MACX MCR-TS-I-OLP-SP
   - 
  Temperature measuring transducer
    
      2908664
      
      
    
  
      Output loop-powered temperature transducer for transmitting up to 2 sensor signals from RTD and TC sensors, as well as from resistance and voltage sensors via 4 mA ... 20 mA. HART, Signal conditioners with SIL functional safety, Standard configuration, Safety Integrity Level (SIL, IEC 61508): 2, Systematic Capability: 3, Push-in connection
      Free download available.
      Downloads
    
  Product details
| Product type | Temperature transmitter | 
| Product family | MACX Analog | 
| No. of channels | 2 | 
| Configuration | Software | 
| HART | |
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Functionality | |
| Configuration | Software | 
| HART | |
| Electrical isolation between input and output | yes | 
| Step response (0–99%) | 0.8 s (TC) | 
| Electrical isolation Input/output | |
| Test voltage | 2 kV AC (50 Hz, 60 s) | 
| Supply | |
| Supply voltage range | loop-powered, no external supply necessary | 
| 12 V DC ... 42 V DC (Standard) | |
| 12 V DC ... 32 V DC (SIL active) | |
| Signal | |
| Input signal | Temperature | 
| Measurement | |
| Number of inputs | 2 | 
| Input voltage range | -20 mV ... 100 mV (Minimum measuring span: 5 mV) | 
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire | 
| Sensor types that can be used (TC) | A, B, C, D, E, J, K, L, N, R, S, T, U | 
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) | 
| -200 °C ... 850 °C (Pt 100) | |
| Temperature measuring range | > 10 K (RTD) | 
| > 50 K (TC) | |
| Linear resistance measuring range | 10 Ω ... 2000 Ω (Minimum measuring span: 10 Ω) | 
| Signal: Current | |
| Configurable/programmable | no | 
| Current output signal | 4 mA ... 20 mA | 
| 20 mA ... 4 mA | |
| Max. current output signal | 23 mA | 
| Load | (UL - 11 V) / 0,023 A | 
| HART coding | FSK ± 0.5 mA | 
| HART version | 7 | 
| Transmission speed | 1200 Baud | 
| Mains frequency filter | 50/60 Hz | 
| Communication resistance | ≥ 250 Ω | 
| Switch-on delay |  10 s (HART) | 
|  28 s (Measured value) | |
| Connection method | Push-in connection | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.2 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Ex installation (EPL) | Gc | 
| Div. 2 | 
| Data communication (bypass) | |
| Protocols supported | HART | 
| Status display | LED (red) | 
| Dimensional drawing |  | 
| Width | 12.5 mm | 
| Height | 116 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C ... 85 °C | 
| -40 °C ... 70 °C (SIL active) | |
| Ambient temperature (storage/transport) | -40 °C ... 100 °C | 
| Altitude | ≤ 4000 m (Above sea level) | 
| Climatic class | B2 | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| ATEX | |
| Identification |  II 3G Ex nA IIC T6...T4 Gc | 
| UL, USA/Canada | |
| Identification | UL 61010 Recognized | 
| FM | |
| Identification | NI, Class I, Div. 2, Groups A, B, C, D | 
| CSA | |
| Identification | NI / Class I / Div. 2 / ABCD T6/T5/T4 | 
| Shipbuilding approval | |
| Certificate | DNV GL TAA00002GX | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Systematic Capability | |
| Identification | 3 | 
| Shipbuilding data | |
| Temperature | D | 
| Humidity | B | 
| Vibration | A | 
| EMC | B | 
| Enclosure | A | 
| Mounting type | DIN rail mounting | 
| Item number | 2908664 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK1143 | 
| Product key | DK1143 | 
| GTIN | 4055626355443 | 
| Weight per piece (including packing) | 205 g | 
| Weight per piece (excluding packing) | 169 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210129 | 
| ECLASS-15.0 | 27210129 | 
ETIM
| ETIM 9.0 | EC002919 | 
UNSPSC
| UNSPSC 21.0 | 41112100 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-E No hazardous substances above the limits | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
- 
    
      MCR-DP - Separating plate 1430594
- 
    
      MCR-PAC-T-USB - Programming adapter 2309000
- 
    
      GW HART USB MODEM - Cable adapter 1003824
- 
    
      MPS-IH WH - Insulating sleeve 0201663
- 
    
      MPS-IH RD - Insulating sleeve 0201676
- 
    
      MPS-IH BU - Insulating sleeve 0201689
- 
    
      MPS-IH YE - Insulating sleeve 0201692
- 
    
      MPS-IH GN - Insulating sleeve 0201702
- 
    
      MPS-IH GY - Insulating sleeve 0201728
- 
    
      MPS-IH BK - Insulating sleeve 0201731
- 
    
      MPS-MT - Test plug 0201744
- 
    
      UC-EMLP (11X9) - Plastic label 0819291
- 
    
      UC-EMLP (11X9) YE - Plastic label 0822602
- 
    
      UC-EMLP (11X9) CUS - Plastic label 0824547
- 
    
      UC-EMLP (11X9) YE CUS - Plastic label 0824548
- 
    
      UC-EMLP (11X9) SR - Plastic label 0828094
- 
    
      UC-EMLP (11X9) SR CUS - Plastic label 0828098
- 
    
      US-EMLP (11X9) - Plastic label 0828789
- 
    
      US-EMLP (11X9) YE - Plastic label 0828871
- 
    
      US-EMLP (11X9) SR - Plastic label 0828872
- 
    
      LS-EMLP (11X9) WH - Device marker 0831678
- 
    
      LS-EMLP (11X9) SR - Device marker 0831705
- 
    
      LS-EMLP (11X9) YE - Device marker 0831732
- 
    
      MACX MCR-PTB - Power and error message module 2865625
- 
    
      MACX MCR-PTB-SP - Power and error message module 2924184
- 
    
      QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
- 
    
      SZS 0,6X3,5 - Screwdriver 1205053
PHOENIX CONTACT nv/sa
        
        Minervastraat 10-12, 1930 Zaventem