Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|---|
Use in potentially explosive areas is not permitted in China. |
Ambient temperature (operation) | -40 °C ... 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
Degree of protection | IP20 |
Electrical isolation | VCC // PE |
---|---|
Test voltage data interface/data interface | 1 kV (50 Hz, 1 min.) |
Test voltage data interface/power supply | 1 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Net weight | 640 g |
Housing material | Metal |
Color | silver |
MTTF | 634 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
295 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
125 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | |
Degree of pollution | 2 |
Supply voltage range | 11 V DC ... 36 V DC (via pluggable COMBICON screw terminal block) |
---|---|
Max. current consumption | < 1.8 A (at 11 V DC (incl. 3 x 125 mA for the outputs)) |
Typical current consumption | < 320 mA (24 V DC) |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 2.5 mm² |
Conductor cross section flexible max. | 2.50 mm² |
Conductor cross section flexible min. | 0.20 mm² |
Conductor cross section solid max. | 2.50 mm² |
Conductor cross section solid min. | 0.20 mm² |
Conductor cross section AWG max. | 14 |
Conductor cross section AWG min. | 24 |
Stripping length | 7 mm |
Interface 1 | Ethernet interface, 10/100Base-T(X) in accordance with IEEE 802.3 |
---|---|
Interface | Ethernet |
No. of ports | 4 |
Connection method | RJ45 |
Transmission length | 100 m (shielded twisted pair) |
Protocols supported | TCP/IP, UDP/IP, FTP, HTTP |
Auxiliary protocols | ARP, DHCP, PING (ICMP), SNMP V1, SMTP |
Basic functions | Router with simplified 2-click firewall and VPN for 2 tunnels (fixed), metal housing, slot for any SD memory card |
Interface 2 | V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN 66259-1 |
Interface | RS-232 |
Connection method | D-SUB 9 plug |
File format/coding | UART/NRZ: 8 Data, 1/2 Stop, None/Even/Odd Parity |
Transmission length | 15 m |
Data flow control/protocols | Software handshake, Xon/Xoff or hardware handshake RTS/CTS |
Serial transmission speed | 9.6; 19.2; 38.4; 57.6; 115.2 kbps |
Interface description | GSM / GPRS / EDGE / UMTS / CDMA2000 |
---|---|
Frequency range | 800 MHz (UMTS/HSPA B6) |
850 MHz (UMTS/HSPA B5) | |
900 MHz (UMTS/HSPA B8) | |
1900 MHz (UMTS/HSPA B2) | |
2100 MHz (UMTS/HSPA B1) | |
800 MHz (CDMA2000 EV-DO) | |
1900 MHz (CDMA2000 EV-DO) | |
850 MHz (2 W (EGSM)) | |
900 MHz (2 W (EGSM)) | |
1800 MHz (1 W (EGSM)) | |
1900 MHz (1 W (EGSM)) | |
Data rate | ≤ 14.4 Mbps (HSDPA) |
≤ 5.7 Mbps (HSUPA) | |
≤ 3.1 Mbps (DL CDMA2000) | |
≤ 1.8 Mbps (UL CDMA2000) | |
Antenna | 50 Ω impedance SMA antenna socket |
SIM interface 1 | 1.8 volt, 3 volt |
SIM interface 2 | 1.8 volt, 3 volt |
GPRS | Class 12, Class B |
CS1 ... CS4 | |
EDGE | Multislot Class 12 |
UMTS | HSPA 3GPP R6 |
Network function | 4 time slots for receiving data, 4 time slots for transmitting data. The PIN is saved in the modem. After a voltage interruption, there is automatic redialing into the network. Integrated TCP/IP stack, firewall and VPN support, independent connection establishment. |
Network check | LED bar graph to display receive quality |
Protocols supported | GPS (Global Positioning System), GLONASS |
Web-based management | yes |
---|---|
Management | Web-based management, SNMP |
Number of VPN tunnels | 2 (Fixed, Ipsec (IETF standard)) |
Security functions | Supported Supported Supported DES, 3DES, AES-128, -192, -256 ESP tunnel / ESP transport Supported Supported X.509v3 certificates with RSA or PSK MD5, SHA-1 Quick mode, Main mode, PFS RFC 3706 Incoming or outgoing traffic Standard routing, NAT, 1:1-NAT, port forwarding |
Output name | Digital output |
---|---|
Number of outputs | 3 |
Voltage output signal | 10 V DC ... 30 V DC (depending on the operating voltage) |
Current output signal | ≤ 125 mA (Short-circuit-proof) |
Description of the input | Digital input |
---|---|
Number of inputs | 3 |
Voltage input signal | 10 V DC ... 30 V DC |
Current input signal | 5 mA |
Designation | CE |
---|---|
Identification | CE-compliant |
Designation | UL, USA/Canada |
Identification | Class I, Div. 2, Groups A, B, C, D |
Certificate | E357918 |
Designation | UL, USA |
Identification | Class I, Zone 2, AEx nA IIC T4 |
Designation | UL, Canada |
Identification | Class I, Zone 2, Ex nA IIC T4 Gc X |
Designation | Corrosive gas test |
Identification | ISA-S71.04-1985 G3 Harsh Group A |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Type of test | Free fall in acc. with IEC 60068-2-32 |
Test result | 1 m |
Type of test | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 |
Test result | 5g, 10...150 Hz, 2.5 h, in XYZ direction |
Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result | Operation: 15g, 11 ms period, half-sine shock pulse |
Type of test | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 |
Test result | Storage: 30g, 11 ms period, half-sine shock pulse |
Free from substances that could impair the application of coating | according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard |
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV (Test Level 3) |
Standards/regulations | EN 61000-4-3 |
Frequency range | 80 MHz ... 3 GHz (Test Level 3) |
Standards/regulations | EN 61000-4-4 |
Comments | Criterion B |
Standards/regulations | EN 61000-4-5 |
Signal | ± 1 kV (Data line, asymmetrical) |
Standards/regulations | EN 61000-6-4 |
EN 61000-4-6 | |
Frequency range | 0.15 MHz ... 80 MHz |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 years |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 10.0.1 | 19170406 |
---|---|
eCl@ss 11.0 | 19170406 |
eCl@ss 4.0 | 27230200 |
eCl@ss 4.1 | 27230200 |
eCl@ss 5.0 | 19030100 |
eCl@ss 5.1 | 19030100 |
eCl@ss 6.0 | 19170100 |
eCl@ss 7.0 | 19170103 |
eCl@ss 9.0 | 19170103 |
ETIM 3.0 | EC000310 |
---|---|
ETIM 4.0 | EC000740 |
ETIM 5.0 | EC001478 |
ETIM 6.0 | EC001478 |
ETIM 7.0 | EC001478 |
UNSPSC 6.01 | 30211506 |
---|---|
UNSPSC 7.0901 | 39121008 |
UNSPSC 11 | 39121008 |
UNSPSC 12.01 | 39121008 |
UNSPSC 13.2 | 43222609 |
UNSPSC 18.0 | 43222609 |
UNSPSC 19.0 | 43222609 |
UNSPSC 20.0 | 43222609 |
UNSPSC 21.0 | 43222609 |