The AXC 3050 modular controller for the Axioline I/O system is fast, robust, and easy, i.e., it is consistently designed for maximum performance, easy handling, and use in harsh industrial environments.
AXC 3050
-
Controller
2700989
Axiocontrol for the direct control of Axioline F I/Os. With 3 Ethernet interfaces for the additional connection of distributed I/Os via PROFINET, Modbus/TCP or TCP/IP. Programming according to IEC 61131-3. Includes connector plug and marking field.
Free download available.
Downloads
Product details
Note on application | |
Note on application | Only for industrial use |
Product type | Controller |
Product family | Axiocontrol |
Type | modular |
Display | |
Diagnostics display | no |
Processor | Intel®Atom® E660, 1x 1.3 GHz |
Retentive data storage | 128 kByte |
IEC 61131 runtime system | |
Program memory | 4 Mbyte |
Data storage system | 8 Mbyte |
Number of control tasks | 16 |
Axioline | |
Amount of process data | max. 8192 bit (per station) |
max. 4096 bit (Axioline F local bus (input)) | |
max. 4096 bit (Axioline F local bus (output)) | |
Number of supported devices | max. 63 (per station) |
Number of local bus devices that can be connected | max. 63 (observe current consumption) |
PROFINET | |
Device function | PROFINET controller, PROFINET device |
Specification | Version 2.3 |
Update rate | min. 1 ms (16 devices) |
min. 2 ms (32 participants) | |
min. 4 ms (64 devices) | |
min. 8 ms (32 participants) | |
min. 16 ms (256 participants) | |
Conformance Class | B |
Number of supported devices | max. 256 (at PROFINET controller) |
Device ID | 0095hex |
Vendor ID | 00B0hex |
Function | |
Diagnostics display | no |
Redundancy function | yes |
Note on redundancy function | applicative system redundancy possible |
Safety function | no |
Functionality | |
Programming languages supported | Instruction list (IL) |
Symbolic flowchart (SFC) | |
Ladder diagram (LD) | |
Function block diagram (FBD) | |
Structured text (ST) | |
System requirements | |
Engineering tool | PC Worx |
Configuration tool | Config+ Version 1.01 or later |
Diagnostics tool | DIAG+ |
Runtime system | eCLR |
Application interface | OPC |
Maximum power dissipation for nominal condition | max. 9.8 W |
Supply | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC |
Residual ripple | ± 5 % |
Max. current consumption | max. 976 mA (with 2 A at UBus for the I/Os and UL = 24 V) |
Typical current consumption | typ. 408 mA (without I/Os and UL = 24 V) |
Real-time clock | |
Realtime clock | yes |
Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL) | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 976 mA (with 2 A at UBus for the I/Os and UL = 24 V) |
Power consumption | max. 23.5 W (2.0 A on UBus, UL = 24 V) |
Potentials: Axioline F local bus supply (UBus) | |
Supply voltage | 5 V DC (via bus base module) |
Power supply unit | 2 A |
Potentials | |
Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131-2) |
Counter: | |
Input name | Counter input for 24 V signals |
Number of inputs | max. 2 (via any digital inputs of the Axioline F modules) |
Input frequency | max. 100 kHz (with AXL F DI16/1 HS 1H module) |
Connection method | Push-in connection |
Axioline F connector | |
Connection method | Push-in connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Web server | yes |
Ethernet | |
Bus system | RJ45 |
Number of interfaces | 3 |
Connection method | RJ45 jack |
Note on the connection method | Auto negotiation and autocrossing |
Transmission speed | 10/100 Mbps |
Transmission physics | Ethernet in RJ45 twisted pair |
No. of channels | 3 |
Axioline F local bus | |
Number of interfaces | 1 |
Connection method | Bus base module |
Transmission speed | 100 Mbps |
Parameterization/operation/diagnostics | |
Bus system | USB |
Number of interfaces | 1 |
Connection method | Micro USB type B |
Transmission speed | max. 115.2 kbps |
No. of channels | 1 |
Service | |
Bus system | USB |
Number of interfaces | 1 |
Connection method | USB type A, socket |
Width | 100 mm |
Height | 125.9 mm |
Depth | 74 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Color | gray (RAL 7042) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 60 °C (up to 2000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (assembly) | -5 °C ... 60 °C |
Permissible humidity (operation) | 5 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 5 % ... 95 % (according to DIN EN 61131-2) |
Shock (operation) | 10g (Bump endurance test according to DIN EN 60068-2-27) |
Vibration (operation) | 5g |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conformance with EMC directives | Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge |
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m | |
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion B, ±2 kV | |
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV | |
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V | |
Noise emission test in accordance with EN 61000-6-3/IEC 61000-6-3 Radio interference properties EN 55022 Class A |
Mounting type | DIN rail mounting |
Item number | 2700989 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DR |
Product key | DRAAEC |
GTIN | 4046356731201 |
Weight per piece (including packing) | 461.7 g |
Weight per piece (excluding packing) | 444 g |
Customs tariff number | 85371091 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242207 |
ETIM
ETIM 9.0 | EC000236 |
UNSPSC
UNSPSC 21.0 | 32151700 |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
EF3.0 Climate Change | |
CO2e kg | 10.12 kg CO2e |
Compatible products
-
AX OPC SERVER - Driver and interface software 2985945
-
SD FLASH 512MB - Program/configuration memory 2988146
-
SD FLASH 512MB APPLIC A - Program/configuration memory 2701799
-
SD FLASH 512MB PDPI PRO - Memory 2701801
-
SD FLASH 512MB PDPI BASIC - Memory 2701800
-
SD FLASH 2GB - Program/configuration memory 2988162
-
SD FLASH 2GB APPLIC A - Program/configuration memory 2701190
-
PC WORX BASIC LIC - Programming software 2985275
-
PC WORX PRO LIC - Programming software 2985385
-
PC WORX UA SERVER-PLC 40 - Driver and interface software 2402685
-
PC WORX UA SERVER-PLC 80 - Driver and interface software 2402686
-
AXC BS - Bus connector 2701582
-
AXL CN S/UL - Plug 2701421
Your advantages
PROFINET controller and PROFINET device
Memory extendable by up to 2 GB via plug-in SD card
3 independent Ethernet interfaces
Modbus/TCP-Client
Integrated FTP and HTML5 web server
Numerous protocols supported such as: http, https, FTP, SNTP, SNMP, SMTP, SQL, MySQL, DCP, etc.
Integrated UPS for targeted shutdown of the application
Maritime approvals (GL, DNV, LR, BV, RINA, ABS)