Ambient temperature (operation) | -25 °C ... 75 °C |
---|---|
Ambient temperature (storage/transport) | -25 °C ... 75 °C |
Housing material | PA 6 |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | jet black RAL 9005 |
For country-specific use in | D |
Mounting type | Plugging into the mains socket |
Type | Attachment plug |
Direction of action | L/N-PE & Signal Line-Earth Ground |
EN type | T3 |
---|---|
Nominal voltage UN | 230 V AC |
Arrester rated voltage UC (L-N) | 275 V AC |
Arrester rated voltage UC (L-PE) | 360 V AC |
Arrester rated voltage UC (N-PE) | 360 V AC |
Nominal frequency fN | 50 Hz (60 Hz) |
Rated load current IL | 16 A (30 °C) |
Standby power consumption PC | ≤ 1 VA |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In (8/20) µs | 3 kA (> 5x) |
Combination wave UOC | 4 kV |
Energy absorption symmetrical | 140 J (L-N) |
Enery absorption, asymmetrical | 220 J (L(N)-PE) |
Voltage protection level Up (L-N) | ≤ 1.2 kV |
Voltage protection level Up (L-PE) | ≤ 1.5 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Response time (L-N) | ≤ 25 ns |
Response time (L-PE) | ≤ 100 ns |
Response time (N-PE) | ≤ 100 ns |
Surge protection fault message | optical |
Max. required back-up fuse | 16 A (gG / B / C) |
Connection method | Grounding plug/socket |
---|---|
Connection method IN | Grounding plug |
Connection method OUT | Grounding socket |
Arrester rated voltage UC | 200 V DC |
---|---|
Rated current | 150 mA (25 °C) |
Operating effective current IC at UC | ≤ 150 µA |
Residual current IPE | ≤ 2 µA |
Insulation resistance Riso | ≥ 1 MΩ |
≥ 1 GΩ | |
Nominal discharge current In (8/20) µs (line-line) | 1 kA |
Nominal discharge current In (8/20) µs (line-earth) | 2.5 kA |
Max. discharge current Imax (8/20) µs | 2.5 kA |
Voltage protection level Up (line-line) | ≤ 460 V (C2 - 1 kA) |
≤ 350 V (C3 - 25 A) | |
Voltage protection level Up (line-earth) | ≤ 900 V (C2 - 2 kA) |
≤ 900 V (C3 - 100 A) | |
Response time tA (line-line) | ≤ 25 ns |
Response time tA (line-earth) | ≤ 100 ns |
Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 4 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 3 MHz |
Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 700 kHz |
Capacity (line-line) | typ. 1 nF |
Capacity (line-earth) | typ. 5 pF |
Output voltage limitation at 1 kV/µs (wire-wire) | ≤ 360 V |
Residual voltage at In (line-line) | ≤ 500 V |
Residual voltage at In (line-earth) | ≤ 30 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 35 V |
Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 35 V |
Impulse durability (line-line) | C2 - 2 kV / 1 kA |
C3 - 25 A | |
Impulse durability (line-earth) | C2 - 4 kV / 2 kA |
C3 - 100 A | |
D1 - 500 A | |
Alternating current carrying capacity (line-line) | 250 mA - 1 s |
Alternating current carrying capacity (line-earth) | 10 A - 1 s |
Pulse reset time (line-line) | ≤ 15 ms |
Connection method | RJ12-/TAE 6 |
---|---|
Connection method IN | RJ12 female connector |
Connection method OUT | TAE 6 socket |
Connection method | Via protective contact plug |
---|
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 |
eCl@ss 10.0.1 | 27130810 |
---|---|
eCl@ss 11.0 | 27130810 |
eCl@ss 4.0 | 27130800 |
eCl@ss 4.1 | 27130800 |
eCl@ss 5.0 | 27130800 |
eCl@ss 5.1 | 27130800 |
eCl@ss 6.0 | 27130800 |
eCl@ss 7.0 | 27130810 |
eCl@ss 8.0 | 27130810 |
eCl@ss 9.0 | 27130810 |
ETIM 2.0 | EC001473 |
---|---|
ETIM 3.0 | EC001473 |
ETIM 4.0 | EC001473 |
ETIM 5.0 | EC001473 |
ETIM 6.0 | EC001473 |
ETIM 7.0 | EC001473 |
UNSPSC 6.01 | 30212010 |
---|---|
UNSPSC 7.0901 | 39121610 |
UNSPSC 11 | 39121610 |
UNSPSC 12.01 | 39121610 |
UNSPSC 13.2 | 39121620 |
UNSPSC 18.0 | 39121620 |
UNSPSC 19.0 | 39121620 |
UNSPSC 20.0 | 39121620 |
UNSPSC 21.0 | 39121620 |