I/O extension module - RAD-DAIO6-IFS - 2901533

Radioline - I/O extension module, 2 digital inputs and outputs (0 ... 250 V AC/DC) and 1 analog input (0/4 ... 20 mA) and output (0/4 ... 20 mA, 0 ... 10 V)

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Application drawing  

Application drawing
Wireless module in I/O data mode

Application drawing  

Application drawing
Wireless module in PLC/Modbus RTU mode



Functional drawing  

Functional drawing
RAD-DAIO6-IFS assignment: analog/digital inputs and outputs

Dimensional drawing  

Dimensional drawing
Slim design



Circuit diagram  

Circuit diagram

Schematic diagram  

Schematic diagram
Function elements



Schematic diagram  

Schematic diagram
DIP switches

Schematic diagram  

Schematic diagram
Thumb wheel



Schematic diagram  

Schematic diagram
LED indicators

Back to top

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area
Use in potentially explosive areas is not permitted in China.
Back to top

Dimensions

Width 17.5 mm
Height 113 mm
Depth 114.5 mm
Dimensional drawing
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (>55°C derating)
-40 °F ... 158 °F (>131°F derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
-40 °F ... 185 °F
Permissible humidity (operation) 20 % ... 85 %
Permissible humidity (storage/transport) 20 % ... 85 %
Altitude 2000 m
Vibration (operation) in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Shock 16g, 11 ms
Back to top

General

Set consists of 2709561 ME 17,5 TBUS 1,5/ 5-ST-3,81 GN
Overvoltage category II
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Degree of pollution 2
Housing material PA 6.6-FR
Flammability rating according to UL 94 V0
MTTF 889 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
391 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
151 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
Weight 230 g
Back to top

Supply

Supply voltage range 19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption ≤ 95 mA (At 24 V DC, at 25°C)
Transient surge protection Yes
Back to top

Analog inputs

Number of inputs 1
Current input signal 0 mA ... 20 mA (can be set via DIP switches)
4 mA ... 20 mA (can be set via DIP switches)
Max. current input signal 22 mA
Input resistance current input < 70 Ω
Precision ≤ 0.02 % (at 25 °C)
Temperature coefficient, typical typ. 0.0025 %/K (at -40 °C ... +70 °C)
Supply voltage ≥ 12 V DC (For passive sensors (via terminal PWR1, +I1))
Resolution 16 bit
Protective circuit Short-circuit and overload protection
Back to top

Digital inputs

Description of the input Digital input
Number of inputs 2
Switching level "1" signal 10 V AC/DC ... 50 V AC/DC (Low-voltage input)
50 V AC/DC ... 250 V AC/DC (High-voltage input)
Switching level "0" signal 0 V AC/DC ... 4 V AC/DC (Low-voltage input)
0 V AC/DC ... 20 V AC/DC (High-voltage input)
Input frequency ≤ 2 Hz
Min. voltage input signal 0 V AC/DC
Max. voltage input signal 250 V AC/DC
Max. current consumption < 1 mA
Back to top

Analog outputs

Number of outputs 1
Voltage output signal 0 V ... 10 V
Max. voltage output signal approx. 10.83 V
Load ≥ 10 kΩ
Precision typ. 0.5 % (Voltage output)
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal approx. 21.67 mA
Load ≤ 500 Ω
Precision ≤ 0.02 % (at 25 °C)
Resolution 16 bit
Temperature coefficient, typical typ. 0.0025 %/K (at -40 °C ... +70 °C)
Protective circuit Transient protection of outputs
Back to top

Digital outputs

Number of outputs 2
Contact type Changeover contact
Contact material AgSnO2
Maximum switching voltage 250 V AC/DC
Min. switching current ≥ 10 mA
Max. switching current 2 A (per channel)
Mechanical service life 1x 107 cycles
Electrical service life 2x 105 cycles (At 2 A, 250 V AC, cosφ 0.4)
2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency 2 Hz
Switching capacity 120 W (24 V DC)
120 W (30 V DC)
20 W (48 V DC)
18 W (60 V DC)
22 W (110 V DC)
40 W (220 V DC)
42 W (250 V DC)
1250 VA
Behavior of the outputs (adjustable via DIP switch) Hold / Reset
Back to top

Electrical isolation

Digital I/O 300 V (Rated insulation voltage (in each case between the digital inputs // digital outputs // TBUS supply, reinforced insulation according to EN 61010))
Analog I/O 50 V (Rated insulation voltage (in each case between the analog inputs / analog outputs / TBUS supply, reinforced insulation according to EN 61010))
Digital/analog I/O 300 V (Rated insulation voltage (in each case between the digital inputs and outputs and between the analog inputs and outputs, reinforced insulation according to EN 61010))
Back to top

Test voltage

Digital I/O 2.5 kV AC (50 Hz, 1 min.)
Analog I/O 1.5 kV AC (50 Hz, 1 min.)
Back to top

Connection data

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Tightening torque 0.6 Nm
Screw thread M3
Back to top

Status indicator

Status display Green LED (supply voltage, PWR)
Green LED (bus communication, DAT)
Red LED (periphery error, ERR)
Yellow LED (digital input, DI1)
Yellow LED (digital input, DI2)
Yellow LED (digital output, DO1)
Yellow LED (digital output, DO2)
Back to top

Conformance/approvals

Designation CE
Identification CE-compliant
Designation EAC
Identification EAC
Designation ATEX
Identification  II 3 G Ex nA nC IIC T4 Gc
Certificate IBExU 15 ATEX B008 X
Additional text Please follow the special installation instructions in the documentation!
Designation IECEx
Identification Ex nA nC IIC T4 Gc
Certificate IECEx IBE 13.0019X
Designation EAC Ex
Identification 2Ex nA nC IIC T4 Gc X
Certificate RU C-DE.HB49.B.00033/20
Designation UL, USA/Canada
Identification 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, IIC T4
Designation Wireless approval South Korea, KC
Certificate R-R-PCK-2901533
Designation Corrosive gas test
Identification ISA-S71.04-1985 G3 Harsh Group A
Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Standards/specifications EMC Directive 2014/30/EU EN 61000-6-2
EMC Directive 2014/30/EU EN 61000-6-4
Ex Directive (ATEX) EN 60079-0
Ex Directive (ATEX) EN-60079-15
Flammability rating according to UL 94 V0
Shock 16g, 11 ms
Vibration (operation) in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz
Back to top

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Articles in set

DIN rail bus connectors ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561

DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.

Back to top

Classifications

eCl@ss

eCl@ss 10.0.1 27242602
eCl@ss 11.0 27242602
eCl@ss 4.0 27230200
eCl@ss 4.1 27230200
eCl@ss 5.0 27250600
eCl@ss 5.1 27242200
eCl@ss 6.0 27242600
eCl@ss 7.0 27242602
eCl@ss 9.0 27242602
Back to top

ETIM

ETIM 3.0 EC001423
ETIM 4.0 EC000310
ETIM 5.0 EC001597
ETIM 6.0 EC001597
ETIM 7.0 EC001597
Back to top

UNSPSC

UNSPSC 6.01 30211506
UNSPSC 7.0901 43223108
UNSPSC 11 39121008
UNSPSC 12.01 43223108
UNSPSC 13.2 43223108
UNSPSC 18.0 32151602
UNSPSC 19.0 32151602
UNSPSC 20.0 32151602
UNSPSC 21.0 32151602
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836
+65 6228 4900
  • Create PDF