The terminal is designed for use within an Inline station. The terminal is used to operate IO-Link-compatible sensors and actuators (devices). It is also used to acquire digital signals. IO-Link is the standard for consistent communication from the controller to the lowest field level. In IO-Link communication, the process data is forwarded during parallel service data transmission. IO-Link is a point-to-point connection between an IO-Link port and the sensor or actuator. IO-Link technology uses the familiar signal technology of the 0 V and 24 V binary interface in order to transmit data using pulse modulation. IO-Link offers full backward compatibility with standard sensors/actuators. Using this terminal, IO-Link-compatible devices from any manufacturer can be operated on INTERBUS, PROFIBUS, and PROFINET.
FLM IOL 4 DI 4 M12
-
Distributed I/O device
2736990
The local bus device has 4 IO-Link ports of 200 mA. Functions: parallel processing of service and process data, 500 kbaud/2 Mbaud selection, short-circuit and overload protection, 800 mA nominal current, M12 fast connection technology.
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 70 mm |
Height | 178 mm |
Depth | 50 mm |
Drill hole spacing | 168 mm |
Color | anthracite |
Fieldline local bus | |
Connection method | M12 connector, B-coded |
Designation connection point | Copper cable |
Number of positions | 5 |
Transmission speed | 500 kbps / 2 Mbps |
Module | |
ID code (dec.) | 223 |
ID code (hex) | DF |
Length code (hex) | 06 |
Length code (dec) | 06 |
Process data channel | 80 bit |
Input address area | 80 bit |
Output address area | 80 bit |
Register length | 96 bit |
Required parameter data | 33 Byte |
Required configuration data | 5 Byte |
Digital: | |
Input name | Digital inputs |
Number of inputs | 4 |
Connection method | M12 connector |
Connection technology | 2-, 3-conductor |
Nominal input voltage UIN | 24 V DC |
Digital | |
Number of inputs | max. 4 |
Nominal input current | 8 mA (at 24 V DC) |
Signal delay | < 3 ms (ton, typical) |
3 ms (toff, typical) | |
Permissible cable length | < 20 m |
IO-Link | |
Description of the input | IEC 61131-2 type 1 |
Connection method | M12 plug connection |
Input filter time | typ. 3 ms |
Protective circuit | Reverse polarity protection |
IO-Link | |
Number of ports | 4 |
Connection method | M12 connector |
Connection technology | 3-conductor |
Digital | |
Number of outputs | max. 4 |
Nominal current per channel | 500 mA (INominal) |
Maximum total current consumption | 2 A (observe derating) |
Limitation of the voltage induced on circuit interruption | approx. -1 V |
Protective circuit | Freewheeling diode; Integrated per channel |
Product type | I/O component |
Product family | Fieldline |
Type | modular |
No. of channels | 4 |
Potentials | |
Voltage supply UL | 24 V DC |
Power supply at UL | max. 4 A |
Current consumption from UL | max. 150 mA (At 500 kBaud) |
typ. 75 mA (At 500 kBaud) | |
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 25 mA (plus power supply for sensors) |
max. 2 A | |
Supply: IO-Link | |
Nominal current for every IO-Link port | max. 200 mA |
Nominal current per device | 800 mA |
Permissible cable length | < 20 m |
Protective circuit | Overload protection; Electronics in the device |
Short-circuit protection; Electronics in the device | |
Supply: Module electronics | |
Connection method | M12 connector |
Designation | UL |
Supply voltage | 24 V DC |
Supply voltage range | 18 V DC ... 30 V DC (including ripple) |
Connection method | M12 connector |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (storage/transport) | 95 % |
Mounting type | Panel mounting |
Item number | 2736990 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to order (non-returnable) |
Sales key | CN |
Product key | DRI453 |
GTIN | 4046356319393 |
Weight per piece (including packing) | 339.3 g |
Weight per piece (excluding packing) | 280 g |
Customs tariff number | 85389091 |
Country of origin | DE |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
-
-
ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
-
SAC-5P-MSB/0,13-PUR/FSB SCO SH - Sensor/actuator cable 1518478
-
SAC-5P-MS/ 0,13-186/FS SCO - Sensor/actuator cable 1518481
-
SAC-5P-MSB/ 0,3-900/FSB SCO - Bus system cable 1517958
-
SAC-5P-MSB/ 0,5-900/FSB SCO - Bus system cable 1517961
-
SAC-5P-MSB/ 1,0-900/FSB SCO - Bus system cable 1517974
-
SAC-5P-MSB/ 2,0-900/FSB SCO - Bus system cable 1517987
-
SAC-5P-MSB/ 5,0-900/FSB SCO - Bus system cable 1517990
-
SAC-5P-MSB/10,0-900/FSB SCO - Bus system cable 1518009
-
SAC-5P-MSB/15,0-900/FSB SCO - Bus system cable 1518012
-
SAC-5P-MS/ 0,3-186/FS SCO - Sensor/actuator cable 1518407
-
SAC-5P-MS/ 0,5-186/FS SCO - Sensor/actuator cable 1518410
-
SAC-5P-MS/ 1,0-186/FS SCO - Sensor/actuator cable 1518423
-
SAC-5P-MS/ 2,0-186/FS SCO - Sensor/actuator cable 1518436
-
SAC-5P-MS/ 5,0-186/FS SCO - Sensor/actuator cable 1518449
-
SAC-5P-MS/10,0-186/FS SCO - Sensor/actuator cable 1518452
-
SAC-5P-MS/15,0-186/FS SCO - Sensor/actuator cable 1518465
Your advantages
4 IO-Link ports and 4 digital inputs
Consistent connection via M12 connectors
Short-circuit and overload protection
Diagnostic and status indicators
SPEEDCON fast locking system
Flexible power supply concept
PHOENIX CONTACT (Ireland) Ltd
C6 The Exchange, Calmount Park, Ballymount, Dublin 12, D12 XE18, Ireland