Repeater power supply and input signal conditioner, HART: Transmits supplied or active 0/4 … 20 mA signals to a load (active or passive). HART signals are transmitted bidirectionally. The output can be operated either actively or passively via switches. The measuring transducer is installed on a corresponding VIP I/O marshalling base element by means of plug-in contact. Installation in zone 2, “ec” type of protection is permitted.
    
  
  IOA MCR-RPSS-I-I
   - 
  Power/input signal conditioner
    
      1085774
      
      
    
  
      Repeater power supply and input signal conditioner, HART-transparent, for VIP I/O marshalling base elements: Transmits 0/4 mA ... 20 mA signals to a load (active or passive). 3-way electrical isolation, SIL 2, SC 3 in accordance with IEC 61508
      This product needs further products for operation.
      Mandatory accessories
    
  Product details
| Product type | Repeater power supply | 
| Product family | VIP I/O-Marshalling | 
| Application | Analog IN | 
| No. of channels | 1 | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Signal transmission behavior | In = Out | 
| Step response (10-90%) | < 200 µs (for jump 0 mA ... 20 mA, load 100 Ω) | 
| < 400 µs (for jump 4 mA ... 20 mA, load 600 Ω) | |
| Maximum temperature coefficient | < 0.01 %/K | 
| Temperature coefficient, typical | < 0.004 %/K | 
| Maximum transmission error | < 0.1 % (of final value) | 
| Transmission error, typical | < 0.05 % (of final value) | 
| Reverse polarity protection | yes | 
| Electrical isolation | |
| Overvoltage category | II (≤ 5000 m) | 
| Pollution degree | 2 (≤ 5000 m) | 
| Electrical isolation Input/output/power supply IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 200 Vrms | 
| Test voltage | 2.3 kV AC (50 Hz, 60 s) | 
| Insulation | Double/reinforced insulation | 
| Electrical isolation Input/output/power supply IEC/EN 60079-7 | |
| Standards/regulations | IEC/EN 60079-7 | 
| Rated insulation voltage | 251 Vrms | 
| 355 VP | |
| Supply | |
| Designation | Repeater power supply operation | 
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC -20 % ... +25 % | 
| Max. current consumption | < 62 mA (24 V DC / 20 mA / 600 Ω) | 
| < 77 mA (19.2 V DC / 20 mA / 600 Ω) | |
| < 54 mA (24 V DC / 20 mA / 250 Ω) | |
| Power dissipation | < 0.8 W (24 V DC / 20 mA / 600 Ω) | 
| < 0.8 W (24 V DC / 20 mA / 250 Ω) | |
| < 1.2 W (24 V DC / 20 mA / 0 Ω) | |
| Power consumption (Output active) | < 1.5 W (24 V DC / 20 mA / 600 Ω) | 
| < 1.3 W (24 V DC / 20 mA / 250 Ω) | |
| Supply | |
| Designation | Signal conditioner operation | 
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC -20 % ... +25 % | 
| Max. current consumption | < 35 mA (24 V DC / 20 mA / 600 Ω) | 
| < 44 mA (19.2 V DC / 20 mA / 600 Ω) | |
| < 27 mA (24 V DC / 20 mA / 250 Ω) | |
| Power dissipation | < 0.6 W (24 V DC / 20 mA / 600 Ω) | 
| < 0.6 W (24 V DC / 20 mA / 250 Ω) | |
| < 1 W (24 V DC / 20 mA / 0 Ω) | |
| Power consumption (Output active) | < 0.8 W (24 V DC / 20 mA / 600 Ω) | 
| < 0.6 W (24 V DC / 20 mA / 250 Ω) | |
| Signal: Repeater power supply operation | |
| Description of the input | Active current input | 
| Number of inputs | 1 | 
| Input signal | Current | 
| Current input signal | 4 mA ... 20 mA | 
| Current limitation | 23.5 mA | 
| Transmitter supply voltage | > 21 V (20 mA) | 
| > 21 V (24 mA) | |
| Polarization and surge protection | Yes | 
| Underload/overload signal range | 0 mA ... 23 mA (Extended transmission range for diagnostics) | 
| Signal: Signal conditioner operation | |
| Description of the input | Passive current input | 
| Number of inputs | 1 | 
| Current input signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Voltage drop | < 3.5 V (in input isolating amplifier operation) | 
| Underload/overload signal range | 0 mA ... 24 mA (500 Ω) | 
| Signal: Repeater power supply operation | |
| Output description | Current output (active and passive) | 
| Number of outputs | 1 | 
| Current output signal | 4 mA ... 20 mA (active) | 
| 4 mA ... 20 mA (Passive, external source voltage 19.2 V ... 26.4 V) | |
| Load/output load current output | ≤ 600 Ω (20 mA) | 
| Output ripple | < 20 mVrms | 
| Output behavior in the event of an error | 0 mA (Cable break in the input) | 
| ≥ 22.5 mA (Cable short-circuit in the input) | |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) | 
| Signal: Signal conditioner operation | |
| Output description | Current output (active and passive) | 
