VAL-MS-T1/T2 600DC-PV/2+V-FM
   - 
  Lightning/surge arrester type 1/2
    
      2801164
      
      
    
  
      Lightning current arrester / surge protective device for 2-pos. isolated and grounded 600 V DC PV voltage systems, for DIN rail mounting, 3-pos. base element with remote indication contact, three pluggable temperature-monitored protective elements, status message at each plug.
Product details
| General | |
| Note | The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area. | 
| Product type | PV arrester | 
| Product family | VALVETRAB MS | 
| IEC test classification | PV I / II | 
| PV T1 / T2 | |
| EN type | T1 / T2 | 
| IEC power supply system | DC | 
| Type | DIN rail module, two-section, divisible | 
| Distance between live and grounded parts | 8 mm | 
| Environment | Indoor | 
| Installation location of the disconnect device | Internal | 
| Accessibility | Accessible | 
| Connection configuration | Y configuration | 
| End-of-life mode | OCFM (Open-Circuit Failure Mode) | 
| Surge protection fault message | Optical, remote indicator contact | 
| Insulation characteristics | |
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Indicator/remote signaling | |
| Connection name | Remote fault indicator contact | 
| Switching function | Changeover contact | 
| Operating voltage | 5 V AC ... 250 V AC | 
| 30 V DC | |
| Operating current | 5 mA AC ... 1.5 A AC | 
| 1 A DC | |
| Connection method | Screw connection | 
| Screw thread | M5 | 
| Tightening torque | 3 Nm (1.5 mm² ... 16 mm²) | 
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm | 
| Conductor cross-section flexible | 1.5 mm² ... 25 mm² | 
| Conductor cross-section rigid | 1.5 mm² ... 35 mm² | 
| Conductor cross-section AWG | 15 ... 2 | 
| Connection method | Fork-type cable lug | 
| Conductor cross-section flexible | 1.5 mm² ... 16 mm² | 
| Remote fault indicator contact | |
| Connection method | Plug-in/screw connection via COMBICON | 
| Screw thread | M2 | 
| Tightening torque | 0.25 Nm | 
| Stripping length | 7 mm | 
| Conductor cross-section flexible | 0.14 mm² ... 1.5 mm² | 
| Conductor cross-section rigid | 0.14 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 28 ... 16 | 
| Dimensional drawing |  | 
| Width | 53.4 mm | 
| Height | 98.7 mm | 
| Depth | 65.7 mm (incl. DIN rail 7.5 mm) | 
| Horizontal pitch | 3 Div. | 
| Color | black (RAL 9005) | 
| Flammability rating according to UL 94 | V-0 | 
| CTI value of material | 600 | 
| Insulating material | PA 6.6-FR | 
| PBT-FR | |
| Material group | I | 
| Housing material | PA 6.6-FR | 
| PBT-FR | 
| Mechanical data | |
| Open side panel | No | 
| Mode of protection | (L+) - (L-) | 
| (L+) - PE | |
| (L-) - PE | |
| Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) | 
| Rated load current IL | 80 A | 
| Protective conductor current IPE | ≤ 20 µA DC | 
| ≤ 350 µA AC | |
| Standby power consumption PC | ≤ 25 mVA | 
| Nominal discharge current In (8/20) µs | 15 kA | 
| Maximum discharge current Imax (8/20) µs | 40 kA | 
| Impulse discharge current (10/350) µs, charge | 2.5 As | 
| Impulse discharge current (10/350) µs, specific energy | 6.25 kJ/Ω | 
| Impulse discharge current (10/350) µs, peak value limp | 5 kA | 
| Total discharge current ITotal (8/20) µs | 40 kA | 
| Total discharge current ITotal (10/350) µs | 7 kA | 
| Voltage protection level Up | ≤ 2.6 kV | 
| Residual voltage Ures | ≤ 2.6 kV (at In) | 
| ≤ 2 kV (at 5 kA) | |
| ≤ 2.3 kV (at 10 kA) | |
| ≤ 2.8 kV (at 20 kA) | |
| ≤ 3.1 kV (at 30 kA) | |
| ≤ 3.6 kV (at 40 kA) | |
| Response time tA | ≤ 25 ns | 
| PV protective circuit | |
| Connection configuration | Y configuration | 
| End-of-life mode | OCFM (Open-Circuit Failure Mode) | 
