Power supply unit - QUINT4-PS/3AC/24DC/40/IOL
1151047

Primary-switched power supply unit, QUINT POWER, Screw connection, DIN rail mounting, input: 3-phase, output: 24 V DC / 40 A

Downloads

Detalhes dos produtos




AC operation
Network type Star network
Nominal input voltage range 3x 400 V AC ... 500 V AC
2x 400 V AC ... 500 V AC
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +10 %
2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage 400 V AC
480 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 1.5 A (at 25 °C)
Inrush current integral (I2t) < 0.06 A2s
Inrush current limitation 1.5 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 26 ms (3x 400 V AC)
typ. 26 ms (3x 480 V AC)
Current consumption 3x 1.8 A (400 V AC)
3x 1.5 A (480 V AC)
2x 3 A (400 V AC)
2x 2.5 A (480 V AC)
3x 1.5 A (500 V AC)
2x 2.4 A (500 V AC)
Reverse polarity protection yes
Nominal power consumption 1217 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.95
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Recommended breaker for input protection 3x 4 A ... 20 A (Characteristic B, C, D, K or comparable)
Recommended fuse for input protection ≥ 300 V AC
Discharge current to PE < 3.5 mA
1 mA (550 V AC, 60 Hz)
DC operation
Nominal input voltage range ± 260 V DC ... 300 V DC
Input voltage range ± 260 V DC ... 300 V DC -13 % ... +30 %
Current consumption 2.2 A (±260 V DC)
1.9 A (±300 V DC)
Nominal power consumption 1217 VA
Recommended breaker for input protection 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection ≥ 1000 V DC

Efficiency typ. 95.4 % (400 V AC)
typ. 95.4 % (480 V AC)
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN) 40 A
Static Boost (IStat.Boost) 45 A
Dynamic Boost (IDyn.Boost) 60 A (5 s)
Selective Fuse Breaking (ISFB) 215 A (15 ms)
Magnetic circuit breaker tripping A1...A40 / B2...B25 / C1...C13 / Z1...Z16
Derating > 60 °C ... 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 960 W
1080 W
1440 W
Maximum no-load power dissipation < 5 W (400 V AC)
< 5 W (480 V AC)
Power loss nominal load max. < 45 W (400 V AC)
< 45 W (480 V AC)
Power dissipation SLEEP MODE < 2 W (400 V AC)
< 2 W (480 V AC)
Crest factor typ. 1,6 (400 V AC)
typ. 1.9 (480 V AC)
Rise time < 1 s (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal relay 13/14 (configurable)
Default closed (Uout > 0.9 USet)
Digital 24 V DC 1 A
30 V AC/DC 0.5 A

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 4 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 10
Stripping length 8 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 16 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 6
Stripping length 10 mm
Tightening torque, min 1.2 Nm
Tightening torque max 1.5 Nm
Signal
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min. 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max. 1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min. 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

IO-Link
Reverse polarity protection yes
Specification V1.1
Interface IO-Link
Connection method 3-conductor port class A
Connection marking 3.3 (L+)
3.4 ()
3.5 (L-)
Transmission speed 230 kbps (COM3)
Cycle time 2 ms
Electrical isolation yes
Amount of process data 6 Byte (Input data)
Device ID 262657dec/ 0x040201hex
Vendor ID 00B0hex / 176dez
Interface System communication
Connection method 2-conductor
Connection marking 3.6 ()
3.5 (L-/Sgnd)
Electrical isolation yes

Signal output
POut > 100 % (LED lights up yellow, output power > 960 W)
UOut > 0.9 x USet (LED lights up green)

