Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|---|
Use in potentially explosive areas is not permitted in China. |
Ambient temperature (operation) | -40 °C ... 85 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Degree of protection | IP20 |
Mounting position | On horizontal DIN rail NS 35 in acc. with EN 60715 |
---|---|
Net weight | 111.7 g |
Color | green |
Conformance | CE-compliant, additionally EN 61326 |
Fieldbus Foundation | FF-846 |
Supply voltage range | 10.5 V DC ... 32 V DC (input on trunk line side) |
---|---|
Max. current consumption | 2 mA (with terminator) |
Conductor cross section flexible max. | 0.20 mm² |
Conductor cross section flexible min. | 2.50 mm² |
Conductor cross section solid max. | 0.20 mm² |
Conductor cross section solid min. | 2.50 mm² |
Max. AWG conductor cross section, flexible | 12 |
Min. AWG conductor cross section, flexible | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section AWG min. | 24 |
Interface 1 | Foundation Fieldbus and PROFIBUS PA Segment |
---|---|
Connection method | Pluggable COMBICON screw connection for each spur |
Termination resistor | 100 Ω, external removable plug included |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Surge protection | Active if voltage exceeds 39 V (typ.) or 41 V (max.) |
Voltage drop trunk line / outputs | ≤ 0.2 V |
Inductance Li | 0 mH (FNICO/FISCO ic) |
Max. output voltage Uo | = Ui |
Input voltage Ui | 17.5 V (FNICO/FISCO ic) |
---|---|
Input current Ii | 1 A (max. T-BUS load current) |
Max. output voltage Uo | = Ui |
ATEX | Sira 14ATEX4017X; II 3G; Ex nA IIC T4 Gc; Ex ic IIC T4, FISCO ic |
IECEx | IECEx SIR 14.0010X; Ex nA IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic |
CSA, USA/Canada |
Class I, Div. 2, Groups A, B, C, D; Ex nA IIC T4 Gc; Ex nL IIC T4, FNICO; Ex ic IIC T4 Gc, FISCO ic Class I, Zone 2; AEx nA IIC T4 Gc; AEx nL IIC T4, FNICO; AEx ic IIC T4 Gc, FISCO ic |
Type of test | Corrosive resistance in acc. to ANSI-ISA 71.04-1985 - Severity level G3 |
---|---|
Designation | Standards/regulations |
Standards/regulations | Ring wave noise immunity in acc. with IEC 61000-4-12 |
Designation | Standards/regulations |
Standards/regulations | Dry heat in acc. with IEC 61131-2 |
Designation | Standards/regulations |
Standards/regulations | Damp heat in acc. with IEC 61131-2 |
Designation | Standards/regulations |
Standards/regulations | Shock and vibration in acc. with EN 61131-2 and EN 50178 |
IEC 61158-2 | |
IEC 60529, IEC 61158-2 | |
NE21 | |
EN 61326, EN 60068-2-27, EN 60068-2-6 | |
FF-846 | |
Shock | 15g, 11 ms |
Vibration (operation) | 1g, 10 Hz ... 150 Hz |
Conformance | CE-compliant, additionally EN 61326 |
Fieldbus Foundation | FF-846 |
ATEX | Sira 14ATEX4017X; II 3G; Ex nA IIC T4 Gc; Ex ic IIC T4, FISCO ic |
IECEx | IECEx SIR 14.0010X; Ex nA IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic |
CSA, USA/Canada |
Class I, Div. 2, Groups A, B, C, D; Ex nA IIC T4 Gc; Ex nL IIC T4, FNICO; Ex ic IIC T4 Gc, FISCO ic Class I, Zone 2; AEx nA IIC T4 Gc; AEx nL IIC T4, FNICO; AEx ic IIC T4 Gc, FISCO ic |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 10.0.1 | 27242608 |
---|---|
eCl@ss 11.0 | 27242608 |
eCl@ss 5.0 | 27259200 |
eCl@ss 5.1 | 27259200 |
eCl@ss 6.0 | 27242600 |
eCl@ss 7.0 | 27242608 |
eCl@ss 8.0 | 27242608 |
eCl@ss 9.0 | 27242608 |
UNSPSC 13.2 | 32151602 |
---|---|
UNSPSC 18.0 | 32151602 |
UNSPSC 19.0 | 32151602 |
UNSPSC 20.0 | 32151602 |
UNSPSC 21.0 | 32151602 |