Temperature measuring transducer - MACX MCR-EX-T-UI-UP-SP - 2924689

Programmable Ex-i temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer in 2-, 3-, or 4-wire technology, thermocouples, electrical isolation, wide-range power supply, Push-in connection, SIL, PL.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Pictogram  

Pictogram



Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width 17.5 mm
Height 99 mm
Depth 114.5 mm
Back to top

Ambient conditions

Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) typ. 5 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 5g, accordance to IEC 60068-2-6
Back to top

Input data

Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -250 °C ... 2500 °C (Range depending on the sensor type)
Input signal range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Input signal range -1000 mV ... 1000 mV
Back to top

Output data

Configurable/programmable Yes
Max. voltage output signal ± 11 V
Current output signal 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal 22 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output ≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable
Output name Switching output
Configurable/programmable no
Contact type 1 PDT
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 30 V AC (30 V DC)
Maximum inrush current 0.5 A (30 V AC)
1 A (30 V DC)
Mechanical service life 1x 105 cycles
Back to top

Power supply

Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Typical current consumption < 50 mA (24 V DC)
Power consumption < 1.5 W
Back to top

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Back to top

General

Maximum temperature coefficient 0.01 %/K
Step response (0–99%) typ. 1000 ms (With SIL)
typ. 700 ms (Without SIL)
Status display Green LED (supply voltage, PWR)
Red LED, flashing (line, sensor error, ERR)
Red LED (module error, ERR)
Yellow LED (switching output)
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Electromagnetic compatibility Conformance with EMC directive
Interference emission EN 61000-6-4
Housing material PA 6.6-FR
Color gray
Designation Input/output/power supply
Electrical isolation 2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/switching output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output/supply
Electrical isolation 300 Vrms (Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
Conformance CE-compliant
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 G Ex nA nC ic IIC T4 Gc X
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
SIL 2
Back to top

Safety data

Max. internal inductance Li negligible
Max. internal capacitance Ci 44 nF
Max. output voltage Uo 6 V
Max. output current Io 7.4 mA
Max. output power Po 11 mW
Group IIC
Max. external inductivity Lo 100 mH
Max. external capacity Co 1.3 µF
Group IIC
Max. external inductivity Lo 10 mH
Max. external capacity Co 1.7 µF
Group IIC
Max. external inductivity Lo 1 mH
Max. external capacity Co 2.6 µF
Group IIB
Max. external inductivity Lo 100 mH
Max. external capacity Co 6.8 µF
Group IIB
Max. external inductivity Lo 10 mH
Max. external capacity Co 9.2 µF
Group IIB
Max. external inductivity Lo 1 mH
Max. external capacity Co 15 µF
Safety-related maximum voltage Um 253 V AC/DC
Back to top

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 2 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 2 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 2 %
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
EN 61000-4-4
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Electrical isolation 4-way, between input/output/power supply/switching output
Flammability rating according to UL 94 V0
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 5g, accordance to IEC 60068-2-6
Conformance CE-compliant
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 G Ex nA nC ic IIC T4 Gc X
IECEx [Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA nC ic IIC T4 Gc X
UL, USA/Canada UL 508 Listed
DNV GL-Temperature B
DNV GL-Humidity B
DNV GL-Vibration A
DNV GL-EMC A
DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
Group IIC
IIC
IIC
IIB
IIB
IIB
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27210120
eCl@ss 4.1 27210120
eCl@ss 5.0 27210120
eCl@ss 5.1 27200200
eCl@ss 6.0 27200200
eCl@ss 7.0 27200206
eCl@ss 8.0 27200206
eCl@ss 9.0 27210129
Back to top

ETIM

ETIM 2.0 EC001446
ETIM 3.0 EC001446
ETIM 4.0 EC001446
ETIM 5.0 EC001446
ETIM 6.0 EC002919
ETIM 7.0 EC002919
Back to top

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 41112105
Back to top

PHOENIX CONTACT

586 Fulling Mill Road
Middletown, PA 17057
(800) 888-7388

  • Create PDF
  • Send by Email
  • Feedback