The module is designed for use within an Axioline F station. It is used to acquire analog voltage and current signals. The high long-term stability of the peripheral electronics ensures service-free continuous operation.
AXL F AI8 W 1F
-
Analog module
2702525
Axioline F, Analog input module, Analog inputs: 8, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 100 Mbps, for SAFE AI applications with service-free continuous operation, degree of protection: IP20, including bus base module and Axioline F connectors
Free download available.
Downloads
Product details
Dimensional drawing |
|
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Note on application | |
Note on application | Only for industrial use |
Axioline F local bus | |
Number of interfaces | 2 |
Connection method | Bus base module |
Transmission speed | 100 Mbps |
Module | |
Input address area | 16 Byte |
Output address area | 0 Byte |
Required parameter data | 27 Byte |
Required configuration data | 6 Byte |
Analog: General | |
Input name | Analog inputs |
Description of the input | Differential inputs, voltage or current can be chosen separately |
Number of inputs | 8 |
A/D conversion time | 2 µs |
A/D converter resolution | 16 bit |
Connection method | Push-in connection |
Connection technology | 2-conductor |
Note regarding the connection technology | shielded, twisted pair |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
-20 mA ... 20 mA | |
Input resistance current input | 104 Ω (typical) |
Voltage input signal | 0 V ... 5 V |
-5 V ... 5 V | |
0 V ... 10 V | |
-10 V ... 10 V | |
Input resistance of voltage input | 268 kΩ (typical) |
Data formats | IB IL, S7-compatible |
Input filter | 30 Hz, 12 kHz and mean value generation (can be parameterized) |
Filtering | RFI filtering / passive TP 1st order |
Limit frequency (3 dB) | 30 Hz |
12 kHz (in fast mode) | |
Common mode voltage range signal - ground | -50 V DC ... 50 V DC |
Measured value representation | 16 bits (15 bits + sign bit) |
Protective circuit | Transient protection of inputs; Suppressor diode |
Overload protection of the current inputs; No; ±5.2 V DC, maximum, Imax = 50 mA | |
Overload protection of the voltage inputs; ±30 V DC, maximum |
Product type | I/O component |
Product family | Axioline F |
Type | block modular |
Mounting position | any (no temperature derating) |
Scope of supply | including bus base module and Axioline F connectors |
Special properties | for SAFE AI applications with service-free continuous operation |
Insulation characteristics | |
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 4.2 W |
Potentials: Axioline F local bus supply (UBus) | |
Supply voltage | 5 V DC (via bus base module) |
Current draw | max. 130 mA (up to HW 04) |
max. 60 mA (from HW 05) | |
typ. 105 mA (up to HW 04) | |
typ. 45 mA (from HW 05) | |
Potentials: Supply for analog modules (UA) | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 55 mA (from HW 05) |
max. 45 mA (up to HW 04) | |
typ. 43 mA (from HW 05) | |
typ. 35 mA (up to HW 04) | |
Protective circuit | Surge protection; electronic (35 V, 0.5 s) |
Reverse polarity protection; Polarity protection diode | |
Transient protection; Suppressor diode | |
Electrical isolation/isolation of the voltage ranges | |
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply of the local bus (UBus) / analog inputs | 500 V AC, 50 Hz, 1 min |
Test voltage: 5 V supply of the local bus (UBus) / functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / analog inputs | 500 V AC, 50 Hz, 1 min |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min |
Test voltage: Analog inputs / functional ground | 500 V AC, 50 Hz, 1 min |
Connection technology | |
Connection name | Axioline F connector |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor connection | |
Connection method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector | |
Connection method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual. |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 60 °C |
-10 °C ... 35 °C (annual average) | |
Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (Non-condensing, annual average < 75%) |
Permissible humidity (storage/transport) | 5 % ... 95 % (Non-condensing, annual average < 75%) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |
Mounting position | any (no temperature derating) |
Item number | 2702525 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI241 |
Product key | DRI241 |
GTIN | 4055626210803 |
Weight per piece (including packing) | 268,4 g |
Weight per piece (excluding packing) | 204 g |
Customs tariff number | 85389091 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27242601 |
ETIM
ETIM 9.0 | EC001596 |
UNSPSC
UNSPSC 21.0 | 32151600 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes |
Exemption | 7(a), 7(c)-I |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
SCIP | 1b73886c-f0b9-428b-bdbc-02ada21852ac |
Compatible products
Your advantages
8 analog, bipolar input channels for the connection of either voltage or current signals
Connection of sensors in 2-conductor technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
High long-term stability of measuring inputs
Device rating plate stored
Safe analog value processing with SAFE AI and other components
PHOENIX CONTACT nv/sa
Minervastraat 10-12, 1930 Zaventem