Controller - AXC F 2152 - 2404267

PLCnext Control for the direct control of Axioline F I/Os. With two Ethernet interfaces. Complete with connector and bus base module.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width 45 mm
Height 126.93 mm
Depth 75 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 60 °C up to 2000 m above mean sea level (observe derating)
-25 °C ... 55 °C up to 3000 m above mean sea level (observe derating)
≤ 55 °C (with max. 1 A on UBus)
> 55 °C ... 60 °C (only in conjunction with an Axioline F power module AXL F PWR 1H (order number 2688297))
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 58 kPa ... 106 kPa (up to 4500 m above mean sea level)
Shock 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation) 5g
Back to top

Control system

Engineering tool PLCnext Engineer
Eclipse
Programming languages supported Programming in acc. with IEC 61131-3
C++
C#
Java
Manufacturer-specific
Supports cloud computing yes
Cloud platform Proficloud
Back to top

General data

Processor Arm® Cortex®-A9 2x 800 MHz
Operating system Linux
RAM 512 Mbyte DDR3 SDRAM
Back to top

IEC 61131 runtime system

Engineering tool PLCnext Engineer
Eclipse
Program memory 8 Mbyte
Mass storage 16 Mbyte
Retentive mass storage 48 kByte (NVRAM)
Realtime clock Yes
Back to top

Fieldbus function

Designation System limits of the controller
Amount of process data max. 8192 Bit (per station)
max. 4096 Bit (Input)
max. 4096 Bit (Output)
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63 (observe current consumption)
Program memory 8 Mbyte
Back to top

Data interfaces

Interface Axioline F local bus
Number 1
Connection method Bus base module
Transmission speed 100 Mbps
Interface Ethernet
Number 2
Connection method RJ45 jack
Transmission speed 10/100 Mbps (full duplex)
Protocols supported HTTP
HTTPS
SFTP
SNTP
SNMP
IPsec
syslog
OPC UA
Back to top

PROFINET

Device function PROFINET controller, PROFINET device
Specification Version 2.3
Update rate min. 1 ms (4 devices)
min. 16 ms (64 devices)
Back to top

Power supply

Typical current consumption 200 mA
Max. current consumption 442 mA
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC
Residual ripple ± 5 %
Power dissipation max. 10.6 W
Back to top

Mechanical design

Weight 225.6 g
Diagnostics display No
Controller redundancy No
Safety function No
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Interference emission Noise emission test as per EN 61000-6-4 Class A
Immunity to surge Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), fieldbus cable shield: ±1 kV
Immunity to burst Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion B, 2 kV
Immunity to EF Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity to ESD Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity to conducted interference Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Vibration (storage/transport) 5g
Shock 30g, 11 ms period, half-sine shock pulse, according to IEC 60068-2-27
Vibration (operation) 5g
Shock (operation) 10g (Bump endurance test according to DIN EN 60068-2-27)
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242207
eCl@ss 4.0 27240602
eCl@ss 4.1 27240602
eCl@ss 5.0 27242700
eCl@ss 5.1 27242700
eCl@ss 6.0 27242200
eCl@ss 7.0 27242207
eCl@ss 8.0 27242207
eCl@ss 9.0 27242207
Back to top

ETIM

ETIM 3.0 EC001045
ETIM 4.0 EC001435
ETIM 5.0 EC000236
ETIM 6.0 EC000236
ETIM 7.0 EC000236
Back to top

PHOENIX CONTACT

586 Fulling Mill Road
Middletown, PA 17057
(800) 888-7388

  • Create PDF
  • Send by Email
  • Feedback