Conductor connectors - QPD C4X2,5/1X9-14 GY - 1424025

Conductor connectors, QUICKON connection, number of positions: 4, 1 mm² ... 2.5 mm², 690 V, 20 A, gray, with one QUICKON nut, cable diameter range: 9 mm ... 14 mm, QUICKON fast connection

Price:

Overview

Technical data

Accessories

Downloads

Drawings



Diagram  

Diagram
Derating diagram

Dimensional drawing  

Dimensional drawing
Dimensional drawing



Back to top

General

Type QPD 4x2,5
Color gray
Locking type Screw locking
Connection method QUICKON connection
IDC connection
Number of positions 4
Note number of positions 4
Tightening torque, union nut 7 Nm
Conductor cross section flexible min. 1 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section solid min. 1 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 14
Back to top

Cabel

Structure of individual litz in acc. with VDE 0295 / smallest wire diameter VDE 0295 class 1 to 6/min. 0.15 mm
Wire insulation material PVC/PE/TPE/rubber
Wire diameter including insulation 2 mm ... 3.6 mm
External cable diameter 9 mm ... 14 mm
Position marking 1, 2, 3, 4
Back to top

Ambient conditions

Degree of protection IP66
IP68 (2 m / 24 h)
IP69K
Ambient temperature (operation) -40 °C ... 100 °C
Ambient temperature (storage/transport) -40 °C ... 100 °C
Temperature when conductor connected -5 °C ... 50 °C
Back to top

Electrical characteristics

Nominal current IN 20 A
Nominal voltage UN 690 V AC
690 V DC
Rated current 20 A
rated voltage (III/3) 690 V
rated voltage (III/2) 690 V
rated voltage (II/2) 1000 V
Rated surge voltage (III/3) 6 kV
Rated surge voltage (III/2) 6 kV
Rated surge voltage (II/2) 6 kV
Back to top

Mechanical characteristics

QUICKON connectability max. 10
Insertion/withdrawal cycles >= 50 (QUICKON connections max. 10)
Category of shock impact IK07
Back to top

Material data

Contact material Cu
Contact surface material silver-plated
Contact carrier material PA
Insulating material PA
Flammability rating according to UL 94 V0
Overvoltage category III
Degree of pollution 3
Back to top

Standards and Regulations

Category of shock impact IK07
Halogen-free yes
Flammability rating according to UL 94 V0
Back to top

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27440605
eCl@ss 11.0 27440605
eCl@ss 7.0 27440605
eCl@ss 9.0 27440605
Back to top

ETIM

ETIM 6.0 EC002560
ETIM 7.0 EC002560
Back to top

PHOENIX CONTACT

586 Fulling Mill Road
Middletown, PA 17057
(800) 888-7388