Monitoring module - EMR-UDC/1/UV- 24V - 2764603

No picture available

Electronic monitoring relay EMR, for overvoltage detection, with adjustable hysteresis and relay output, nominal voltage 24 V DC

Price:

Overview

Technical data

Downloads

Drawings



Application drawing  

Application drawing

Diagram  

Diagram



Circuit diagram  

Circuit diagram

Back to top

Dimensions

Width 45 mm
Height 75 mm
Depth 108 mm
Back to top

Ambient conditions

Ambient temperature (operation) -10 °C ... 60 °C (non-condensing)
Immunity to the discharge of static electricity IEC 801-2/EN 60 801-2/intensity 3
Immunity to electromagnetic fields IEC 801-3/DIN VDE 0843-3/intensity 3
Immunity to fast transients (Burst) IEC/DIS 77B(CO)22/prEN 61 000-4-4/intensity 4
Immunity to surge currents (Surge) IEC 65A/77B (CO)41/25, Draft/intensity 4
Back to top

Input data

Nominal input voltage UN 24 V DC
Input voltage range in reference to UN 0.7 ... 1.3
Setting range of the nominal value 75 % ... 105 % (with reference to UN)
Temperature coefficient, typical < 0.03 %
Setting range of the hysteresis 2 % ... 40 % (with reference to the setpoint)
Response delay 0.1 s ... 10 s
Off delay 200 ms
Back to top

Contact side

Contact type Single contact, 2-PDT
Contact material AgNi 90/10, + 5 µm hard gold-plated
Maximum switching voltage 24 V AC/DC
250 V AC/DC (when the gold layer is destroyed)
Limiting continuous current 0.5 A
5 A (when the gold layer is destroyed)
Maximum inrush current 0.2 A
6 A (when the gold layer is destroyed)
Interrupting rating (ohmic load) max. 5 W (at 24 V DC)
120 W (at 24 V DC - Value applies when the gold layer is destroyed)
40 W (at 48 V DC - Value applies when the gold layer is destroyed)
35 W (at 60 V DC - Value applies when the gold layer is destroyed)
30 W (at 110 V DC - Value applies when the gold layer is destroyed)
55 W (at 220 V DC - Value applies when the gold layer is destroyed)
5 VA (for 24 V AC)
1100 VA (at 250 V AC - Value applies when the gold layer is destroyed)
Back to top

General

Mechanical service life 2x 107 cycles
Nominal power consumption < 5 VA
Test voltage relay winding/relay contact 4 kV AC
Test voltage relay contact/relay contact 2 kV AC
Mounting position any
Assembly instructions In rows with zero spacing
Housing insulation material ABS
Color green
Back to top

Connection data

Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Back to top

Standards and Regulations

Standards/regulations IEC 664
IEC 664 A
DIN VDE 0110-1
DIN VDE 0106-101
DIN VDE 0160
Immunity to the discharge of static electricity IEC 801-2/EN 60 801-2/intensity 3
Immunity to electromagnetic fields IEC 801-3/DIN VDE 0843-3/intensity 3
Immunity to fast transients (Burst) IEC/DIS 77B(CO)22/prEN 61 000-4-4/intensity 4
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27371105
eCl@ss 4.1 27371105
eCl@ss 5.0 27371801
eCl@ss 5.1 27371801
eCl@ss 6.0 27371801
Back to top

ETIM

ETIM 2.0 EC001438
ETIM 3.0 EC001438
ETIM 4.0 EC001438
Back to top

UNSPSC

UNSPSC 6.01 30211916
UNSPSC 7.0901 39121535
UNSPSC 11 39121535
UNSPSC 13.2 39121535
Back to top

PHOENIX CONTACT (Pty) Ltd.

36 Lyn Road
P.O. Box 916
ZA-Ferndale 2160
+27/11/801-8200