MCR-FL-T-LP-I-EX
-
Temperature measuring transducer
2864574
MCR head-mounted temperature transducers: Programmable loop-powered temperature transducers. Resistance thermometers, thermocouples, resistance-type sensors and voltage sensors.
Free download available.
Downloads
Product details
Product type | Temperature transmitter |
Application | Temperature |
Configuration | Using MCR-PI-CONF-WIN configuration software package |
Functionality | |
Configuration | Using MCR-PI-CONF-WIN configuration software package |
Switch-on delay | 4 s |
Line monitoring | NE 43 |
Test voltage input/output | 2 kV AC (50 Hz, 60 s) |
Step response (10-90%) | < 2 s |
Transmission error voltage sensor | ±20 µV (-10 mV ... 100 mV) |
Transmission error thermocouples | typ. 0.5 K (K, J, T, E, L, U), 1.0 K (N, C, D), 2.0 K (S, B, R) |
Transmission error resistance-type sensor | ±0.1 Ω (10 ... 400 Ω), ±1.5 Ω (10 ... 2000 Ω) |
Transmission error resistance thermometer | 0.2 K (Pt 100, Ni 100), 0.5 K (Pt 500, Ni 500), 0.3 K (Pt 1000, Ni 1000) |
Supply | |
Designation | Loop-powered |
Supply voltage range | 12 V DC ... 30 V DC |
Max. current consumption | < 3.5 mA |
Signal | |
Number of inputs | 1 |
Input signal | Temperature |
Measurement | |
Configurable/programmable | Yes, programmable |
Sensor types (RTD) that can be used | Pt, Ni (100, 500, 1000); min. measurement range 10 K |
Sensor types that can be used (TC) | B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K |
Sensor type: | -200 °C ... 850 °C (freely adjustable) |
-200 °C ... 250 °C (freely adjustable) | |
-200 °C ... 250 °C (freely adjustable) | |
-60 °C ... 180 °C (freely adjustable) | |
-60 °C ... 150 °C (freely adjustable) | |
-60 °C ... 150 °C (freely adjustable) | |
0 °C ... 1820 °C (freely adjustable) | |
0 °C ... 2320 °C (freely adjustable) | |
0 °C ... 2495 °C (freely adjustable) | |
-270 °C ... 1000 °C (freely adjustable) | |
-210 °C ... 1200 °C (freely adjustable) | |
-270 °C ... 1372 °C (freely adjustable) | |
-200 °C ... 900 °C (freely adjustable) | |
-270 °C ... 1300 °C (freely adjustable) | |
-50 °C ... 1760 °C (freely adjustable) | |
-50 °C ... 1760 °C (freely adjustable) | |
-270 °C ... 400 °C (freely adjustable) | |
-200 °C ... 600 °C (freely adjustable) | |
Connection technology | 2-, 3-, 4-conductor |
Linear resistance measuring range | 10 Ω ... 400 Ω (min. measurement range 10 Ω) |
10 Ω ... 2000 Ω (min. measurement range 100 Ω) | |
Linear mV signal range | -10 mV ... 100 mV (min. measurement range 5 mV) |
Switching: | |
Configurable/programmable | no |
Signal | |
Output description | Current output |
Number of outputs | 1 |
Configurable/programmable | Yes |
Current output signal | 4 mA ... 20 mA |
20 mA ... 4 mA | |
Max. current output signal | ≤ 23 mA |
Output current with short-circuit | ≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples) |
Output current with wire break | ≤ 3.6 mA or ≥ 21 mA (adjustable) |
Output current range with overrange/underrange | 3.8 mA ... 20.5 mA |
Load/output load current output | ≤ 520 Ω (At UV = 24 V; Usupply - 12 V / 0.023 A) |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Safety data | |
Max. voltage Ui | 30 V |
Max. current Ii | 100 mA |
Max. power Pi | 750 mW |
Max. output voltage Uo | 4.4 V DC |
Max. output current Io | 9.6 mA |
Max. output power Po | 10.6 mW |
Max. ambient temperature | T4 = 85 °C, T5 = 65 °C, T6 = 50 °C |
Safety-related maximum voltage Um | 250 V |
IIA: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 12 µF |
IIB: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 12 µF |
IIC: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 2.4 µF |
Dimensional drawing |
|
Width | 12.5 mm |
Height | 99 mm |
Depth | 114.5 mm |
Color | green (RAL 6021) |
Flammability rating according to UL 94 | V0 |
Housing material | Polyamide PA non-reinforced |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C ... 55 °C |
CE | |
Certificate | CE-compliant |
ATEX | |
Identification | II 2(1) G Ex ia IIC T4...T6 |
UL, USA/Canada | |
Identification | cULus |
Standards | |
Standards/regulations | NAMUR recommendation NE 21 |
Mounting type | DIN rail mounting |
Mounting position | any |
Item number | 2864574 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DK1XXX |
Product key | DK1XXX |
Catalog page | Page 195 (C-5-2017) |
GTIN | 4017918907273 |
Weight per piece (including packing) | 104 g |
Weight per piece (excluding packing) | 104 g |
Customs tariff number | 85437090 |
Country of origin | DE |
UNSPSC
UNSPSC 21.0 | 41112105 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Your advantages
Input for resistance thermometers, thermocouples, and linear mV signals, Ex ia IIC
Configuration via software
Can be installed in zone 1
2-way electrical isolation
1-channel
Loop-powered
HART-compatible (MCR-FL-TS-LP-I-EX)
Output: 4 mA ... 20 mA/20 mA ... 4 mA
PHOENIX CONTACT nv/sa
Minervastraat 10-12, 1930 Zaventem