Repeater - PSI-REP-PROFIBUS/12MB
2708863

Modular repeater for electrical isolation and range increase for PROFIBUS up to 12 Mbps, 4-way isolation, rail-mountable, supply 24 V DC


Product Details


The performance and availability of bus systems can be significantly increased by using repeaters. In addition to electrical isolation, bus segmentation with repeaters makes it possible to multiply the permissible coverage of the network and to extend the number of devices.



Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.

Product type Interface converter
MTTF 1638 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
812 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
340 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
MTBF 1136 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
238 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))

Electrical isolation VCC // TBUS // PROFIBUS (A) // PROFIBUS (B)
Maximum power dissipation for nominal condition 2.16 W
Test voltage data interface/power supply 1.5 kVrms (50 Hz, 1 min.)
Test voltage data interfaces 1.5 kV
Supply
Supply voltage range 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominal supply voltage 24 V DC (in acc. with UL)
Typical current consumption < 90 mA (24 V DC )
Max. current consumption ≤ 2 A (For operation in a joining station, via the DIN rail connector)

Output name Relay output
Output description Alarm output
Number of outputs 1
Maximum switching voltage 60 V DC (Resistive Load, General Load)
30 V AC (Resistive load)
42 V AC (peak, resistive load)
Limiting continuous current 0.46 A

Supply
Torque 0.6 Nm ... 0.8 Nm

Bit distortion, input max. ± 35 %
Bit distortion, output < 6.25 %
Bit delay 1 bit (Direct mode)
Signal PROFIBUS
Transmission channels 2 (1/1), TD, RD, half duplex
Data: PROFIBUS acc. to IEC 61158, RS-485 2-conductor
Transmission speed 9.6/19.2/45.45/93.75/187.5/500/1500/3000/6000/12000 kbps (can be set manually and automatically)
Connection method D-SUB-9 female connector
Transmission length ≤ 1200 m (Depends on transmission speed and cable type)
Termination resistor external
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section AWG max. 14
Conductor cross section AWG min. 24
Transmission medium 2-wire twisted pair, shielded
File format/coding UART (11 Bit, NRZ)
Data direction switching Automatic control, min. station response time 2 bits
Output nominal voltage 5 V DC ±5 %
Output current 50 mA

Dimensional drawing
Width 35 mm
Height 99 mm
Depth 105 mm

Color gray
Material PA 6.6-FR (Housing)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation)
≤ 2000 m (Hazardous locations)
Permissible humidity (operation) 30 % ... 95 % (non-condensing)

CE
Designation CE
Certificate CE-compliant
CE
Designation ATEX
Identification  II 3 G Ex ec IIC T5 Gc
Certificate UL 21 ATEX 2550X
Note Please follow the special installation instructions in the documentation!
CE
Designation IECEx
Identification Ex ec IIC T5 Gc
Certificate IECEx ULD 21.00013X
CE
Designation UL, USA / Canada
Identification Class I, Zone 2, AEx ec IIC T5 Gc
Ex ec IIC T5 Gc X
Class I, Div. 2, Groups A, B, C, D
CE
Designation KC approval for South Korea
Certificate MSIP-REI-PCK-2708863
CE
Designation Corrosive gas test
Identification ISA-S71.04-1985 G3 Harsh Group A

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission EN 55011
Noise immunity EN 61000-4-2
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge ± 6 kV
Discharge in air ± 8 kV
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 3 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input ± 2 kV
Signal ± 2 kV
Comments Criterion B
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Input ± 0.5 kV
Signal ± 1 kV
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Comments Criterion A
Voltage 10 V
Emitted interference
Standards/regulations EN 55011
Comments Class A, industrial applications
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Free from substances that could impair the application of coating according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard
Standards/regulations EN 62368

Mounting type DIN rail mounting

Item number 2708863
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CN
Product Key DNC121
Catalog Page Page 422 (C-6-2019)
GTIN 4046356078993
Weight per Piece (including packing) 232.3 g
Weight per Piece (excluding packing) 212.4 g
Customs tariff number 85176200
Country of origin DE


ECLASS

ECLASS-9.0 19179290
ECLASS-10.0.1 19179290
ECLASS-11.0 19179090

ETIM

ETIM 8.0 EC002608

UNSPSC

UNSPSC 21.0 43222600

EAC

Approval ID: TR TS_D_01871-19

KC

Approval ID: MSIP-REI-PCK-2708863

UL Listed

Approval ID: FILE E 238705

cUL Listed

Approval ID: FILE E 238705

ATEX

Approval ID: PxCIF06ATEX2708863X

cUL Listed

Approval ID: FILE E 199827

UL Listed

Approval ID: FILE E 199827

IECEx

Approval ID: IECEx ULD 21.0013X

ATEX

Approval ID: UL 21 ATEX 2550X

cULus Listed

cULus Listed


REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Your advantages

Automatic data rate detection or fixed data rate setting via DIP switches
Suitable for all data rates up to 12 Mbps
High-quality 4-way isolation between all interfaces
Bit oversampling for reliable detection of sporadic disturbances
Bit retiming for unrestricted cascading of devices
Filtering of faulty telegrams based on start delimiter detection
Can be combined with PSI-MOS FO converters in a modular way thanks to DIN rail connectors