Type 2 surge arrester - BLT-T2-1S-305-UT - 1078433

Type 2 surge arrester for universal mounting in lights, cable connection boxes, installation boxes, sill-type trunking, underfloor installations or direct installation in the end device. Specifically for insulation class I with optical fault indication. Installation in branch or through wiring. Version: 230 V AC

Price:

Overview

Technical data

Approvals

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Circuit diagram  

Circuit diagram



Back to top

Dimensions

Height 56 mm
Width 36.5 mm
Depth 34 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (5 ... 500 Hz / 2.5 h / X, Y, Z)
Back to top

General

IEC test classification II / III
EN type T2 / T3
IEC power supply system TN-S
TT
SPD failure behavior OCM
Accessibility Accessible
Installation location of the disconnect device Internal
Mode of protection L-N
L-PE
N-PE
Mounting type 4 mm screw
Color light grey RAL 7035
Housing material PA 6.6
Degree of pollution 2
Distance between live and grounded parts 3 mm
Flammability rating according to UL 94 V-0
Protection class I
Back to top

Protective circuit

Nominal voltage UN 100 V AC ... 230 V AC (TN-S)
100 V AC ... 230 V AC (TT)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N) 305 V AC
Maximum continuous operating voltage UC (L-PE) 265 V AC
Maximum continuous voltage UC (N-PE) 265 V AC
Rated load current IL 16 A
Residual current IPE ≤ 5 µA
Nominal discharge current In (8/20) µs (L-N) 5 kA
Nominal discharge current In (8/20) µs (L-PE) 5 kA
Nominal discharge current In (8/20) µs (N-PE) 10 kA
Maximum discharge current Imax (8/20) µs (L-N) 10 kA
Maximum discharge current Imax (8/20) µs (L-PE) 10 kA
Maximum discharge current Imax (8/20) µs (N-PE) 20 kA
Combination wave UOC (L-N) 10 kV
Combination wave UOC (L-PE) 10 kV
Combination wave UOC (N-PE) 20 kV
Total discharge current Itotal (8/20) µs 20 kA
Follow current interrupt rating Ifi (N-PE) 100 A ()
Short-circuit current rating ISCCR 10 kA (6 A gG backup fuse)
3 kA (16 A MCB B/C backup fuse)
Voltage protection level Up (L-N) ≤ 1.3 kV
Voltage protection level Up (L-PE) ≤ 1.5 kV
Voltage protection level Up (N-PE) ≤ 1.5 kV
TOV behavior at UT (L-N) 336 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE) 440 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE) 1200 V AC (200 ms / safe failure mode)
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PE) ≤ 100 ns
Response time tA (N-PE) ≤ 100 ns
Max. backup fuse with V-type through wiring 16 A (MCB B/C)
Max. backup fuse with branch wiring 16 A (MCB B/C)
Back to top

Connection data

Connection method Screw terminal blocks
Screw thread M3
Tightening torque 0.6 Nm
Stripping length 8 mm
2 conductors with same cross section, stranded min. 0.2 mm²
2 conductors with same cross section, stranded max. 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
2 conductors with same cross section, solid min. 0.2 mm²
2 conductors with same cross section, solid max. 1.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Back to top

Standards and Regulations

Standards/regulations IEC 61643-11 2011
EN 61643-11 2012
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27130805
eCl@ss 11.0 27130805
eCl@ss 8.0 27130805
eCl@ss 9.0 27130805