The module is designed for use within an Axioline F station. The power measurement module is used for direct measurement of AC currents up to 5 A, including neutral conductor current and phase voltages up to 400 V AC (phase/neutral conductor) or phase-to-phase voltages up to 690 V AC (phase/phase). The module is used to perform analysis of AC power grids. You can use it in distribution systems for measuring current, voltage, and power, as well as detecting distortion and harmonics. You can use the power measurement module to acquire RMS values and instantaneous values. RMS values are used to acquire mains variables of three-phase mains networks. Mains variables are phase currents, neutral conductor current, phase and phase-to-phase voltages, active power, reactive power, and apparent power, power factors of the phases, energy flow directions, frequency. Instantaneous values are used to analyze the waveform of the measuring signal.
AXL F PM EF 1F
-
Function module
2702671
Axioline F, power measurement module, input voltage: up to 400 V AC (phase/neutral) or 690 V AC (phase/phase), input current: up to 5 A AC, transmission speed in local bus: 100 Mbps, degree of protection: IP20 , including bus base module and Axioline F connectors
Free download available.
Downloads
Product details
| Dimensional drawing |
|
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 65.5 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Note on application | |
| Note on application | Only for industrial use |
| Note on application | As things stand now, we are preparing the product so that, as of December 11, 2027, it will comply with the requirements of the EU Cyber Resilience Act (CRA) based on the information currently available regarding the CRA. |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Mounting type | DIN rail mounting |
| Mounting position | any (no temperature derating) |
| Color (Housing) | gray (RAL 7042) |
| Axioline F local bus | |
| Number of interfaces | 2 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Programming data | |
| Input address area | 64 Byte |
| Output address area | 0 Byte |
| Fieldbus data telegram (PROFIBUS) | |
| Required parameter data | 26 Byte |
| Required configuration data | 6 Byte |
| Measuring category | CAT III 300 V / CAT II 400 V in accordance with DIN EN 61010-1 and DIN EN 61010-2-030 |
| Measurement: Current | |
| Input name | Current measuring input |
| Description of the input | Detection of I1 ... I3 and IN currents, up to 5 A AC, supports direct connection |
| Number of inputs | 4 |
| Measuring procedure | Sigma-Delta |
| Measuring range | 0 A AC ... 6 A AC (overrange starting at 5 A) |
| Nominal current IN | 5 A AC |
| Nominal current range | 0 A AC ... 5 A AC |
| Load | typ. 10 mΩ |
| Overload | 1.4 times continuous; 150 A for 10 ms |
| Tolerance, relative | 0.25 % (of the nominal value) |
| Scanning rate | 8k samples/s |
| Process data update | < 1 ms |
| Measurement: voltage | |
| Input name | Voltage measuring input |
| Description of the input | Detection of phase voltages U1 ... U3, for phase-to-phase voltages up to 690 V AC (phase/phase), direct connection supported |
| Number of inputs | 3 |
| Measuring procedure | Sigma-Delta |
| Measuring range | 0 V AC ... 440 V AC (Phase/neutral conductor) |
| 0 V AC ... 760 V AC (Phase/Phase) | |
| Nominal voltage range | 0 V AC ... 400 V AC (Phase/neutral conductor) |
| 0 V AC ... 690 V AC (Phase/Phase) | |
| Voltage (N-G) | max. 45 V |
| Mains frequency | 40 Hz ... 70 Hz |
| Input filter | 3.2 kHz |
| Overload | 1.2 times the nominal value |
| Tolerance, relative | 0.25 % (of the nominal value) |
| Tolerance, relative | 8k samples/s |
| Process data update | < 1 ms |
| Product type | I/O component |
| Product family | Axioline F |
| Type | block modular |
| Mounting position | any (no temperature derating) |
| Operating mode | Process data mode with 32 words |
| Special properties | The product is being prepared for compliance with the Cyber Resilience Act (CRA) |
| Insulation characteristics | |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Maximum power dissipation for nominal condition | 2.15 W |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Current draw | max. 80 mA |
| typ. 73 mA | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: 5 V supply for local bus (UBus) / peripheral range AC | 4 kV, 50 Hz, 1 min |
| Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min |
| Test voltage: Peripheral range for AC/functional ground | 4 kV, 50 Hz, 1 min |
| Connection technology | |
| Connection name | Axioline F connector |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual. Only use reinforced or double-insulated conductors with a conductor cross-section of 1.5 mm². |
| Axioline F connector | |
| Connection method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual. Only use reinforced or double-insulated conductors with a conductor cross-section of 1.5 mm². |
| Conductor cross-section, rigid | 1.5 mm² |
| Conductor cross-section, flexible | 1.5 mm² |
| Conductor cross-section AWG | 16 |
| Stripping length | 8 mm |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level, from HW 01) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Mechanical test | |
| Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6 | 5g |
| Shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 30g |
| Continuous shock in accordance with EN 60068-2-27/IEC 60068-2-27 | 10g |
| Protection class | II |
| Item number | 2702671 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Sales key | DRI265 |
| Product key | DRI265 |
| GTIN | 4055626364940 |
| Weight per piece (including packing) | 287 g |
| Weight per piece (excluding packing) | 222 g |
| Customs tariff number | 85389091 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27242605 |
| ECLASS-15.0 | 27242605 |
ETIM
| ETIM 10.0 | EC001601 |
UNSPSC
| UNSPSC 21.0 | 32151600 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol (CAS: 119-47-1) |
| SCIP | b1221b74-62e2-4a26-8087-24463c78e22a |
| EF3.1 Climate Change | |
| CO2e kg | 12,618 kg CO2e |
Compatible products
-
AXL F BS F - Bus connector 2688129
-
AXL F BS CAP - Protective cap 2702275
-
ZB 20,3:UNPRINTED - Zack marker strip 0820248
-
ZBF 10/5,8 AXL UNPRINTED - Zack Marker strip, flat 0829580
-
ZB 10:UNBEDRUCKT - Zack marker strip 1053001
-
ZBF 5:UNBEDRUCKT - Zack Marker strip, flat 0808642
-
EMT (35X46)R - Insert label 0801604
-
PACT MCR-V1-21-44 - Current transformer 2277268
-
PACT MCR-V2- 3015- 60 - Current transformer 2277271
-
PACT MCR-V2- 4012- 70 - Current transformer 2277284
-
PACT MCR-V2- 5012- 85 - Current transformer 2277297
-
PACT MCR-V2- 6015- 85 - Current transformer 2277336
-
PACT MCR-V2-10020-129 - Current transformer 2277378
-
PACT MCR-V3-60 - Current transformer 2277417
Your advantages
4 inputs, 0 A AC ... 5 A AC for phase currents and neutral conductor current
3 inputs for outer conductor voltages up to 690 V AC, supports direct connection
Harmonics analysis
Determination of maximum values
Energy meter
Process data update < 1 ms
Also suitable for use in IT networks