Surge protection device - TTC-6-1X2-F-M-24DC-PT-I - 2906772

Surge protection with integrated status indicator and knife disconnection for a 2-wire floating signal circuit, e.g., 0(4) ... 20 mA current loop. Indirect grounding via gas-filled surge arrester.

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Diagram  

Diagram

Dimensional drawing  

Dimensional drawing



Pictogram  

Pictogram

Circuit diagram  

Circuit diagram



Back to top

Dimensions

Height 105.8 mm
Width 6.2 mm +0.1 mm
Depth 83.5 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20
Back to top

General

Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, one-piece 
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top

Protective circuit

IEC test classification C1
C2
C3
D1
Nominal voltage UN 24 V DC
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 600 mA (40 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge current In (8/20) µs (line-earth) 5 kA
Nominal discharge current In (8/20) µs (line-signal ground) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-signalground) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 55 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
≤ 1.3 kV (C3 - 25 A)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level Up (line-signalground) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level Up static (line-line) ≤ 50 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-earth) ≤ 900 V (C1 - 1 kV/500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-signalground) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-signalground) ≤ 100 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 940 kHz
Capacity (line-line) typ. 2.2 nF
Resistance per path 1.65 Ω ±20 %
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Impulse durability (line-signalground) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line) ≤ 700 ms
Pulse reset time (line-earth) ≤ 30 ms
Pulse reset time (line-signalground) ≤ 1500 ms
Back to top

Additional technical data

Max. total discharge current I total max (8/20) µs 20 kA (1x)
Back to top

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Back to top

Standards and Regulations

Standards/specifications IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130800
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
eCl@ss 9.0 27130807
Back to top

ETIM

ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
ETIM 6.0 EC000943
ETIM 7.0 EC000943
Back to top

UNSPSC

UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836
+65 6228 4900
  • Create PDF
  • Recommend
  • Feedback