Number of phases 3.00
Insulation voltage input/output 4 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency 32 kHz ... 100 kHz (Auxiliary converter stage)
55 kHz ... 300 kHz (Main converter stage)
25 kHz ... 500 kHz (PFC stage)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 849000 h (25 °C)
> 517000 h (40 °C)
> 236000 h (60 °C)
Environmental protection directive RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class I
Degree of pollution 2
Life expectancy (electrolytic capacitors)
Current 20 A
Temperature 40 °C
Time 394000 h
Additional text 400 V AC
Life expectancy (electrolytic capacitors)
Current 20 A
Temperature 40 °C
Time 367000 h
Additional text 480 V AC
Life expectancy (electrolytic capacitors)
Current 40 A
Temperature 25 °C
Time 394000 h
Additional text 400 V AC
Life expectancy (electrolytic capacitors)
Current 40 A
Temperature 25 °C
Time 367000 h
Additional text 480 V AC
Life expectancy (electrolytic capacitors)
Current 40 A
Temperature 40 °C
Time 139000 h
Additional text 400 V AC
Life expectancy (electrolytic capacitors)
Current 40 A
Temperature 40 °C
Time 130000 h
Additional text 480 V AC

Width 120 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

Mounting type DIN rail mounting
Mounting position horizontal DIN rail NS 35, EN 60715
With protective coating No

Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Hood version Stainless steel X6Cr17
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude ≤ 5000 m (> 2000 m, observe derating)
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 11 ms, 15 g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5 Hz ... 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) mounted with UWA 130 - 2901664

Rail applications EN 50121-3-2
EN 50121-5
IEC 62236-3-2
IEC 62236-5
HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard - Safety of transformers EN 61558-2-16
DIN 41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706, EN 61000-4-11
Overvoltage category
EN 61010-1 II (≤ 5000 m)
EN 62477-1 III (≤ 2000 m)
EN 61558-2-16 II (≤ 4000 m)

CSA CAN/CSA-C22.2 No. 61010-1-12
CAN/CSA-C22.2 No. 61010-2-201
SIQ CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals UL Listed UL 61010-1
UL Listed UL 61010-2-201
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements, power plant EN 61000-6-5
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Interference emission Noise emission according to EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Noise immunity Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
Harmonic currents
Standards/regulations EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range 0 kHz ... 2 kHz
Flicker
Standards/regulations EN 61000-3-3
EN 61000-3-3
Frequency range 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 2 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations EN 61000-4-8
Frequency 16.7 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz ... 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips
Standards/regulations EN 61000-4-11
Voltage 400 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 0.5 / 1 / 25 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 period
Criterion B: 25 periods
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Additional text Test Level 2
Comments Criterion B
Voltage dip 0 %
Number of periods 0,5 / 1 / 5 / 50 / 250 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations EN 61000-4-12
Input 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 3)
Voltage 10 V 1 V
Test level 2 150 Hz 1.5 kHz (Test Level 3)
Voltage 1 V
Test level 3 1.5 kHz 15 kHz (Test Level 3)
Voltage 1 V 10 V
Test level 4 15 kHz 150 kHz (Test Level 3)
Voltage 10 V
Test level 5 50 Hz 60 Hz (Test Level 3)
Voltage 10 V (Permanent)
Test level 6 50 Hz 60 Hz (Test Level 3)
Voltage 100 V (1 s)
Comments Criterion A
Attenuated oscillating magnetic field
Standards/regulations EN 61000-4-10
Test field strength 100 A/m
Test level 1 100 kHz
Test field strength 100 A/m
Test level 2 1 MHz
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

N.º de artigo 1151047
Pcs./Emb 1 Unidade
Quantidade mínima de pedido 1 Unidade
Chave comercial CMP
Chave de produto CMPI13
GTIN 4063151146894
Peso por unidade (inclusive embalagem) 2 811,6 g
Peso por unidade (excluindo embalagem) 2 811,6 g
Número do imposto alfandegário 85044030
País de origem TH


ECLASS

ECLASS-11.0 27040701
ECLASS-9.0 27040701
ECLASS-10.0.1 27040701

ETIM

ETIM 8.0 EC002540

UNSPSC

UNSPSC 21.0

CSA

Approval ID: 80005464

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

Vantagens

Most powerful output side: easy system expansion, reliable heavy load startup and miniature circuit breaker tripping
Most robust input side: high noise immunity, thanks to integrated gas-filled surge arrester (up to 6 kV) and ≥ 20 ms mains failure buffer time
Most comprehensive signaling: preventive function monitoring reports critical operating states before errors occur
Communicative: Use in all industrial networks with integrated IO-Link interface and direct connection to the QUINT UPS or the CAPAROC circuit breaker system with the system integration