VAL-SPP-T2-600DC-PV-2+V-UT-R
-
Type 2 surge arrester
1466771
Surge arrester, in accordance with type 2/Class II, for 2-pos. insulated and grounded 600 V DC PV systems, for DIN rail mounting, 3-pos. base element with remote indication contact, three pluggable temperature-monitored protective elements, status message on each plug.
Product details
Product type | PV arrester |
Product family | VAL-SPP |
IEC test classification | PV II |
PV T2 | |
EN type | T2 |
IEC power supply system | DC |
Type | DIN rail module, two-section, divisible |
Number of positions | 3 |
Installation location | Indoor |
Installation location of the disconnect device | Internal |
Accessibility | Accessible |
Connection configuration | Y configuration |
End-of-life mode | OCFM (Open-Circuit Failure Mode) |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Indicator/remote signaling | |
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Max. required back-up fuse | 1 A (gG) |
AC operating voltage | 5 V AC ... 250 V AC (≤2000 m (amsl)) |
5 V AC ... 150 V AC ( 5000 m (amsl)) | |
AC operating current | 5 mA AC ... 1 A AC |
DC operating voltage | 30 V DC ( 5000 m (amsl)) |
DC operating current | 1 A DC |
DC operating voltage | 125 V DC ( 5000 m (amsl)) |
DC operating current | 200 mA DC |
Insulation type | The product has double/reinforced insulation between the main and auxiliary circuit. |
Connection method | Screw connection |
Screw thread | M5 |
Tightening torque | 2.5 Nm ... 3 Nm |
Stripping length | 12 mm |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
2x 1.5 mm² ... 6 mm² (2 conductors with the same cross-section) | |
Conductor cross section rigid | 1.5 mm² ... 25 mm² |
2x 1.5 mm² ... 6 mm² (2 conductors with the same cross-section) | |
Conductor cross section AWG | 15 ... 4 |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 1.5 mm² ... 6 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 1.5 mm² ... 16 mm² |
2x 1.5 mm² ... 6 mm² (2 conductors with the same cross-section) | |
Conductor cross section flexible, with ferrule without plastic sleeve | 1.5 mm² ... 16 mm² |
2x 1.5 mm² ... 6 mm² (2 conductors with the same cross-section) | |
Remote fault indicator contact | |
Connection method | Screw connection |
Screw thread | M3 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 0.75 mm² |
Dimensional drawing |
|
Width | 53.4 mm |
Height | 96.6 mm |
Depth | 71.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 3 Div. |
Color | gray (RAL 7042) |
light gray (RAL 7035) | |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6-FR 20 % GF |
PBT | |
Material group | I |
Housing material | PA 6.6-FR 20 % GF |
PBT |
Mechanical data | |
Open side panel | No |
Mode of protection | (DC+) - (DC-) |
(DC+) - PE | |
(DC-) - PE | |
Protective conductor current IPE | ≤ 350 µA AC |
≤ 100 µA DC | |
Standby power consumption PC | ≤ 80 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Total discharge current ITotal (8/20) µs | 40 kA |
Voltage protection level Up | ≤ 3 kV |
Residual voltage Ures | ≤ 3 kV (at In) |
≤ 2.5 kV (at 10 kA) | |
≤ 2.3 kV (at 5 kA) | |
≤ 2.1 kV (at 3 kA) | |
Response time tA | ≤ 25 ns |
PV protective circuit | |
Connection configuration | Y configuration |
End-of-life mode | OCFM (Open-Circuit Failure Mode) |
Protective circuit DC voltage side (DC) | |
Open circuit voltage UOCSTC | 667 V DC |
Maximum discharge current Imax (8/20) µs | 40 kA |
Response time tA | ≤ 25 ns |
Total discharge current ITotal (8/20) µs | 40 kA |
Insulation resistance Riso | > 5 MΩ (at 500 V DC) |
Nominal discharge current In (8/20) µs | 20 kA |
Continuous operating current ICPV | ≤ 100 µA DC |
Maximum continuous operating voltage UCPV | 800 V DC |
Short-circuit current rating ISCPV | 15000 A |
Residual voltage Ures | ≤ 3 kV (at In) |
≤ 2.5 kV (at 10 kA) | |
≤ 2.3 kV (at 5 kA) | |
≤ 2.1 kV (at 3 kA) | |
Protective conductor current IPE | ≤ 350 µA AC |
≤ 100 µA DC | |
Voltage protection level Up | ≤ 3 kV |
Standby power consumption PC | ≤ 80 mVA |
Ambient conditions | |
Degree of protection | IP20C (Installed) |
Ambient temperature (operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (assembly) | -5 °C ... 50 °C |
Altitude | ≤ 5000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5-500 Hz/2.5 h/XYZ) |
Standards/specifications | EN 61643-31 |
Note | 2019 |
Standards/specifications | IEC 61643-31 |
Note | 2018 |
Mounting type | DIN rail: 35 mm |
Item number | 1466771 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | K1 - Overvoltage Protect. |
Product key | CL13A2 |
GTIN | 4063151862237 |
Weight per piece (including packing) | 311 g |
Weight per piece (excluding packing) | 282,2 g |
Customs tariff number | 85363010 |
Country of origin | DE |
ECLASS
ECLASS-13.0 | 27171402 |
ETIM
ETIM 9.0 | EC000941 |
EU RoHS | |
Fulfills EU RoHS substance requirements | Yes (No exemptions) |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
Your advantages
Easy and safe installation with forward-thinking handling and safety features
Reliable system protection with maximum performance and endurance
Can be used in a wide range of applications due to the optimized design and broad portfolio
Simple planning due to comprehensive digital data and selectors
Phoenix Contact GmbH & Co. KG
Flachsmarktstraße 8, D-32825 Blomberg