You can integrate Axioline Smart Elements into systems with the Smart Element interface. This Smart Element detects the positions of incremental encoders.
    
  
  AXL SE INC1 SYM
   - 
  Function module
    
      1088130
      
      
    
  
      Axioline Smart Elements, Position detection module, Incremental encoder input: 1, symmetrical encoders in accordance with EIA-422, Digital inputs: 2, 24 V DC, degree of protection: IP20
      This product needs further products for operation.
      Mandatory accessories
    
  
      Free download available.
      Downloads
    
  Product details
| Dimensional drawing |  | 
| Width | 14.9 mm | 
| Height | 62.2 mm | 
| Depth | 62 mm | 
| Note on application | |
| Note on application | Only for industrial use | 
| Smart Element interface | |
| Number of interfaces | 1 | 
| Connection method | Card edge connector | 
| Transmission speed | See system in which you use the Smart Element. | 
| Start time until ready to operate | < 500 ms | 
| Module | |
| ID code (hex) | none | 
| Process data channel | 80 bit | 
| Input address area | 10 Byte | 
| Output address area | 10 Byte | 
| Required parameter data | 19 Byte | 
| Required configuration data | 7 Byte | 
| Digital: | |
| Input name | Digital inputs | 
| Description of the input | EN 61131-2, type 3 | 
| Number of inputs | 2 (DI Ref, DI L) | 
| Connection method | Push-in connection | 
| Connection technology | 1-conductor | 
| Input voltage range "0" signal | -3 V DC ... 5 V DC | 
| Input voltage range "1" signal | 11 V DC ... 30 V DC | 
| Nominal input voltage UIN | 24 V DC | 
| Nominal input current at UIN | 3 mA | 
| Protective circuit | Transient protection; Suppressor diode | 
| Encoder | |
| Number of inputs | 1 (A, /A, B, /B, Z, /Z) | 
| Input name | Incremental encoder input | 
| Encoder signals | symmetrical encoders in accordance with EIA-422 | 
| Cable length | max. 30 m (Shielded cable) | 
| Product type | I/O component | 
| Product family | Axioline Smart Elements | 
| Type | modular | 
| Mounting position | See the system in which the Smart Element is used. | 
| Insulation characteristics | |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) | 
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) | 
| Maximum power dissipation for nominal condition | 1.8 W | 
| Encoder | |
| Number | 1 (+5 V) | 
| Nominal output voltage | 5 V DC | 
| Voltage range | 5 V DC ... 5.5 V DC | 
| Current carrying capacity | max. 250 mA | 
| Protective circuit | Short-circuit protection; Electrical and thermal | 
| Overload protection | |
| Transient protection; Suppressor diode | |
| Number | 1 (+24 V) | 
| Nominal output voltage | 24 V DC | 
| Voltage range | 19.2 V DC ... 30 V DC | 
| Current carrying capacity | max. 500 mA | 
| Protective circuit | Short-circuit protection; Electrical (from approx. 600 mA) | 
| Overload protection | |
| Transient protection; Suppressor diode | |
| Number | 1 (A, /A, B, /B, Z, /Z) | 
| Designation | Symmetrical incremental encoders | 
| Signal voltage level | Differential signal (signal – inverted signal), in accordance with EIA-422 | 
| Common mode voltage range signal - ground | -20 V DC ... 20 V DC | 
| Input frequency | max. 1 MHz | 
| Potentials: Communications power supply of the Smart Elements (USE) | |
| Supply voltage | using card edge connectors | 
| Potentials: I/O supply (UP) | |
| Supply voltage | 24 V DC (using card edge connectors) | 
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) | 
| Current draw | max. 700 mA | 
| typ. 512 mA | |
| Current consumption | min. 11 mA (without connected peripherals) | 
| Protective circuit | Surge protection; See the system in which the Smart Element is used. | 
| Reverse polarity protection; Polarity protection diode | |
| Electrical isolation/isolation of the voltage ranges | |
| Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min | 
| Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min | 
| Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min | 
| Connection technology | |
| Connection name | I/O | 
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline Smart Elements” user manual. | 
| Conductor connection | |
| Connection method | Push-in connection | 
| Conductor cross-section rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Stripping length | 8 mm | 
| I/O | |
| Connection method | Push-in connection | 
| Note on the connection method | Please observe the information provided on conductor cross-sections in the “Axioline Smart Elements” user manual. | 
| Conductor cross-section, rigid | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section, flexible | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section AWG | 24 ... 16 | 
| Conductor cross-section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Conductor cross-section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² | 
| Stripping length | 8 mm | 
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 60 °C | 
| Degree of protection | IP20 | 
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) | 
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) | 
| Mounting type | Plug-in mounting (Smart Element slot) | 
| Mounting position | See the system in which the Smart Element is used. | 
| Item number | 1088130 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | O1 - Automatation Systems | 
| Product key | DRIB61 | 
| GTIN | 4055626886183 | 
| Weight per piece (including packing) | 37,7 g | 
| Weight per piece (excluding packing) | 35 g | 
| Customs tariff number | 85389091 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27242605 | 
| ECLASS-15.0 | 27242605 | 
ETIM
| ETIM 9.0 | EC001601 | 
UNSPSC
| UNSPSC 21.0 | 32151600 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| SCIP | c1cefc67-bf3c-4ac2-91fa-26cef19be2ca | 
Compatible products
- 
    
      SZS 0,4X2,5 VDE - Screwdriver 1205037
- 
    
      CRIMPFOX 6 - Crimping pliers 1212034
- 
    
      CRIMPFOX DUO 10 - Crimping pliers 1031721
- 
    
      CRIMPFOX 10T-F - Crimping pliers 1134913
- 
    
      MM-TML (EX4,2)R C1 TR/BK - Label 0803979
- 
    
      SK 5,0 WH:REEL - Marker strip 0805221
- 
    
      UM6M-TM (5X12) - Marker for terminal blocks 0830928
- 
    
      UCT6M-TM 5 - Marker for terminal blocks 0830756
Your advantages
Acquisition of digital signals from symmetrical incremental encoders (A, /A, B, /B, Z, /Z)
        Measuring pulses of up to 1 MHz
        Evaluating linear or rotary axes
        Power supply for 5 V or 24 V encoder
        1 input can be used for referencing
        Latch function for quick buffering of positions
        32-bit register to output the measured increments
        Device rating plate stored
        Frequently searched
Phoenix Contact GmbH & Co. KG
        
        Flachsmarktstraße 8, D-32825 Blomberg