical isolation, conversion, amplification and filtering of standard signals.
The signals 0...24 V and 0...30 V can be processed on the input side.
The analog signals 0...20 mA, 4...20 mA, 0...10 V, 2...10 V, 0...5 V or 1..5 V are available electrically isolated on the output side.
The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Signal conditioner
No. of channels 1
Configuration DIP switches
Insulation characteristics
Overvoltage category II
Pollution degree 2

No. of channels 1
Electrical isolation Basic insulation in accordance with EN 61010
Electrical isolation between input and output yes
Limit frequency (3 dB) approx. 100 Hz
Protective circuit Transient protection
Step response (10-90%) approx. 3.5 ms
Maximum temperature coefficient < 0.01 %/K
Temperature coefficient, typical < 0.002 %/K
Maximum transmission error < 0.1 % (of final value)
< 0.4 % (Without adjustment)
Electrical isolation Input/output/power supply
Rated insulation voltage 50 V AC/DC
Test voltage 1.5 kV AC (50 Hz, 60 s)
Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption < 19 mA (at 24 V DC incl. load)
Power consumption < 450 mW

Signal: Voltage
Number of inputs 1
Configurable/programmable Yes, unconfigured
Voltage input signal 0 V ... 24 V
0 V ... 30 V
Max. voltage input signal 50 V DC
Input resistance of voltage input approx. 125 kΩ (0 ... 24 V)
approx. 155 kΩ (0 ... 30 V)

Signal: Voltage/current
Number of outputs 1
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage output signal ≤ 12.5 V
Non-load voltage ≤ 12.5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal 28 mA
Short-circuit current ≤ 22 mA
Load/output load voltage output > 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)

Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

Dimensional drawing
Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm

Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
Housing material PBT

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
UL, USA / Canada
Identification UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding approval
Certificate DNV GL TAA000020N
DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 5 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 5 %
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 5 %

Electrical isolation Basic insulation in accordance with EN 61010

Mounting type DIN rail mounting
Assembly instructions The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715.
Mounting position any

Item number 2865007
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CK
Product Key CK1211
Catalog Page Page 96 (C-7-2015)
GTIN 4046356046565
Weight per Piece (including packing) 77.4 g
Weight per Piece (excluding packing) 65.8 g
Customs tariff number 85437090
Country of origin DE


ECLASS

ECLASS-9.0 27210120
ECLASS-10.0.1 27210120
ECLASS-11.0 27210120

ETIM

ETIM 8.0 EC002653

UNSPSC

UNSPSC 21.0 39121000

cUL Recognized

Approval ID: FILE E 238705

UL Recognized

Approval ID: FILE E 238705

DNV GL

Approval ID: TAA000020N
Approval Specification Data
Nominal Voltage UN Nominal Current IN Cross Section AWG Cross Section mm2

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

cULus Recognized

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Power supply possible via the foot element (TBUS)
Low power consumption
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of 24 V or
30 V DC signals to create standard analog signals
Up to 12 signal combinations can be configured using DIP switches
3-way isolation