PSR-SPP-120UC/URM/5X1/2X2
   - 
  Coupling relay
    
      2981415
      
      
    
  
      Safe coupling relay with force-guided contacts, 5 N/O contacts, 2 N/C contacts, 1-channel, width: 22.5 mm, pluggable Push-in terminal block
      Free download available.
      Downloads
    
  Product details
| Note on application | |
| Note on application | Only for industrial use | 
| Product type | Coupling relay | 
| Product family | PSRclassic | 
| Application | Safe switch off | 
| High demand | |
| Low demand | |
| Control | 1 and 2 channel | 
| Mechanical service life | 10x 106 cycles | 
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 | 
| Insulation characteristics: Air clearances and creepage distances between the power circuits | |
| Overvoltage category | III | 
| Degree of pollution | 2 | 
| Times | |
| Typ. starting time with Us | typ. 20 ms (with Us when controlled via A1) | 
| Typical release time | 20 ms (with Us when controlled via A1) | 
| Restart time | < 1 s (Boot time) | 
| Recovery time | < 500 ms | 
| Maximum power dissipation for nominal condition | 8.8 W (at UB = 132 V DC, US = 120 V, IS = 11 mA, n = 1, IL² = 72 A², Rcontact = 0.1 ) | 
| Nominal operating mode | 100% operating factor | 
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V | 
| 250 V | |
| Rated surge voltage/insulation | 4 kV basic insulation (4 kV safe isolation, reinforced insulation between A1/A2, 13/14, 23/24, 33/34 to 43/44, 53/54, 61/62, 71/72) | 
| Supply | |
| Rated control circuit supply voltage US | 120 V AC/DC -20 % ... +10 % | 
| Rated control supply current IS | typ. 11 mA | 
| Power consumption at US | typ. 1.32 W | 
| Inrush current | typ. 600 mA (Δt = 200 µs at Us) | 
| Protective circuit | Surge protection; Varistor | 
| General | |
| Rated control circuit supply voltage US | 120 V AC/DC -20 % ... +10 % | 
| Power consumption at US | typ. 1.32 W | 
| Rated control supply current IS | typ. 11 mA | 
| Input voltage range | 19.2 V AC/DC ... 26.4 V AC/DC | 
| Inrush current | typ. 600 mA (Δt = 200 µs at Us) | 
| Typ. starting time with Us | typ. 20 ms (when controlled via A1) | 
| Typical release time | typ. 20 ms (when controlled via A1) | 
| Recovery time | < 500 ms | 
| Maximum switching frequency | 0.5 Hz | 
| Protective circuit | Surge protection; Varistor | 
| Operating voltage display | 1 x LED (green) | 
| Contact switching type | 5 enabling current paths | 
| 2 confirmation current paths | |
| Contact material | AgSnO2 | 
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) | 
| Minimum switching voltage | 5 V AC/DC | 
| Limiting continuous current | 6 A (N/O contact) | 
| 3 A (N/C contact) | |
| Maximum inrush current | 6 A | 
| Inrush current, minimum | 10 mA | 
| Sq. Total current | 72 A2 | 
| Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) | 
| 288 W (N/O contact, 48 V DC, τ = 0 ms) | |
| 240 W (N/O contact, 60 V DC, τ = 0 ms) | |
| 110 W (N/O contact, 110 V DC, τ = 0 ms) | |
| 88 W (N/O contact, 220 V DC, τ = 0 ms) | |
| 1380 VA (N/O contact, 230 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) | 
| 42 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching power | min. 50 mW | 
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (24 V (DC13)) | 
| 3 A (230 V (AC 15)) | |
| Switching capacity (360/h cycles) | 4 A (24 V (DC13)) | 
| 4 A (230 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) | 
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) | |
| Relay: Enabling current paths (13/14, 23/24, 33/34, 43/44, 53/54) | |
| Number of outputs | 5 | 
| Contact switching type | 5 enabling current paths | 
| Contact material | AgSnO2 | 
| Switching power | min. 50 mW | 
| Inrush current | max. 6 A | 
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (AC15, 250 V) | 
