Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -40 °C ... 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Degree of protection | IP20 (not assessed by UL) |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Description of the input | Current input (sensor circuit) |
---|---|
Number of inputs | 1 |
Current input signal | 4 mA ... 20 mA (Power supply and signal duplicator mode) |
0 mA ... 20 mA (Signal duplicator mode) | |
Input resistance current input | 90 Ω (+1.6 V) |
Transmitter supply voltage | > 19.5 V |
Output name | Current output |
---|---|
Number of outputs | 2 |
Current output signal | 4 mA ... 20 mA (Power supply and signal duplicator mode) |
0 mA ... 20 mA (Signal duplicator mode) | |
Max. output current | 25 mA |
Load/output load current output | ≤ 500 Ω (per channel) |
Ripple | < 20 mVPP (at 500 Ω) |
Transmission Behavior | 1:1 to input signal |
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Typical current consumption | 40 mA (For 24 V DC and in signal duplicator mode) |
65 mA (For 24 V DC and in power supply duplicator mode) | |
75 mA (For 12 V DC and in signal duplicator mode) | |
130 mA (For 12 V DC and in power supply duplicator mode) | |
Power consumption | 1.6 W (at IOUT = 20 mA, 500 Ω load) |
Connection method | Screw connection |
---|---|
Stripping length | 10 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 1.5 mm² (with ferrule) |
0.14 mm² ... 2.5 mm² (without ferrule) | |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 (flexible) |
Torque | 0.5 Nm ... 0.6 Nm |
No. of channels | 2 |
---|---|
Maximum transmission error | 0.05 % (of final value) |
Maximum temperature coefficient | 0.0075 %/K |
Limit frequency (3 dB) | > 1 kHz (typ.) |
Step response (10-90%) | < 400 µs (typ.) |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 300 V |
Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | gray |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Designation | CE |
---|---|
Identification | CE-compliant |
Designation | ATEX |
Identification | II 3 G Ex ec ic IIC T4 Gc |
Certificate | BVS 19 ATEX E 047 X |
Designation | IECEx |
Identification | Ex ec ic IIC T4 Gc |
Certificate | IECEx BVS 19.0041X |
Designation | UL, USA/Canada |
Identification | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T5 | |
Class I, Zone 2, Group IIC T5 | |
Designation | Shipbuilding approval |
Certificate | DNV GL TAA000021E |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 10.0.1 | 27210120 |
---|---|
eCl@ss 11.0 | 27210120 |
eCl@ss 4.0 | 27210100 |
eCl@ss 4.1 | 27210100 |
eCl@ss 5.0 | 27210100 |
eCl@ss 5.1 | 27210100 |
eCl@ss 6.0 | 27210100 |
eCl@ss 7.0 | 27210120 |
eCl@ss 8.0 | 27210120 |
eCl@ss 9.0 | 27210120 |
"$pageName" on