Redundancy module - TRIO2-DIODE/12-24DC/2X10/1X20
2907380

Redundancy module, 12 V - 24 V DC, 2 x 10 A, 1 x 20 A


Product Details


A safe redundant system is the result of the parallel connection of two power supply units which are decoupled from one another. To further increase system availability, TRIO DIODE provides the solution: decoupling with diode.



DC operation
Nominal input voltage range 12 V DC ... 24 V DC
Input voltage range 10 V DC ... 30 V DC
Voltage type of supply voltage DC
Reverse polarity protection < Yes60 V
Maximum current Imax 2x 15 A (-25°C ... 40°C)
1x 30 A (-25°C ... 40°C)
Transient surge protection Varistor
Voltage drop, input/output 0.5 V

Efficiency > 97 %
Output voltage UIn -
Nominal output current (IN) 20 A
10 A
Derating 60 °C ... 70 °C (2.5%/K)
Power loss nominal load max. 5 W (IOUT = 10 A)
Connection in series No
Derating 60 °C ... 70 °C (2.5%/K)

Input
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 10 mm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 6 mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 8
Stripping length 15 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Insulation voltage input, output / housing 500 V

Product type Redundancy module
MTBF (IEC 61709, SN 29500) 66425178 h (25 °C)
56586762 h (40 °C)
41744164 h (60 °C)
Insulation characteristics
Protection class III
Degree of pollution 2

Width 35 mm
Height 130 mm
Depth 115 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Housing material Metal
Type of housing Steel sheet, zinc-plated
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety IEC 62368-1 (SELV)
Standard – Safety extra-low voltage IEC 62368-1 (SELV) und EN 60204-1 (PELV)

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 4 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criterion A Normal operating behavior within the specified limits.

Item number 2907380
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key *****
Product Key CMRO43
Catalog Page Page 308 (C-4-2019)
GTIN 4055626198262
Weight per Piece (including packing) 500.01 g
Weight per Piece (excluding packing) 500 g
Customs tariff number 85049091
Country of origin CN


ECLASS

ECLASS-9.0 27371010
ECLASS-10.0.1 27371010
ECLASS-11.0 27371010

ETIM

ETIM 8.0 EC000683

UNSPSC

UNSPSC 21.0 32151500

cUL Recognized

Approval ID: FILE E 211944

UL Recognized

Approval ID: FILE E 211944

EAC

Approval ID: RU S-DE.BL08.W.00764

DNV GL

Approval ID: TAA000011F

UL Listed

Approval ID: FILE E 123528

cUL Listed

Approval ID: FILE E 123528

cULus Recognized

cULus Listed


China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Your advantages

Quick and easy installation with Push-in connection technology
Save energy
Redundant wiring up to the load
Permanent monitoring of redundancy
Consistent redundancy up to the load