Inline terminal - IB IL SGI 1/CAL - 2700064

Inline analog strain gauge input terminal, without accessories, evaluating electronics with EC type approval

Price:

Overview

Technical data

Accessories

Downloads

Drawings



Connection diagram  

Connection diagram
Connection of strain gauges in 6-wire technology (calibration set)

Dimensional drawing  

Dimensional drawing



Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Dimensional drawing
Width 48.8 mm
Height 120 mm
Depth 71.5 mm
Note on dimensions Dimensions with covering hood
Back to top

Ambient conditions

Ambient temperature (operation) -25 °C ... 55 °C (Type approval according to DIN EN 45501 and OIML R76: -10°C ... 40°C)
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Back to top

General

Mounting type DIN rail
Color green
Net weight 160 g
Operating mode Process data operation with 2 words, PCP with 2 words
Diagnostics messages Failure of the power supply at UANA Error message in the process data
Failure of or insufficient communications power UL I/O error message sent to the bus coupler
I/O error Error message in the process data
User error Error message in the process data
Back to top

Interfaces

Designation Inline local bus
Connection method Inline data jumper
Transmission speed 500 kbps
Back to top

Serial interface

Designation RS-485
Network Yes
Addressing Address 0 = Broadcast, alternating display of measured gross/net value and measured tare value
Address 1 = Measured gross/net value
Address 2 = Measured tare value
Address 3 ... 9 = reserved
Termination resistor 120 Ω
Transmission protocol STX/ETX
Back to top

Inline potentials

Designation Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current consumption typ. 80 mA
max. 100 mA
Designation Supply of analog modules (UANA)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption typ. 12 mA (For a typical load of 350 Ω and display)
43 mA (for a maximum load of 55 Ω and display)
max. 50 mA
Power consumption typ. 1 W (Device in nominal operation)
Back to top

Contacts

Description Lock of parameters
Quantity 1 (PSa - PSb)
Logic PSa - PSb connected = Parameter locked
Typical response time < 100 ms
Back to top

Analog inputs

Description of the input Input channel for strain gauge
Number of inputs 1
Connection technology 6-wire, twisted pair shielded cable
Bridge difference Ud Measuring range specified by selecting the characteristic
Bridge voltage U0 5 V
Characteristics ±1 mV/V, ±2 mV/V, ±3 mV/V, ±3.33 mV/V, ±4 mV/V, ±5 mV/V
Measured value representation Process data: status bits and measured value including decimal places of the gross/net display
Process data update typ. 100 ms
Back to top

Analog outputs

Type of protection Short-circuit protection of the voltage outputs
Protective circuit/component Yes, at least 1 minute through temperature monitoring
Output description Voltage output
Number of outputs 1
Impedance > 55 Ω
Output voltage typ. 5 V ±2 %
max. 5 V ±5 %
Output current max. 90 mA
Maximum output current max. 90 mA
Back to top

Electrical isolation

Test section Logic/analog I/O (digital isolator) 500 V AC 50 Hz 1 min.
24 V supply (UANA)/analog I/O (DC/DC converter) 500 V AC 50 Hz 1 min.
RS-485/analog I/O (isolating distance) 500 V AC 50 Hz 1 min.
Contacts PSa - PSb/analog I/O (isolating distance) 500 V AC 50 Hz 1 min.
Functional ground/analog I/O (isolating distance) 500 V AC 50 Hz 1 min.
Logic/24 V supply (UANA) (DC/DC converter) 500 V AC 50 Hz 1 min.
RS-485/24 V supply (UANA) (DC/DC converter) 500 V AC 50 Hz 1 min.
Functional ground/24 V supply (UANA) (isolating distance) 500 V AC 50 Hz 1 min.
Logic/RS-485 (digital isolator) 500 V AC 50 Hz 1 min.
Functional ground/RS-485 (isolating distance) 500 V AC 50 Hz 1 min.
Logic/contacts PSa - PSb (optocoupler) 500 V AC 50 Hz 1 min.
Functional ground/contacts PSa - PSb (isolating distance) 500 V AC 50 Hz 1 min.
Logic/functional ground (isolating distance) 500 V AC 50 Hz 1 min.
Back to top

Standards and Regulations

Protection class III (IEC 61140, EN 61140, VDE 0140-1)
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27240405
eCl@ss 4.1 27240405
eCl@ss 5.0 27242201
eCl@ss 5.1 27242600
eCl@ss 6.0 27242600
eCl@ss 7.0 27242601
eCl@ss 8.0 27242601
eCl@ss 9.0 27242601
Back to top

ETIM

ETIM 3.0 EC001599
ETIM 4.0 EC001599
ETIM 5.0 EC001596
ETIM 6.0 EC001596
Back to top

UNSPSC

UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172015
UNSPSC 12.01 43201404
UNSPSC 13.2 32151602
UNSPSC 19.0 32151602
Back to top

PHOENIX CONTACT

586 Fulling Mill Road
Middletown, PA 17057
(800) 888-7388

Service