PLC-RSP- 24UC/21-21
   - 
  Relay module
    
      2912510
      
      
    
  
      PLC-INTERFACE, consisting of PLC-BSP.../21-21 basic terminal block with spring-cage connection and plug-in miniature relay with power contact, for mounting on DIN rail NS 35/7,5, 2 changeover contacts, input voltage 24 V AC/DC
Product details
| Product type | Relay Module | 
| Product family | PLC-INTERFACE | 
| Application | Universal | 
| Operating mode | 100% operating factor | 
| Mechanical service life | 3x 107 cycles | 
| Insulation characteristics: Standards/regulations | |
| Insulation | Safe isolation: Control side / contact side | 
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Data management status | |
| Date of last data management | 12.09.2025 | 
| Maximum power dissipation for nominal condition | 0.42 W | 
| Standards/regulations | |
| Rated surge voltage | 6 kV | 
| Coil side | |
| Nominal input voltage UN | 24 V AC/DC | 
| Input voltage range | 20.2 V AC/DC ... 33.6 V AC/DC | 
| Drive and function | monostable | 
| Typical input current at UN | 17.5 mA | 
| Typical response time | 8 ms | 
| Typical release time | 10 ms | 
| Protective circuit | Bridge rectifier; Bridge rectifier | 
| Operating voltage display | Yellow LED | 
| Switching | |
| Contact switching type | 2 changeover contacts | 
| Type of switch contact | Single contact | 
| Contact material | AgNi | 
| Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) | 
| Minimum switching voltage | 5 V AC/DC (at 10 mA) | 
| Limiting continuous current | 6 A | 
| Maximum inrush current | 15 A (300 ms) | 
| Min. switching current | 10 mA (At 5 V) | 
| Interrupting rating (ohmic load) max. | 140 W (at 24 V DC) | 
| 85 W (at 48 V DC) | |
| 60 W (at 60 V DC) | |
| 44 W (at 110 V DC) | |
| 60 W (at 220 V DC) | |
| 1500 VA (for 250 V AC) | |
| Switching capacity | 2 A (at 24 V, DC13) | 
| 3 A (at 24 V, AC15) | |
| 3 A (at 120 V, AC15) | |
| 0.2 A (at 250 V, DC13) | |
| 3 A (at 250 V, AC15) | |
| Coil side | |
| Connection method | Spring-cage connection | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.14 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.14 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 26 ... 14 | 
| Contact side | |
| Connection method | Spring-cage connection | 
| Stripping length | 8 mm | 
| Conductor cross-section rigid | 0.14 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.14 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 26 ... 14 | 
| Width | 14 mm | 
| Height | 80 mm | 
| Depth | 94 mm | 
| Color | green (RAL 6021) | 
| Flammability rating according to UL 94 (Housing) | V0 (Housing) | 
| Ambient conditions | |
| Degree of protection (Relay) | RT III (Relay) | 
| Degree of protection (Relay base) | IP20 (Relay base) | 
| Ambient temperature (operation) | -40 °C ... 60 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Standards/regulations | |
| Standards/regulations | IEC 60664 | 
| IEC 60947-5-1 | |
| Mounting type | DIN rail mounting | 
| Assembly note | in rows with zero spacing | 
| Mounting position | any | 
| Item number | 2912510 | 
| Packing unit | 10 pc | 
| Minimum order quantity | 10 pc | 
| Sales key | DK622C | 
| Product key | DK622C | 
| GTIN | 4046356050920 | 
| Weight per piece (including packing) | 63.39 g | 
| Weight per piece (excluding packing) | 61.55 g | 
| Customs tariff number | 85364190 | 
| Country of origin | DE | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | No substance above 0.1 wt% | 
Compatible products
            Note: Applying some accessories below might limit this product.
          
          
        - 
    
      FBST 500-PLC RD - Continuous plug-in bridge 2966786
- 
    
      FBST 500-PLC BU - Continuous plug-in bridge 2966692
- 
    
      FBST 500-PLC GY - Continuous plug-in bridge 2966838
- 
    
      FBST 6-PLC RD - Single plug-in bridge 2966236
- 
    
      FBST 6-PLC BU - Single plug-in bridge 2966812
- 
    
      FBST 6-PLC GY - Single plug-in bridge 2966825
- 
    
      NS 35/ 7,5 V2A UNPERF 2000MM - DIN rail, unperforated 0801377
- 
    
      NS 35/ 7,5 PERF 2000MM - DIN rail perforated 0801733
- 
    
      NS 35/ 7,5 CU UNPERF 2000MM-VPE 10 - DIN rail, unperforated 0801762
- 
    
      NS 35/15 UNPERF 2000MM - DIN rail, unperforated 1201714
- 
    
      NS 35/15 CU UNPERF 2000MM-VPE 10 - DIN rail, unperforated 1201895
- 
    
      NS 35/15-2,3 UNPERF 2000MM-VPE 10 - DIN rail, unperforated 1201798
- 
    
      NS 35/15 AL UNPERF 2000MM - DIN rail, unperforated 1201756
- 
    
      NS 35/15 PERF 2000MM - DIN rail perforated 1201730
- 
    
      NS 35/ 7,5 UNPERF 2000MM - DIN rail, unperforated 0801681
- 
    
      ZB10/WH-100:UNBEDRUCKT - Zack marker strip 5060883
- 
    
      ZB 10:UNBEDRUCKT - Zack marker strip 1053001
- 
    
      PLC-ATP BK - Separating plate 2966841
- 
    
      PLC-ESK GY - Power terminal block 2966508
- 
    
      SZF 1-0,6X3,5 - Screwdriver 1204517
- 
    
      UC-TM 12 - Marker for terminal blocks 0819194
- 
    
      UCT-TM 12 - Marker for terminal blocks 0829144
- 
    
      REL-MR- 24DC/21-21 - Single relay 2961192
Your advantages
Slim design
        Efficient connection to system cabling using V8 adapter
        RT III sealed relay
        Safe isolation between coil and contact side
        Functional plug-in bridges
        Integrated input circuit and interference suppression circuit
        PHOENIX CONTACT PTY Ltd.
        
        Level 12 1PSQ, 169 Macquarie Street, Parramatta NSW 2150