| Protective circuit DC voltage side (DC) | |
| Open-circuit voltage UOCSTC | ≤ 600 V DC | 
| Maximum discharge current Imax (8/20) µs | 40 kA | 
| Response time tA | ≤ 25 ns | 
| Impulse discharge current (10/350) µs, charge | 2.5 As | 
| Impulse discharge current (10/350) µs, specific energy | 6.25 kJ/Ω | 
| Impulse discharge current (10/350) µs, peak value limp | 5 kA | 
| Total discharge current ITotal (8/20) µs | 40 kA | 
| Total discharge current ITotal (10/350) µs | 7 kA | 
| Insulation resistance Riso | > 5 GΩ (at 500 V DC) | 
| Nominal discharge current In (8/20) µs | 15 kA | 
| Rated load current IL | 80 A | 
| Continuous operating current ICPV | < 20 µA | 
| Maximum continuous operating voltage UCPV | 720 V DC | 
| Short-circuit current rating ISCPV | 2000 A | 
| Residual voltage Ures | ≤ 2.6 kV (at In) | 
| ≤ 2 kV (at 5 kA) | |
| ≤ 2.3 kV (at 10 kA) | |
| ≤ 2.8 kV (at 20 kA) | |
| ≤ 3.1 kV (at 30 kA) | |
| ≤ 3.6 kV (at 40 kA) | |
| Protective conductor current IPE | ≤ 20 µA DC | 
| ≤ 350 µA AC | |
| Voltage protection level Up | ≤ 2.6 kV | 
| Standby power consumption PC | ≤ 25 mVA | 
| Ambient conditions | |
| Degree of protection | IP20 (only when all terminal points are used) | 
| Ambient temperature (operation) | -40 °C ... 80 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 80 °C | 
| Altitude | ≤ 2000 m (amsl) | 
| Permissible humidity (operation) | 5 % ... 95 % | 
| Shock (operation) | 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) | 
| Vibration (operation) | 7.5g (5-500 Hz/2.5 h/XYZ) | 
| UL specifications | |
| Maximum continuous operating voltage MCOV | 800 V DC | 
| Short-circuit current rating (SCCR) | 50 kA | 
| Voltage protection rating VPR | 2 kV | 
| Nominal discharge current In | 20 kA | 
| Mode of protection | (L+) - (L-) | 
| (L+) - G | |
| (L-) - G | |
| Nominal voltage | 800 V DC | 
| Power distribution system | DC PV | 
| SPD Type | 1 | 
| UL indicator/remote signaling | |
| Operating voltage | 125 V AC | 
| AC operating current | 1 A AC | 
| UL connection data | |
| Tightening torque | 30 lbf-in. | 
| Conductor cross-section AWG | 14 ... 2 | 
| Standards/specifications | EN 61643-31 | 
| Note | 2019 | 
| Standards/specifications | IEC 61643-31 | 
| Note | 2018 | 
| Mounting type | DIN rail: 35 mm | 
| Item number | 2801164 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | CL1152 | 
| Product key | CL1152 | 
| GTIN | 4046356714297 | 
| Weight per piece (including packing) | 368,4 g | 
| Weight per piece (excluding packing) | 340,62 g | 
| Customs tariff number | 85363030 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27171401 | 
ETIM
| ETIM 9.0 | EC000381 | 
UNSPSC
| UNSPSC 21.0 | 39121620 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes (No exemptions) | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-E No hazardous substances above the limits | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
- 
    
      ZBN 18 CUS - Zack marker strip 0825059
- 
    
      ZBN 18,LGS:ERDE - Marker for terminal blocks 2749589
- 
    
      ZBN 18,LGS:L1-N,ERDE - Marker for terminal blocks 2749576
- 
    
      ZBN 18:UNBEDRUCKT - Zack marker strip 2809128
- 
    
      ATP-QTTCB - Partition plate 3206238
- 
    
      B-STIFT - Marker pen 1051993
- 
    
      SZK PZ2 VDE - Screwdriver 1206463
- 
    
      VAL-MS-T1/T2 600DC-PV-ST - Type 1/2 surge protection plug 2801165
Your advantages
Quality proven millions of times over in the widest range of applications
        Rapid installation with bridges, thanks to industry-standard overall width of 1 HP
        Easy testing and insulation measurement, thanks to pluggable protection modules
        PHOENIX CONTACT nv/sa
        