| Current output signal | 0 mA ... 20 mA (active) | 
| 4 mA ... 20 mA (active) | |
| 0 mA ... 20 mA (Passive, external source voltage 19.2 V ... 26.4 V) | |
| 4 mA ... 20 mA (Passive, external source voltage 19.2 V ... 26.4 V) | |
| Load/output load current output | ≤ 600 Ω (20 mA) | 
| Output ripple | < 20 mVrms | 
| Output behavior in the event of an error | 0 mA (Cable break in the input) | 
| 0 mA (Cable short-circuit in the input) | |
| Underload/overload signal range | 0 mA ... 22.5 mA (Extended transmission range for diagnostics) | 
| Connection method | Plug-in connection | 
| Number of connections | 1 | 
| Number of positions | 11 | 
| Data communication (bypass) | |
| HART function | HART transparency | 
| Protocols supported | HART | 
| Status display | Green LED (supply voltage) | 
| Width | 10.3 mm | 
| Height | 80.1 mm | 
| Depth | 136 mm | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -40 °C ... 70 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 2000 m ... 3000 m | 
| Ambient temperature (operation) | -40 °C ... 63 °C | 
| Rated insulation voltage | 150 Vrms (Input/output/power supply) | 
| Insulation | Double/reinforced insulation | 
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 3000 m ... 4000 m | 
| Ambient temperature (operation) | -40 °C ... 56 °C | 
| Rated insulation voltage | 150 Vrms (Input/output/power supply) | 
| Insulation | Double/reinforced insulation | 
| Altitude range (IEC/EN 61010-1) | |
| Height range | > 4000 m ... 5000 m | 
| Ambient temperature (operation) | -40 °C ... 49 °C | 
| Rated insulation voltage | 150 Vrms (Input/output/power supply) | 
| Insulation | Double/reinforced insulation | 
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 2000 m ... 3000 m | 
| Ambient temperature (operation) | -40 °C ... 63 °C | 
| Rated insulation voltage | 162 Vrms (Input/output/power supply) | 
| 230 VP (Input/output/power supply) | |
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 3000 m ... 4000 m | 
| Ambient temperature (operation) | -40 °C ... 56 °C | 
| Rated insulation voltage | 60 Vrms (Input/output/power supply) | 
| 84 VP (Input/output/power supply) | |
| Altitude range (IEC/EN 60079-7) | |
| Height range | > 4000 m ... 5000 m | 
| Ambient temperature (operation) | -40 °C ... 49 °C | 
| Rated insulation voltage | 60 Vrms (Input/output/power supply) | 
| 84 VP (Input/output/power supply) | |
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  II 3 G Ex ec IIC T4 Gc | 
| Certificate | PxCIF08ATEX2865955X | 
| IECEx | |
| Identification | Ex ec IIC T4 Gc | 
| Certificate | IECEx BVS 08.0016X | 
| UL, USA/Canada | |
| Identification | UL 61010-1 | 
| UL 61010-2-201 | |
| UL 61010-2-030 | |
| CAN/CSA No. 61010-1-12 | |
| CAN/CSA C22.2 No. 61010-2-201 | |
| CSA C22.2 No. 61010-2-030 | |
| Certificate | E330267 | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Certificate | 1435.IM.131623/19, V1.0 | 
| Systematic Capability | |
| Identification | 3 | 
| Corrosive gas test | |
| Identification | ISA S71.04.2013 G3 Harsh Group A | 
| UL data | |
| Operating mode | Indoor use | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 1 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 1 % | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 1 % | 
| Electrical isolation | 3-way isolation | 
| Mounting type | Plug-in mounting | 
| Mounting position | any | 
| Item number | 1085774 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK1151 | 
| Product key | DK1151 | 
| GTIN | 4055626875439 | 
| Weight per piece (including packing) | 122.7 g | 
| Weight per piece (excluding packing) | 100 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210120 | 
| ECLASS-15.0 | 27210120 | 
ETIM
| ETIM 9.0 | EC002653 | 
UNSPSC
| UNSPSC 21.0 | 39121008 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | EFUP-50 An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. | 
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
Compatible products
Your advantages
Up to SIL 2 in accordance with EN 61508
        Installation in zone 2, protection type "ec" (EN 60079-7) permitted
        Bidirectional transmission of digital HART communication signals
        3-way electrical isolation
        Output: 0/4 mA ... 20 mA (active or passive)
        Input: 0/4 mA ... 20 mA (powered or not powered)
        PHOENIX CONTACT SAS
        
        52 Boulevard de Beaubourg; Emerainville 77436 Marne La Vallée Cedex 2