The terminal is designed for use within an Inline station. The power measurement terminal is used to analyze AC power grids. You can use it in distribution systems for measuring current, voltage, and power as well as detecting distortion and harmonics. You can run the power measurement terminal in five operating modes. In “Basic measured values” operating mode, the power measurement terminal is used to acquire mains variables in three-phase mains. Mains variables are phase currents, neutral conductor current, phase and phase-to-phase voltages, active power, reactive power, and apparent power as well as the power factors of phases, energy flow directions, and frequency. The measured variables and operands are calculated in accordance with DIN 40110 Parts 1 and 2 (non-sinusoidal variables). In “Scanning measured values” operating mode, the power measurement terminal acquires the instantaneous values (scanning values) of a measuring signal. This measuring mode is used to analyze the waveform of the measuring signal. In “Heating current measured values” operating mode, the power measurement terminal monitors non-equivalence. Phase currents and phase voltages are measured to detect faults at an early stage. In the “1-phase or 3-phase synchronization” operating modes, the power measurement terminal acquires measured values that can be used for controlling the voltage, speed, and phase angle of a generator so that connection to the mains is possible.
IB IL PM 3P/N/EF-PAC
-
Function module
2700965
Inline power measurement terminal for direct measurement of AC currents up to 5 A, including neutral conductor current and phase conductor voltages up to 400 V AC (phase/neutral conductor) or 690 V AC (phase/phase) complete with accessories (connectors and labeling fields)
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Note on application | |
Note on application | Only for industrial use |
Inline local bus | |
Number of interfaces | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Module | |
ID code (dec.) | 220 |
ID code (hex) | DC |
Length code (hex) | 0C |
Length code (dec) | 12 |
Process data channel | 192 bit |
Input address area | 24 Byte |
Output address area | 24 Byte |
Register length | 28 Byte |
Required parameter data | 29 Byte |
Required configuration data | 5 Byte |
Product type | I/O component |
Product family | Inline |
Type | modular |
Operating mode | Process data mode with 12 words, PCP with 2 words |
Diagnostics messages | Two line conductors confused I/O error message |
One line conductor not connected or wire break at line conductor I/O error message | |
Measuring circuit fault I/O error message | |
Value range for transformer factors exceeded I/O error message | |
Value range for other settings exceeded I/O error message | |
Insulation characteristics | |
Overvoltage category | III (up to 300 V), II (up to 400 V) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 2.7 W |
Potentials: Communications power (UL) | |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | typ. 130 mA |
Connection technology | |
Connection name | Inline connector |
Conductor connection | |
Connection method | Spring-cage connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Inline connector | |
Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Protection class | II (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Item number | 2700965 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI165 |
Product key | DRI165 |
Catalog page | Page 155 (C-6-2019) |
GTIN | 4046356665919 |
Weight per piece (including packing) | 231,2 g |
Weight per piece (excluding packing) | 200 g |
Customs tariff number | 85389099 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242605 |
ETIM
ETIM 9.0 | EC001601 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 24c5394e-f8a5-43dc-94a1-04c11d49f9fa |
EF3.0 Climate Change | |
CO2e kg | 21,73 kg CO2e |
Compatible products
-
-
IB IL FIELD 8 - Marking field 2727515
-
EMT (62X46)R - Insert label 0800059
-
IB IL FIELD 2 - Marking field 2727501
-
EMT (62X10)R - Insert label 0800057
-
ZBF 6:UNBEDRUCKT - Zack Marker strip, flat 0808710
-
UCT-TMF 6 - Marker for terminal blocks 0828746
-
UC-TMF 6 - Marker for terminal blocks 0818140
-
ZBF 12:UNBEDRUCKT - Zack Marker strip, flat 0809735
-
UCT-TMF 12 - Marker for terminal blocks 0829214
-
UC-TMF 12 - Marker for terminal blocks 0819233
Your advantages
4 inputs, 0 A AC ... 5 A AC for phase currents and neutral conductor current
3 inputs for outer conductor voltages up to 690 V AC, supports direct connection
Triggers for meas. intervals can be freely defined
Harmonics analysis
Determination of maximum values
Operating hours counter
Energy meter
Bimetal filtering
Short-time control
PHOENIX CONTACT nv/sa
Minervastraat 10-12, 1930 Zaventem