Power supply unit - TRIO-PS/1AC/48DC/ 5 - 2866491

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 48 V DC/5 A

Price:

Overview

Technical data

Accessories

Approvals

Downloads

Drawings



Block diagram  

Block diagram

Back to top

Dimensions

Width 60 mm
Height 130 mm
Depth 152.5 mm
Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Back to top

Input data

Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz ... 65 Hz
Discharge current to PE < 3.5 mA
Current consumption 2.5 A (120 V AC)
1.3 A (230 V AC)
Nominal power consumption 282 VA
Inrush current < 15 A
Mains buffering time > 15 ms (120 V AC)
> 16 ms (230 V AC)
Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.96
Type of protection Transient surge protection
Protective circuit/component Varistor
Back to top

Output data

Nominal output voltage 48 V DC ±1 %
Setting range of the output voltage (USet) 30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (-25 °C ... 55 °C)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance 60 V DC
Protection against overvoltage at the output (OVP) < 60 V DC
Max. capacitive load unlimited
Active current limitation Approx 5.7 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP
Output power 240 W
Typical response time < 1 s
Peak switching voltages nominal load < 50 mVPP
Maximum power dissipation in no-load condition 7 W
Power loss nominal load max. 28 W
Back to top

General

Net weight 1.4 kg
Operating voltage display Green LED
Efficiency > 89 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Protection class I (with PE connection)
Degree of protection IP20
MTBF (IEC 61709, SN 29500)
> 1337000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Back to top

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Back to top

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Back to top

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Limitation of mains harmonic currents EN 61000-3-2
Rail applications EN 50121-4
Back to top

Conformance/approvals

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Back to top

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with LV directive 2006/95/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 6 kV (Test Level 3)
Discharge in air 8 kV (Test Level 3)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Surge voltage load (surge) EN 61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Voltage dips EN 61000-4-11
Back to top

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.0 27040700
eCl@ss 4.1 27040700
eCl@ss 5.0 27049000
eCl@ss 5.1 27049000
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701
Back to top

ETIM

ETIM 2.0 EC001039
ETIM 3.0 EC001039
ETIM 4.0 EC000599
ETIM 5.0 EC002540
ETIM 6.0 EC002540
ETIM 7.0 EC002540
Back to top

UNSPSC

UNSPSC 6.01 30211502
UNSPSC 7.0901 39121004
UNSPSC 11 39121004
UNSPSC 12.01 39121004
UNSPSC 13.2 39121004
Back to top

PHOENIX CONTACT
SEA Pte. Ltd.

105 Eunos Avenue 3
#04-00
Singapore 409836
+65 6228 4900
  • Create PDF
  • Recommend
  • Feedback