Power supply - MINI-PS-100-240AC/24DC/1.5/EX 2866653

Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the potentially explosive area

Detalii despre produs


MINI POWER power supplies for MCR technology
In measurement and control technology (MCR), modular electronics housing has become the industry standard. MINI POWER is the power supply unit to go with it. The devices are flexible, thanks to special voltages and special versions.



Efficiency > 84 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 1.5 A (-25 °C ... 60 °C)
POWER BOOST (IBoost) 2 A (-25°C ... 40°C)
Derating 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Residual ripple < 40 mVPP (with nominal values)
Output power 36 W
Peak switching voltages nominal load < 20 mVPP (20 MHz)
Maximum power dissipation in no-load condition 1.5 W
Power loss nominal load max. 6.5 W
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK active
Output description UOUT > 0.9 x UN: High signal
Maximum switching voltage ≤ 24 V
Output voltage + 24 V DC (Signal)
Maximum inrush current max. 44 mA
Continuous load current ≤ 40 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed

Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
Input voltage range
Input voltage range AC 85 V AC ... 264 V AC
Voltage type of supply voltage AC
Inrush current < 15 A (typical)
Inrush current integral (I2t) 0.6 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time typ. 35 ms (120 V AC)
Mains buffering time typ. 150 ms (230 V AC)
Current consumption 0.75 A (120 V AC)
Current consumption 0.45 A (230 V AC)
Nominal power consumption 88 VA
Typical response time < 0.5 s
Input fuse 3.15 A (slow-blow, internal)
Permissible backup fuse B6 B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)

Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
China RoHS For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Insulation voltage input/output 4 kV AC (type test)
Insulation voltage input/output 3 kV AC (routine test)
Insulation voltage input / PE 4 kV AC (type test)
Insulation voltage input / PE 3 kV AC (routine test)

Width 35 mm
Height 99 mm
Depth 95 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Types of signaling LED
Types of signaling Relay contact
Signal output: DC OK floating
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V DC: LED ON
Signal output: DC OK active
Status display "DC OK" LED green
Note on status display UOUT < 0.9 x UN: LED flashing

Type of housing Polyamide PA, color: green

Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

UL approvals UL/C-UL listed UL 508
UL approvals UL/C-UL Recognized UL 60950-1
Conformity/Approvals
ATEX  II 3 G Ex nA nC IIC T4 Gc X
SIL in accordance with IEC 61508 0

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise emission EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EMC requirements for noise immunity EN 61000-6-2

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 100 % (condensation permitted)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (operation) 15 Hz ... 150 Hz, 2.3g, 90 min.

Signal
Conductor cross section solid min. 0.5 mm2
Conductor cross section solid max. 2.5 mm2
Conductor cross section flexible min. 0.5 mm2
Conductor cross section flexible max. 2.5 mm2
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M4
Input
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm2
Conductor cross section solid max. 2.5 mm2
Conductor cross section flexible min. 0.2 mm2
Conductor cross section flexible max. 2.5 mm2
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm2
Conductor cross section solid max. 2.5 mm2
Conductor cross section flexible min. 0.2 mm2
Conductor cross section flexible max. 2.5 mm2
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Standards/specifications EN 60079-0
Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410

MTBF (IEC 61709, SN 29500) > 2789000 h (40 °C)
Insulation characteristics
Protection class II (in closed control cabinet)
Overvoltage category III
Degree of pollution 2


Cod comandă 2866653
Unitate de ambalare 1 pc
Cantitate minimă pentru comandă 1 pc
Pagina de catalog Pagina 277 (C-4-2019)
GTIN 4046356147989
Greutate pe bucată (inclusiv ambalajul) 289,3 GRM
Greutate pe bucată (fără ambalaj) 250,0 GRM
Cod tarifar vamal 85044030
Țara de origine CN



cULus Recognized

cULus Listed


Avantajele dumneavoastră

Easy-maintenance connection technology thanks to keyed COMBICON connectors
Status and error indication via diagnostic LEDs
For supplying the supply voltage via the foot element (DIN rail connector) where AC voltages are available
100 ... 240 V AC nominal input voltage range
24 V DC output voltage
For up to 60 MINI Analog modules
For up to 1.5 A, secondary