Controller - AXC 3050 - 2700989

Axiocontrol for the direct control of Axioline F I/Os. With 3 Ethernet interfaces for the additional connection of distributed I/Os via PROFINET, Modbus TCP or TCP/IP. Programming according to IEC 61131-3. Includes connector plug and marking field.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width 100 mm
Height 125.9 mm
Depth 74 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C (up to 2000 m above sea level)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Ambient temperature (assembly) -5 °C ... 60 °C
Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 58 kPa ... 106 kPa (up to 4500 m above mean sea level)
Shock 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation) 5g
Back to top

Control system

Engineering tool PC WORX
Programming languages supported Programming in acc. with IEC 61131-3
Diagnostics tool DIAG+
Configuration tool Config+ Version 1.01 or later
Back to top

IEC 61131 runtime system

Engineering tool PC WORX
Program memory 4 Mbyte
Mass storage 8 Mbyte
Retentive mass storage 128 kByte
Number of control tasks 16
Realtime clock Yes
Back to top

Fieldbus function

Amount of process data max. 8192 Bit (per station)
max. 4096 Bit (Axioline F local bus (input))
max. 4096 Bit (Axioline F local bus (output))
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63 (observe current consumption)
Program memory 4 Mbyte
Back to top

Data interfaces

Interface Axioline F local bus
Number 1
Connection method Bus base module
Transmission speed 100 Mbps
Interface Ethernet
Number 3
Connection method RJ45 jack
Transmission speed 10/100 Mbps
Interface Parameterization/operation/diagnostics
Number 1
Connection method Micro USB type B
Transmission speed max. 115.2 kbps
Interface Service
Number 1
Connection method USB type A, socket
Back to top

PROFINET

Device function PROFINET controller, PROFINET device
Specification Version 2.3
Update rate max. of 256 devices
Back to top

Direct I/Os

Input name Counter input for 24 V signals
Number of inputs max. 2 (via any digital inputs of the Axioline F modules)
Input frequency max. 100 kHz (with AXL F DI16/1 HS 1H module)
Back to top

Power supply

Typical current consumption typ. 408 mA (without I/Os and UL = 24 V)
Max. current consumption max. 976 mA (with 2 A at UBus for the I/Os and UL = 24 V)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC
Residual ripple ± 5 %
Power dissipation max. 9.8 W
Back to top

Mechanical design

Weight 444 g
Diagnostics display No
Controller redundancy yes
Note on controller redundancy applicative system redundancy possible
Safety function No
Back to top

General data

Processor Intel® Atom™ E660 1x 1.3 GHz
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Interference emission Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class A
Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Vibration (storage/transport) 5g
Shock 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation) 5g
Shock (operation) 10g (Bump endurance test according to DIN EN 60068-2-27)
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242207
eCl@ss 4.0 27240600
eCl@ss 4.1 27240600
eCl@ss 5.0 27242700
eCl@ss 5.1 27242700
eCl@ss 6.0 27242200
eCl@ss 7.0 27242207
eCl@ss 8.0 27242207
eCl@ss 9.0 27242207
Back to top

ETIM

ETIM 3.0 EC001045
ETIM 4.0 EC001435
ETIM 5.0 EC000236
ETIM 6.0 EC000236
ETIM 7.0 EC000236
Back to top

UNSPSC

UNSPSC 6.01 81111810
UNSPSC 7.0901 81111810
UNSPSC 11 81111810
UNSPSC 12.01 81111810
UNSPSC 13.2 39122114
UNSPSC 18.0 39122114
UNSPSC 19.0 39122114
UNSPSC 20.0 39122114
UNSPSC 21.0 39122114
Back to top

PHOENIX CONTACT

586 Fulling Mill Road
Middletown, PA 17057
(800) 888-7388

  • Create PDF
  • Send by Email
  • Feedback