Bus coupler - AXL F BK ETH XC - 2701949

The figure shows the standard item

Axioline F XC, Bus coupler, Modbus/TCP(UDP), RJ45 jack, Extreme conditions version, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Connection diagram  

Connection diagram

Block diagram  

Block diagram
Internal wiring of the terminal points



Dimensional drawing  

Dimensional drawing

Back to top

Dimensions

Dimensional drawing
Width 45 mm
Height 126.1 mm
Depth 74 mm
Note on dimensions The depth is valid when a TH 35-7,5 DIN rail is used (according to EN 60715).
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 60 °C (Standard and applications with UL approval; mounting position: wall mounting on horizontal DIN rail)
-25 °C ... 55 °C (Standard applications and applications with UL approval; mounting position: anywhere)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Back to top

Connection data

Designation Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Applications with UL approval: only use copper conductors.
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Back to top

General

Mounting type DIN rail mounting
Color traffic grey A RAL 7042
Net weight 177 g
Note on weight specifications with connector and bus base module
Mounting type DIN rail mounting
Mounting position any (observe temperature derating)
Back to top

Interfaces

Designation Modbus/TCP (UDP)
No. of channels 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Transmission speed 10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually))
Transmission physics Ethernet in RJ45 twisted pair
Designation Axioline F local bus
No. of channels 1
Connection method Bus base module
Transmission speed 100 Mbps
Designation Service
Connection method USB type C (as of HW 02)
Micro USB type B (up to HW 01)
Back to top

Network/bus system

Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63
Back to top

Axioline potentials

Designation Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption max. 583 mA (2.0 A at UBus, UL = 24 V, up to HW 01)
max. 670 mA (2.5 A at UBus, UL = 24 V, HW 02 or later)
Power consumption max. 14 W (2.0 A at UBus, UL = 24 V, up to HW 01)
max. 16 W (2.5 A at UBus, UL = 24 V, HW 02 or later)
Type of protection Surge protection
Reverse polarity protection
Designation Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Power supply unit max. 2 A (up to HW 01)
max. 2.5 A (as of HW 02)
Back to top

Electrical isolation

Test section Ethernet interface 1 / Ethernet interface 2 1500 V AC 50 Hz 1 min.
Ethernet interface 1 / 24 V communications voltage (UL) feed-in 1500 V AC 50 Hz 1 min.
Ethernet interface 2 / 24 V communications voltage (UL) feed-in 1500 V AC 50 Hz 1 min.
Ethernet interface 1 / functional ground 1500 V AC 50 Hz 1 min.
Ethernet interface 2 / functional ground 1500 V AC 50 Hz 1 min.
24 V communications voltage (UL) feed-in / functional ground 500 V AC 50 Hz 1 min.
Back to top

Standards and Regulations

Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Protection class III (IEC 61140, EN 61140, VDE 0140-1)
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242608
eCl@ss 5.1 27242600
eCl@ss 6.0 27242600
eCl@ss 7.0 27242608
eCl@ss 8.0 27242608
eCl@ss 9.0 27242608
Back to top

ETIM

ETIM 5.0 EC001604
ETIM 6.0 EC001604
ETIM 7.0 EC001604
Back to top

UNSPSC

UNSPSC 13.2 32151602
UNSPSC 18.0 32151602
UNSPSC 19.0 32151602
UNSPSC 20.0 32151602
UNSPSC 21.0 32151602
Back to top