IB IL EX-IS DIO 4/NAM-PAC
-
Inline terminal
2869911
Inline intrinsically safe digital I/O terminal, 4 configurable input/output channels, complete with accessories
Product details
Dimensional drawing |
|
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Utilization restriction | |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Color | blue |
Inline local bus | |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Module | |
ID code (hex) | none |
Digital: | |
Input name | Digital inputs |
Description of the input | Can be configured as input or output |
Number of inputs | 4 |
Connection method | Inline connector |
Connection technology | 2-conductor |
Protective circuit | Polarity protection, surge protection |
Digital: | |
Output name | Digital outputs |
Output description | Digital passive output |
Connection method | Inline connector |
Connection technology | 3-conductor |
Number of outputs | 4 |
Protective circuit | Polarity protection, surge protection |
Output voltage | 24 V |
Nominal output voltage | 24 V DC |
Product type | I/O component |
Product family | Inline |
Type | modular |
Inline | |
No. of channels | 4 |
Potentials | |
Power consumption | 4.8 W (per channel) |
Potentials: Communications power (UL) | |
Supply voltage | 5 V DC (via voltage jumper) |
Current draw | max. 50 mA |
Potentials: | |
Supply voltage | 28 V DC |
Current draw | max. 190 mA |
Conductor connection | |
Connection method | Spring-cage connection |
Conductor cross-section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross-section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross-section AWG | 28 ... 16 |
Stripping length | 8 mm |
Connection method | Spring-cage connection |
Conductor cross-section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross-section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross-section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C ... 60 °C |
Degree of protection | IP20 |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Ex data | |
ATEX | II 3(1)GD Ex ec [ia Ga Da] IIC T4 Gc Sira 09ATEX2339X |
IECEx | Ex ec [ia Ga Da] IIC T4 Gc IECEx SIR 10.0033X |
UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D |
Mounting type | DIN rail mounting |
Safety data | |
Max. output voltage Uo | max. 28 V DC (Output) |
max. 11.76 V DC (Input) | |
Max. output current Io | max. 109 mA (Output) |
max. 15.3 mA (Input) | |
Max. output power Po | max. 757 mW (Output) |
max. 44.8 mW (Input) | |
Safety-related maximum voltage Um | 28 V DC |
IIC (A, B) (Output): Max. external inductivity Lo / Max. external capacitance Co | 1.015 mH / 0.083 µF |
IIB, [IIIC, IIIB] (C, E, F, G) (Output): Max. external inductivity Lo / Max. external capacitance Co | 3.045 mH / 0.625 µF |
IIA (D) (Output): Max. external inductivity Lo / Max. external capacitance Co | 8.12 mH / 2.15 µF |
IIC (A, B) (Input): Max. external inductivity Lo / Max. external capacitance Co | 1.52 mH / 1.5 µF |
IIB, [IIIC, IIIB] (C, E, F, G) (Input): Max. external inductivity Lo / Max. external capacitance Co | 4.56 mH / 9.9 µF |
IIA (D) (Input): Max. external inductivity Lo / Max. external capacitance Co | 21.1 mH / 39 µF |
Item number | 2869911 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales key | DRI1E4 |
Product key | DRI1E4 |
GTIN | 4046356470209 |
Weight per piece (including packing) | 305 g |
Weight per piece (excluding packing) | 204 g |
Customs tariff number | 85389099 |
Country of origin | US |
ECLASS
ECLASS-13.0 | 27242604 |
ETIM
ETIM 9.0 | EC001599 |
UNSPSC
UNSPSC 21.0 | 32151600 |
China RoHS | |
Environment friendly use period (EFUP) |
EFUP-E
No hazardous substances above the limits
|
EU REACH SVHC | |
REACH candidate substance (CAS No.) | No substance above 0.1 wt% |
Compatible products
Your advantages
NAMUR sensors supported (EN 60947-5-6)
4 configurable I/O channels
Single-channel diagnostics
8.2 V sensor supply
PHOENIX CONTACT SAS