The configurable and individually scalable PSRmodular safety system is a flexible safety solution for monitoring your machine or system. The safe extension module provides the system with additional safe analog inputs.
PSR-M-EF7-SAI4-PI
-
Extension module
1104986
Safe extension module with 4 safe analog inputs, 0 V ... 10 V; 0 mA or 4 mA ... 20 mA; TBUS interface, up to Cat. 4/PL e, SIL 3, plug-in Push-in terminal block, TBUS connector included
Free download available.
Downloads
Product details
Note on application | |
Note on application | Only for industrial use |
Product type | Safety device |
Application | Analog IN |
Control | 1 and 2 channel |
Insulation characteristics | |
Protection class | III |
Insulation characteristics | |
Overvoltage category | II |
Degree of pollution | 2 |
Times | |
Response time | see user manual |
Restart time | min. 5 s (Boot time) |
max. 10 s (Boot time) |
Maximum power dissipation for nominal condition | 2.76 W (with max. permissible load) |
Nominal operating mode | 100% operating factor |
Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
Electrical isolation, 0.5 kV functional insulation between logic and analog inputs and between the analog inputs | |
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 19.2 V DC ... 28.8 V DC |
Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (external fuse, typically 6 A) |
Rated control supply current IS | typ. 82 mA (without sensor supply) |
typ. 212 mA (with sensor supply) | |
Power consumption at US | typ. 1.96 W (without sensor supply) |
typ. 5.08 W (with sensor supply) | |
Inrush current | max. 14 A (Δt = 1 ms at Us) |
Filter time | typ. 5 ms (in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal |
General | |
Protective circuit | Overload protection of the current inputs; Suppressor diode |
Analog | |
Input name | IN S1, IN S2, IN S3, IN S4 |
Description of the input | Safety-oriented analog inputs, configurable as current or voltage inputs, galvanically isolated |
Number of inputs | 4 |
Connection technology | 2-conductor, 3-conductor or 4-conductor (2-conductor sensor signal + 2-conductor sensor supply) |
Note regarding the connection technology | shielded |
Scanning rate | 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000 Hz |
Current input signal | 0 mA ... 25 mA (Measuring range) |
0 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1 mA ... 23 mA) | |
4 mA ... 20 mA (Configurable measuring range with diagnostics range 20.1 mA ... 23 mA (upper limit), 2.5 mA ... 3.8 mA (lower limit)) | |
Voltage input signal | 0 V ... 12 V (Measuring range) |
0 V ... 10 V (Configurable measuring range with diagnostics range 10.05 V ... 11.5 V (upper limit), 0.1 V (lower limit)) | |
Max. permissible current | max. 35 mA (as current input) |
Permissible voltage | max. 24 V (as current input) |
max. 14 V (as voltage input) | |
Input resistance current input | 290 Ω ±25 % (incl. internal protective circuit) |
Input resistance of voltage input | 185 kΩ ±25 % |
A/D converter resolution | 16 bit |
Resolution (current) | 381 nA |
Resolution (voltage) | 152 µV |
Precision | typ. ± 2 % (as current input, relative to the measuring range final value) |
max. ± 2.5 % (as current input) | |
typ. ± 1 % (as voltage input, relative to the measuring range final value) | |
max. ± 1.5 % (as voltage input) | |
Temperature coefficients | typ. ± 0.07 %/K |
max. ± 0.07 %/K | |
Limit frequency (3 dB) | 160 Hz (RC low pass, 1st order, as current input) |
4 Hz (RC low pass, as voltage input) | |
Frequency | 12 Hz (max. recommended sensor signal frequency, as current input) |
2 Hz (max. recommended sensor signal frequency, as voltage input) | |
Permissible cable length | max. 100 m (per input) |
Protective circuit | Overload protection of the current inputs |
Overload protection of the voltage inputs |
Sensor supply: OUT S1/0V ...OUT S4/0V | |
Description | Sensor supply voltage per analog input |
Supply voltage | 24 V DC ±3 % |
Current | max. 30 mA (Sensor current recording per channel) |
Short-circuit-proof | yes |
Protective circuit | Overload protection Overload detection at 38 mA |
Connection technology | |
pluggable | yes |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 14 |
Stripping length | 10 mm |
Status display | 4 x LED (yellow, red) |
Operating voltage display | 1 x LED (green) |
Width | 22.61 mm |
Height | 107.74 mm |
Depth | 113.6 mm |
Color (Housing) | yellow (RAL 1018) |
Housing material | Polyamide PA non-reinforced |
Safety data | |
Stop category | 0 |
Safety data: EN ISO 13849 | |
Performance level (PL) | e (2-channel wiring) |
d (1-channel wiring) | |
Safety data: IEC 61508 - High-demand for 2-channel wiring | |
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - High-demand for 1-channel wiring | |
Safety Integrity Level (SIL) | 2 |
Safety data: EN IEC 62061 | |
Safety Integrity Level (SIL) | 3 (2-channel wiring) |
2 (1-channel wiring) |
Ambient conditions | |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient temperature (operation) | -10 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -20 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 95 % (non-condensing) |
Max. permissible relative humidity (operation) | 95 % (non-condensing) |
Shock | 10g for Δt = 16 ms (continuous shock, 1000 shocks in each space direction) |
Vibration (operation) | 10 Hz ... 150 Hz, 2g |
CE | |
Identification | CE-compliant |
Mounting type | DIN rail mounting |
Assembly note | Observe derating |
Mounting position | vertical or horizontal |
Item number | 1104986 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DNA362 |
Product key | DNA362 |
GTIN | 4055626974804 |
Weight per piece (including packing) | 196 g |
Weight per piece (excluding packing) | 145 g |
Customs tariff number | 85371098 |
Country of origin | IT |
ECLASS
ECLASS-13.0 | 27371819 |
ETIM
ETIM 9.0 | EC001449 |
UNSPSC
UNSPSC 21.0 | 39122200 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
Your advantages
Cost-effective safety solution with a high level of adaptability to individual requirements
Fast startup, thanks to easy hardware and software configuration
Machine downtimes minimized with comprehensive, easy-to-understand diagnostics
Tool-free and time-saving installation thanks to Push-in technology
Low housing width of just 22.6 mm
Up to Cat. 4/PL e in accordance with ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Suitable for elevator applications in accordance with EN 81-20
PHOENIX CONTACT nv/sa
Minervastraat 10-12, 1930 Zaventem