Inline terminal - IB IL 24 DO8/HD-PAC - 2700172

Inline, Digital output terminal, Digital outputs: 8, 24 V DC, 500 mA, connection method: 1-wire, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Connection diagram  

Connection diagram

Block diagram  

Block diagram
Internal wiring of the terminal points



Dimensional drawing  

Dimensional drawing

Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Use in potentially explosive areas is not permitted in China.
Back to top

Dimensions

Dimensional drawing
Width 12.2 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Back to top

General

Mounting type DIN rail
Color green
Net weight 60 g
Note on weight specifications with connector
Diagnostics messages Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Back to top

Interfaces

Designation Inline local bus
No. of channels 2
Connection method Inline data jumper
Transmission speed 500 kbps
Back to top

Inline potentials

Designation Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current consumption max. 45 mA
Designation Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption max. 4 A
Power consumption max. 0.62 W
Current consumption 0 A
Back to top

Digital outputs

Output name Digital outputs
Connection method Spring-cage connection
Connection technology 1-wire
Number of outputs 8
Protective circuit Overload protection, short-circuit protection of outputs Zener diode in output chip
Output voltage 24 V (US - 1 V)
Nominal output voltage 24 V DC
Nominal load, inductive 12 VA (1.2 H, 50 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 W (48 Ω)
Output voltage when switched off max. 1 V
Output current when switched off max. 300 µA
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Reverse voltage resistance to short pulses Reverse voltage proof
Back to top

Electrical isolation

Test section 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic)/functional ground 500 V AC 50 Hz 1 min.
24 V supply (I/O)/functional ground 500 V AC 50 Hz 1 min.
Back to top

Standards and Regulations

Protection class III (IEC 61140, EN 61140, VDE 0140-1)
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242604
eCl@ss 4.0 27240400
eCl@ss 4.1 27240400
eCl@ss 5.0 27242200
eCl@ss 5.1 27242600
eCl@ss 6.0 27242600
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
eCl@ss 9.0 27242604
Back to top

ETIM

ETIM 2.0 EC001433
ETIM 3.0 EC001599
ETIM 4.0 EC001599
ETIM 5.0 EC001599
ETIM 6.0 EC001599
ETIM 7.0 EC001599
Back to top

UNSPSC

UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 39121311
UNSPSC 12.01 39121311
UNSPSC 13.2 32151602
UNSPSC 18.0 32151602
UNSPSC 19.0 32151602
UNSPSC 20.0 32151602
UNSPSC 21.0 32151602
Back to top