Type 1 surge protection device - VAL-US-120/65/2+0-FM - 2910357

Surge protective device, two channel with remote indicator contact for 120/240 V split phase AC, 3-wire.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Dimensional drawing  

Dimensional drawing

Circuit diagram  

Circuit diagram



Back to top

Dimensions

Height 96.8 mm
Width 35.6 mm
Depth 77.5 mm
Horizontal pitch 2 Div.
Back to top

Ambient conditions

Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Back to top

General

IEC test classification I / II
T1 / T2
EN type T1 / T2
IEC power supply system TN-C
Mode of protection L-PEN
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 2
Surge protection fault message Optical, remote indicator contact
Back to top

Protective circuit

Nominal voltage UN 120/240 V AC (TN-C)
Nominal frequency fN 50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-PEN) 175 V AC
Rated load current IL 80 A
Residual current IPE ≤ 0.8 mA
Nominal discharge current In (8/20) µs 20 kA
Nominal discharge current In (8/20) µs (L-PEN) 12.5 kA
Total discharge current Itotal (10/350) µs 25 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up ≤ 0.8 kV
Residual voltage Ures ≤ 0.8 kV (at In)
≤ 0.75 kV (at 10 kA)
≤ 0.65 kV (at 5 kA)
≤ 0.5 kV (at 3 kA)
TOV behavior at UT 208 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
Response time tA ≤ 25 ns
Max. backup fuse with V-type through wiring 80 A (gG)
Max. backup fuse with branch wiring 160 A (gG)
Back to top

Indicator/remote signaling

Switching function PDT contact
Operating voltage 5 V AC ... 250 V AC
30 V DC
Operating current 5 mA AC ... 1.5 A AC
1 A DC
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Back to top

Connection data

Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
Conductor cross section AWG 15 ... 2
Back to top

UL specifications

SPD Type 1
Maximum continuous operating voltage MCOV (L-L) 350 V AC
Maximum continuous operating voltage MCOV (L-G) 175 V AC
Nom. voltage 120/240 V AC (Split phase)
Mode of protection L-L
L-G
Power distribution system Split phase
Nominal frequency 50/60 Hz
Voltage protection rating VPR (L-L) 1200 V
Voltage protection rating VPR (L-G) 700 V
Nominal discharge current In 20 kA
Maximum Surge Current per Phase 65 kA
Short-circuit current rating (SCCR) 200 kA
Back to top

UL indicator/remote signaling

Operating voltage 125 V AC
Operating current 1 A AC
Tightening torque 2 lbf-in. ... 4 lbf-in.
Conductor cross section AWG 30 ... 14
Back to top

UL connection data

Conductor cross section AWG 10 ... 2
Tightening torque 30 lbf-in.
Back to top

Standards and Regulations

Standards/regulations IEC 61643-11 2011
EN 61643-11 2012
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27130805
eCl@ss 11.0 27130805
eCl@ss 6.0 27130800
eCl@ss 7.0 27130805
eCl@ss 8.0 27130805
eCl@ss 9.0 27130805
Back to top

ETIM

ETIM 5.0 EC000941
ETIM 6.0 EC000941
ETIM 7.0 EC000941
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836