DIN rail bus connectors - ME 17,5 TBUS 1,5/ 5-ST-3,81 GN - 2709561

DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.

Price:

Overview

Technical data

Approvals

Downloads

Item properties

Brief article description DIN rail bus connectors
Range of articles TBUS5..3,81
Pitch 3.81 mm
Number of positions 5
Mounting type DIN rail mounting
Back to top

Electrical parameters

Nominal current IN 8 A (parallel contacts)
Nom. voltage 125 V
Rated voltage (III/3) 125 V
Rated voltage (III/2) 125 V
Rated voltage (II/2) 320 V
Rated surge voltage (III/3) 2.5 kV
Rated surge voltage (III/2) 2.5 kV
Rated surge voltage (II/2) 2.5 kV
Back to top

Material data - contact

Contact material Cu alloy
Surface characteristics Completely gold-plated
Back to top

Material data - housing

Housing color green (6021)
Insulating material PA
Insulating material group I
CTI according to IEC 60112 600
Flammability rating according to UL 94 V0
Back to top

Dimensions for the product

Length [ l ] 20.45 mm
Width [ w ] 24.2 mm
Height [ h ] 36.3 mm
Pitch 3.81 mm
Back to top

Dimensions for PCB design

PCB thickness 1.4 mm ... 1.8 mm
Back to top

Packaging information

Type of packaging packed in cardboard
Pieces per package 10
Denomination packing units Pcs.
Outer packaging type Carton
Back to top

General product information

Type of note Recommendation
Note Material of contact pads for bus connector, galvanic gold (hard gold)
Back to top

Ambient conditions

Ambient temperature (storage/transport) -40 °C ... 55 °C
Ambient temperature (assembly) -5 °C ... 100 °C
Ambient temperature (operation) -40 °C ... 105 °C (dependent on the derating curve)
Relative humidity (storage/transport) 80 %
Back to top

Mechanical tests according to standard

Test specification IEC 61984:2008-10
Visual inspection IEC 60512-1-1:2002-02
Dimension check IEC 60512-1-2:2002-02
Insertion and withdrawal force IEC 60512-13-2:2006-02
No. of cycles 25
Insertion strength per pos. approx. 6 N
Withdraw strength per pos. approx. 5 N
Polarization and coding IEC 60512-13-5:2006-02
Contact holder in insert IEC 60512-15-1:2008-05
Test force per pos. 20 N
Back to top

Air clearances and creepage distances

Clearances and creepage distances IEC 60664-1:2007-04
Specification IEC 60664-1:2007-04
Minimum clearance - inhomogeneous field (III/3) 1.5 mm
Minimum clearance - inhomogeneous field (III/2) 1.5 mm
Minimum clearance - inhomogeneous field (II/2) 1.5 mm
Minimum creepage distance value (III/3) 1.9 mm
Minimum creepage distance value (III/2) 0.75 mm
Minimum creepage distance value (II/2) 1.6 mm
Back to top

Mechanical tests (A)

Test specification IEC 61984:2008-10
Insertion strength per pos. approx. 6 N
Withdraw strength per pos. approx. 5 N
Polarization when inserted requirement >20 N Test passed
Contact holder in insert requirements >20 N Test passed
Back to top

Durability tests (B)

Specification IEC 60512-9-1:2010-03
Contact resistance R1 4.4 mΩ
Insertion/withdrawal cycles 25
Contact resistance R2 4.5 mΩ
Impulse withstand voltage at sea level 2.95 kV
Back to top

Thermal tests (C)

Specification IEC 60512-5-1:2002-02
Number of positions 5
Back to top

Climatic tests (D)

Specification ISO 6988:1985-02
Cold stress -40 °C/2 h
Thermal stress 100 °C/168 h
Corrosive stress 0.2 dm3 SO2 on 300 dm3/40 °C/1 cycle
Impulse withstand voltage at sea level 2.95 kV
Power-frequency withstand voltage 1.39 kV
Back to top

Environmental and durability tests (E)

Specification IEC 61984:2008-10
Result, degree of protection, IP code Finger safety with IP20 test finger
Back to top

Mechanical strength/tumbling barrel

Specification IEC 60998-1:2002-12
Number of drop cycles 50
Back to top

Vibration test

Specification IEC 60068-2-6:2007-12
Frequency 10 - 150 - 10 Hz
Sweep speed 1 octave/min
Amplitude 0.35 mm (10 - 60.1 Hz)
Acceleration 5g (60.1 - 500 Hz)
Test duration per axis 2.5 h
Test directions X-, Y- and Z-axis (pos. and neg.)
Back to top

Shocks

Specification IEC 60068-2-27:2008-02
Pulse shape Semi-sinusoidal
Acceleration 15g
Shock duration 11 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Back to top

Test for assessing the risk of fire (glow wire)

Specification IEC 60695-2-10:2013-04
Temperature 850 °C
Time of exposure 30 s
Back to top

Standards and Regulations

Connection in acc. with standard CUL
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27440402
eCl@ss 11.0 27460201
eCl@ss 4.0 27260700
eCl@ss 4.1 27260700
eCl@ss 5.0 27260700
eCl@ss 5.1 27260700
eCl@ss 6.0 27260700
eCl@ss 7.0 27440309
eCl@ss 9.0 27440402
Back to top

ETIM

ETIM 2.0 EC001031
ETIM 3.0 EC001031
ETIM 4.0 EC002638
ETIM 5.0 EC002637
ETIM 6.0 EC002584
ETIM 7.0 EC002584
Back to top

UNSPSC

UNSPSC 6.01 31261501
UNSPSC 7.0901 31261501
UNSPSC 11 31261501
UNSPSC 12.01 31261501
UNSPSC 13.2 39121409
UNSPSC 18.0 39121552
UNSPSC 19.0 39121552
UNSPSC 20.0 39121552
UNSPSC 21.0 39121552
Back to top

PHOENIX CONTACT (Pty) Ltd.

36 Lyn Road
P.O. Box 916
ZA-Ferndale 2160
+27/11/801-8200

Service

HIGHLIGHTS 2020

Creative solutions for a smart world

  • Create PDF
  • Recommend
  • Feedback