| 3 A (DC13, 24 V) | |
| Switching capacity (360/h cycles) | 4 A (AC15, 250 V) | 
| 4 A (DC13, 24 V) | |
| Limiting continuous current | 6 A (N/O contact) | 
| 3 A (N/C contact) | |
| Sq. Total current | 72 A2 (observe derating) | 
| Switching frequency | max. 0.5 Hz | 
| Mechanical service life | 107 cycles | 
| Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) | 
| 288 W (N/O contact, 48 V DC, τ = 0 ms) | |
| 240 W (N/O contact, 60 V DC, τ = 0 ms) | |
| 110 W (N/O contact, 110 V DC, τ = 0 ms) | |
| 88 W (N/O contact, 220 V DC, τ = 0 ms) | |
| 1380 W (N/O contact, 250 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) | 
| 42 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Output fuse | 6 A gL/gG NEOZED (N/C contact) | 
| 4 A gL/gG NEOZED (N/O contact, low demand) | |
| 10 A gL/gG NEOZED (N/O contact) | |
| Relay: Confirmation current paths (61/62, 71/72) | |
| Number of outputs | 2 | 
| Contact switching type | 2 confirmation current paths | 
| Contact material | AgSnO2 | 
| Switching power | min. 50 mW | 
| Inrush current | min. 10 mA | 
| max. 6 A | |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (DC13, 24 V) | 
| 3 A (AC15, 250 V) | |
| Switching capacity (360/h cycles) | 4 A (DC13, 24 V) | 
| 4 A (AC15, 250 V) | |
| Limiting continuous current | 6 A (N/O contact) | 
| 3 A (N/C contact) | |
| Sq. Total current | 72 A2 (see to derating) | 
| Mechanical service life | 107 cycles | 
| Connection technology | |
| pluggable | yes | 
| Conductor connection | |
| Connection method | Push-in connection | 
| Conductor cross-section, rigid | 0.2 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.2 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) | 
| Conductor cross-section AWG | 24 ... 16 | 
| Stripping length | 8 mm | 
| Tightening torque | 0.6 Nm | 
| Operating voltage display | 1 x LED (green) | 
| Width | 22.5 mm | 
| Height | 114.5 mm | 
| Depth | 112 mm | 
| Color | yellow | 
| Housing material | PA | 
| Safety data | |
| Stop category | 0 | 
| Safety data: EN ISO 13849 | |
| Category | 1 | 
| Performance level (PL) | c | 
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 1 | 
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 1 | 
| Safety data | |
| Safety Integrity Level (SIL) | 1 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Min. degree of protection of inst. location | IP54 | 
| Ambient temperature (operation) | -20 °C ... 55 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Maximum altitude | ≤ 2000 m (Above sea level) | 
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) | 
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) | 
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) | 
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) | 
| CE | |
| Certificate | CE-compliant | 
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | DIN EN 50178 | 
| Mounting type | DIN rail mounting | 
| Mounting position | vertical or horizontal | 
| Item number | 2981415 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DNA162 | 
| GTIN | 4046356051675 | 
| Weight per piece (including packing) | 196,2 g | 
| Weight per piece (excluding packing) | 135,88 g | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27371601 | 
| ECLASS-15.0 | 27371601 | 
UNSPSC
| UNSPSC 21.0 | 39122334 | 
Your advantages
Suitable up to category 1, PL c (EN ISO 13849-1), SIL 1 (EN IEC 62061), SIL 1 (IEC 61508)
        Safe readback due to force-guided signal contact in accordance with EN 50205
        Easy proof test according to IEC 61508 thanks to integrated signal contact
        1 or 2-channel control
        5 enabling current paths, 2 confirmation current paths
        120 V version
        PHOENIX CONTACT nv/sa
        
        Minervastraat 10-12, 1930 Zaventem