The 6.2 mm wide MINI MCR-SL-IDS-I-I... output signal conditioner transmits 0/4 - 20 mA signals from the controller to a load located in the field (I/P converters, control valves, indicators) with simultaneous 3-way electrical isolation between the input, output, and supply.
HART data protocols can be transmitted bidirectionally.
Electrically isolated 0 ... 20 mA or 4 ... 20 mA standard analog signals are available on the input and output side.
Power (19.2 V DC ... 30 V DC) can either be supplied via the connection terminal blocks of the modules or in conjunction with the DIN rail connector.  
    
  
  MINI MCR-SL-IDS-I-I
   - 
  Output signal conditioner
    
      2905577
      
      
    
  
      3-way output signal conditioner for transmitting 0/4 ... 20 mA signals from the controller to a load located in the field with simultaneous 3-way electrical isolation between the input, output, and supply, with screw connection
Product details
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area | 
| Product type | Repeater power supply | 
| Product family | MINI Analog | 
| No. of channels | 1 | 
| Insulation characteristics | |
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Limit frequency (3 dB) | > 175 Hz | 
| Protective circuit | Transient protection | 
| Signal transmission behavior | In = Out | 
| Step response (10-90%) | < 2 ms | 
| Maximum temperature coefficient | < 0.01 %/K | 
| Temperature coefficient, typical | < 0.01 %/K | 
| Maximum transmission error | ≤ 0.1 % (of final value) | 
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 50 V AC/DC | 
| Test voltage | 1.5 kV AC (50 Hz, 60 s) | 
| Insulation | Basic insulation in accordance with IEC/EN 61010 | 
| Supply | |
| Nominal supply voltage | 24 V DC | 
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) | 
| Power consumption | < 600 mW (at 24 V DC) | 
| Signal | |
| Number of inputs | 1 | 
| Current input signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Max. current input signal | 20 mA | 
| Input voltage limitation | < 2 V (20 mA) | 
| Signal: Current | |
| Number of outputs | 1 | 
| Current output signal | 0 mA ... 20 mA | 
| 4 mA ... 20 mA | |
| Load/output load current output | ≤ 800 Ω (at 20 mA) | 
| Ripple | < 20 mVrms | 
| Connection method | Screw connection | 
| Stripping length | 12 mm | 
| Screw thread | M3 | 
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 26 ... 12 | 
| Data communication (bypass) | |
| HART function | Yes | 
| Limit frequency (3 dB) | 2.5 Hz | 
| Dimensional drawing | 
                 | 
            
| Width | 6.2 mm | 
| Height | 93.1 mm | 
| Depth | 101.2 mm | 
| Color | green (RAL 6021) | 
| Housing material | PBT | 
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 | 
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -20 °C ... 60 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| UKCA | |
| Certificate | UKCA-compliant | 
| UL, USA/Canada | |
| Identification | UL 508 Listed | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Zone 2, Group IIC | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA000020N | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | B | 
| EMC | A | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 | 
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Typical deviation from the measuring range final value | 3 % | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Typical deviation from the measuring range final value | 3 % | 
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 | 
| Surge current load (surge) | |
| Comments | Criterion B | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Typical deviation from the measuring range final value | 3 % | 
| Electrical isolation | 3-way isolation | 
| Mounting type | DIN rail mounting | 
| Assembly note | The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715. | 
| Mounting position | any | 
| Item number | 2905577 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | DK1132 | 
| Product key | DK1132 | 
| GTIN | 4046356966290 | 
| Weight per piece (including packing) | 87.7 g | 
| Weight per piece (excluding packing) | 87.7 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
ECLASS
| ECLASS-13.0 | 27210120 | 
| ECLASS-15.0 | 27210120 | 
ETIM
| ETIM 9.0 | EC002653 | 
UNSPSC
| UNSPSC 21.0 | 39121000 | 
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes | 
| Exemption | 6(c), 7(a), 7(c)-I | 
| China RoHS | |
| Environment friendly use period (EFUP) | 
              EFUP-50
               An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. 
             | 
          
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) | 
| 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol (CAS: 79-94-7) | |
| SCIP | 635dca74-920d-42ee-a421-9ee4157137aa | 
Compatible products
- 
    
      
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY - DIN rail bus connector 2695439
 - 
    
      
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - DIN rail bus connector 2869728
 - 
    
      
MCR-DP - Separating plate 1430594
 - 
    
      
TC-D37SUB-AIO16-M-PS-UNI - Module carrier 2902934
 - 
    
      
TC-D37SUB-ADIO16-M-P-UNI - Module carrier 2902933
 - 
    
      
GW HART USB MODEM - Cable adapter 1003824
 - 
    
      
MINI MCR DKL - Transparent cover 2308111
 - 
    
      
MINI MCR-DKL-LABEL - Marking label 2810272
 - 
    
      
MINI MCR-SL-PTB - Power terminal block 2864134
 - 
    
      
QUINT4-SYS-PS/1AC/24DC/2.5/SC - Power supply 2904614
 - 
    
      
SZS 0,6X3,5 - Screwdriver 1205053
 
PHOENIX CONTACT SAS
        
        52 Boulevard de Beaubourg; Emerainville 77436 Marne La Vallée Cedex 2